Plan Review Details - Permit 19041509
Plan Review Stops For Permit 19041509
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-11 Cont ID  
Sent By shill Date 2019-07-11 Time 12:33 Rev Time 0.00
Received By shill Date 2019-07-11 Time 12:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-17 Cont ID  
Sent By shill Date 2019-05-17 Time 15:41 Rev Time 0.00
Received By shill Date 2019-05-17 Time 15:40 Sent To  
Notes
2019-05-17 15:43:38****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, SCOPE NOT CLEAR. PERMIT DESCRIPTION STATES
 SCOPE IS KITCHEN, A BATHROOM PLAN WAS ALSO PROVIDED,
 REVISE.
  
 2. FBC 107, PROVIDE A SITE PLAN AND OVERALL FLOOR PLAN
 SHOWING LOCATION OF PROPOSED IMPROVEMENT; THIS PARCEL
 APPEARS TO HAVE TWO STRUCTURES. FLOOR PLAN DOES NOT
 NEED TO BE THE ENTIRE HOUSE, BUT SHOULD SHOW LOCATION
 OF BATHROOM AND KITCHEN.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-11 Cont ID  
Sent By jpearson Date 2019-06-11 Time 14:48 Rev Time 0.00
Received By jpearson Date 2019-06-11 Time 14:47 Sent To B
Notes
2019-06-11 14:49:38TO MISC 2 BLDG BIN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By jpearson Date 2019-05-16 Time 11:11 Rev Time 0.00
Received By jpearson Date 2019-05-16 Time 10:32 Sent To  
Notes
2019-05-16 11:11:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. WPB FBC 107.2.1,
 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-11 Cont ID  
Sent By shill Date 2019-07-11 Time 12:33 Rev Time 0.00
Received By shill Date 2019-06-06 Time 13:40 Sent To  
Notes
2019-06-07 13:40:09RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-17 Cont ID  
Sent By shill Date 2019-05-17 Time 15:43 Rev Time 0.00
Received By shill Date 2019-04-30 Time 15:14 Sent To  
Notes
2019-05-01 15:14:58R03

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-05-02 Cont ID  
Sent By thunt Date 2019-05-02 Time 10:49 Rev Time 0.00
Received By thunt Date 2019-05-02 Time 10:49 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved