Plan Review Details - Permit 19050002
Plan Review Stops For Permit 19050002
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-03 Cont ID  
Sent By pvalenti Date 2019-07-03 Time 10:43 Rev Time 0.00
Received By pvalenti Date 2019-07-03 Time 10:43 Sent To  
Notes
2019-07-03 10:48:27***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED WITH PROVISO:
  
 AS PER PAGE ID-1001, NOTE #16, PROVIDE ENGINEER
 APPROVED SHORING PLAN PRIOR TO WORK IN SHORED AREAS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-24 Cont ID  
Sent By pvalenti Date 2019-05-24 Time 10:02 Rev Time 0.00
Received By pvalenti Date 2019-05-24 Time 07:35 Sent To  
Notes
2019-05-24 11:26:53***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1ST BUILDING REVIEW DENIED:
  
 1. FBC B 107.2.1 PROVIDE A LIFE SAFETY PLAN INCLUDING
 EGRESS REQUIREMENTS.
 2. FBC B 107.2.1 PROVIDE AN ADJUSTMENT TO PLAN DETAILS
 AND PERMIT APPLICATION. THE APPLICATION STATES THAT
 THIS PERMIT IS FOR INTERIOR AND EXTERIOR DEMOLITION AND
 THE PLAN PAGES INDICATE EXTERIOR WORK IS NOT INCLUDED.
 3. FBC B 105. PROVIDE A SEPERATE PERMIT APPLICATION FOR
 THE BUILDING OF DEMOED AREAS.
 4. FBC B 110.8 PROVIDE A THRESHOLD INSPECTOR DUE TO THE
 NATURE OF STRUCTURAL WORK PROPSED ON PAGE ID-002,
 KEYNOTE D02 OF SUBMITTED PLANS. PLEASE SEE THE
 REQUIREMENTS LISTED BELOW AS PER F.S. 553.79 FOR
 THRESHOLD BUILDINGS:
  
 THE FOLLOWING IS REQUIRED PRIOR TO COMMENCEMENT:
  
 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO
 CONTRACTOR.
  
 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS.
  
 3. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D). ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRESAFETY STANDARDS AS DETERMINED BY
 THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS CHAPTER 553
 AND CHAPTER 633.
  
 NOTE:
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.
2019-05-16 09:52:17PLANS EXAMINER, VERIFY INTERIOR ONLY & ASSURE PERMIT
 DESCRIPTION IS ACCURATE. IF EXTERIOR, ADD A ZONING
 REVIEW STOP.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-15 Cont ID  
Sent By jleahy Date 2019-07-15 Time 14:27 Rev Time 0.00
Received By jleahy Date 2019-07-15 Time 14:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-10 Cont ID  
Sent By jleahy Date 2019-05-10 Time 08:23 Rev Time 0.00
Received By jleahy Date 2019-05-10 Time 08:23 Sent To  
Notes
2019-05-10 08:32:03ELECTRICAL PERMIT REQUIRED JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-28 Cont ID  
Sent By pleduc Date 2019-06-28 Time   Rev Time 0.00
Received By pleduc Date 2019-06-28 Time 13:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-05-20 Cont ID  
Sent By pleduc Date 2019-05-20 Time   Rev Time 0.00
Received By pleduc Date 2019-05-20 Time 11:18 Sent To  
Notes
2019-05-20 11:37:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS THAT THE OCCUPANCY WILL
 REMAIN OPEN AND OCCUPIED DURING
 DEMOLITION/RECONSTRUCTION PERIODS.
  
 PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING THE
 MAINTENANCE/FREE AND CLEAR ACCESS OF ALL REQUIRED EXITS
 ON EACH FLOOR.
  
  
  
 2) THERE ARE NO INDICATIONS OF EXISTING FIRE ALARM AND
 FIRE SPRINKLER SYSTEMS.
  
 THESE SYSTSM SHALL BE MAINTAINED/FULLY FUNCTIONAL AT
 ALL TIMES DURING DEMOLITION AND RECONSTRUCNTION.
  
 ALL WORK ON ANY FIRE ALARM/FIRE SPRINKLER EQUIPMENT
 SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT
 AND COMPLIANCE.
  
  
  
 3) ALL DEMO SHEETS - UNDER THE DEMOLITION PLAN GENERAL
 NOTES, # 5 THERE IS AN INDICATION TO REFER TO FIRE
 PROTECTION DRAWINGS FOR EXTENT OF WORK.
  
 THERE IS NOT FIRE PROTECTION DRAWINGS ATTACHED.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-15 Cont ID  
Sent By jleahy Date 2019-07-15 Time 14:27 Rev Time 0.00
Received By jleahy Date 2019-06-26 Time 08:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-24 Cont ID  
Sent By pvalenti Date 2019-05-24 Time 11:33 Rev Time 0.00
Received By pvalenti Date 2019-05-07 Time 15:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-07-15 Cont ID  
Sent By jleahy Date 2019-07-15 Time 14:27 Rev Time 0.00
Received By jleahy Date 2019-07-15 Time 14:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-05-24 Cont ID  
Sent By pvalenti Date 2019-05-24 Time 11:27 Rev Time 0.00
Received By pvalenti Date 2019-05-24 Time 11:27 Sent To  
Notes
2019-05-24 11:30:51***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THE SIGNATURES WILL BE REVIEWED AGAIN ON THE NEXT ROUND
 AFTER ADDITIONAL DOCUMENTATION IS SUBMITTED.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2019-07-03 Cont ID  
Sent By pvalenti Date 2019-07-03 Time 10:42 Rev Time 0.00
Received By pvalenti Date 2019-07-03 Time 10:42 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2019-05-24 Cont ID  
Sent By pvalenti Date 2019-05-24 Time 11:33 Rev Time 0.00
Received By pvalenti Date 2019-05-24 Time 11:31 Sent To  
Notes
2019-05-24 11:33:27***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 553.79(5) 2016, THIS IS A THRESHOLD BUILDING. THE
 FOLLOWING IS REQUIRED PRIOR TO COMMENCEMENT:
  
 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO
 CONTRACTOR.
  
 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS.
  
 3. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D). ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRESAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS CHAPTER 553 AND
 CHAPTER 633.
  