Plan Review Details - Permit 19041488
Plan Review Stops For Permit 19041488
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-06-05 Cont ID  
Sent By pvalenti Date 2019-06-05 Time 09:30 Rev Time 0.00
Received By pvalenti Date 2019-06-05 Time 08:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-05-15 Cont ID  
Sent By jleahy Date 2019-05-15 Time 16:55 Rev Time 0.00
Received By jleahy Date 2019-05-15 Time 16:55 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2019-07-08 Cont ID  
Sent By tklarge Date 2019-07-08 Time 11:42 Rev Time 0.00
Received By tklarge Date 2019-07-08 Time 06:51 Sent To  
Notes
2019-07-08 11:42:071) THE SUBMITTED GAS PLAN DOES NOT SHOW THE TOTAL BTU
 LOAD ON THIS SYSTEM PER CITY RECORDS. THE FOLLOWING GAS
 APPLIANCES ARE ALSO CONNECTED TO THIS SYSTEM AND MUST
 BE INCLUDED ON THE RISER DIAGRAM:
 A) FIREPLACE - 40,000 BTU'S
 B) STOVE - 60,000 BTU'S
 C) WATER HEATER - 35,000 BTU'S
 D) FIRE TABLE - 50,000 BTU'S
 TOTAL - 185,000 BTU'S
 2) THE POOL HEATER SHALL HAVE A THERMAL EFFICIENCY OF
 82% PER THE 2017 FBC-ENERGY SEC.R403.10.4. SUBMIT
 DOCUMENTAION.
 3) A VAPOR -RETARDANT POOL COVER OR A LIQUID COVER IS
 REQUIRED ON OR AT THE WATER SURFACE PER 2017 FBC-ENERGY
 SEC. R 403.10.3.
 4) THE GAS DRAWING REFERS TO ITRON REGULATORS. ARE THE
 EXISTING REGULATORS BEING REPLACED? IF SO, SUBMIT
 INSTALLATION INSTRUCTIONS AND MANUF. SPECIFICATIONS FOR
 THE REGULATORS. REGULATORS SHALL BE APPROVED FOR
 EXTERIOR USE. , 2017 FBC-RES. SEC. G2421.1.
 5) WHY IS THE GENERATOR BEING REMOVED IF THE PERMIT IS
 FOR A POOL? CLARIFY ON THE PLANS. WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2019-07-01 Cont ID  
Sent By thunt Date 2019-07-01 Time 09:11 Rev Time 0.00
Received By thunt Date 2019-07-01 Time 09:11 Sent To  
Notes
2019-07-01 09:13:34A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1.
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-06-19 Cont ID  
Sent By thunt Date 2019-06-19 Time 16:49 Rev Time 0.00
Received By thunt Date 2019-06-19 Time 16:49 Sent To  
Notes
2019-06-19 16:52:52GAS 2ND REVIEW**DENIED**
  
 YOU SUBMITTED A GAS PERMIT APPLICATION BUT NO GAS PLAN.
 PROVIDE A COMPLETE GAS ISOMETRIC DRAWING SHOWING ALL
 EXISTING BTU LOADS AND NEW LOAD'S. FBC 107.3.5
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2019-05-07 Cont ID  
Sent By thunt Date 2019-05-07 Time 11:52 Rev Time 0.00
Received By thunt Date 2019-05-07 Time 11:52 Sent To  
Notes
2019-05-07 11:53:00A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-07-08 Cont ID  
Sent By tklarge Date 2019-07-08 Time 11:44 Rev Time 0.00
Received By tklarge Date 2019-07-02 Time 14:48 Sent To  
Notes
2019-07-03 14:48:56RESUB ROUTED TO TKLARGE'S OFFICE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-01 Cont ID  
Sent By thunt Date 2019-07-01 Time 09:18 Rev Time 0.00
Received By thunt Date 2019-06-25 Time 11:38 Sent To  
Notes
2019-06-27 11:39:07RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-19 Cont ID  
Sent By thunt Date 2019-06-19 Time 16:53 Rev Time 0.00
Received By thunt Date 2019-06-14 Time 16:32 Sent To  
Notes
2019-06-17 16:32:31RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-05 Cont ID  
Sent By pvalenti Date 2019-06-05 Time 09:30 Rev Time 0.00
Received By pvalenti Date 2019-04-30 Time 15:15 Sent To  
Notes
2019-05-01 15:15:58ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-07-08 Cont ID  
Sent By tklarge Date 2019-07-08 Time 11:42 Rev Time 0.00
Received By tklarge Date 2019-07-08 Time 06:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-07-01 Cont ID  
Sent By thunt Date 2019-07-01 Time 09:18 Rev Time 0.00
Received By thunt Date 2019-07-01 Time 09:18 Sent To  
Notes
2019-07-01 09:18:47PLUMBING 3RD REVIEW8**DENIED**
  
 1) PROVIDE 2 COMPLETE SET OF PLANS. 2ND SET IS MISSING
 SHT.1 WITH BUILDING REVIEWER APPROVAL AND SHT 3 WITH
 ELC REVIEW APPROVAL. FBC 107.3.5
  
 2) REMOVE OR CROSS OUT ALL LEGENDS OR DETAILS ON ALL
 SHEETS THAT REFER TO SIMPLIFIED TDH. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-06-19 Cont ID  
Sent By thunt Date 2019-06-19 Time 16:40 Rev Time 0.00
Received By thunt Date 2019-06-19 Time 16:40 Sent To  
Notes
2019-06-19 16:48:33PLUMBING 2ND REVIEW**DENIED**
  
 1) THE SUBMITTED TDH CALCULATIONS DO NOT APPEAR TO SHOW
 THE FRICTION LOSS THROUGH ALL THE SYSTEM COMPONENTS.
 THE CALCULATOR SHOWS THE PIPE, FITTINGS, VALVES,
 HEATER, FILTER, ETC. BUT THERE IS NO FRICTION LOSS
 ASSOCIATED WITH THESE ITEMS. CLARIFY. FBC 107.2.1
  
 2) ALL NEW SUBMITTED SHEETS THAT BEAR R.GLORSKI
 PROFESSIONAL ENGINEER ARE REQUIRED TO BE WET SIGNED.
 COPIES ARE NOT PERMITTED. F.S 471
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-07 Cont ID  
Sent By thunt Date 2019-05-07 Time 11:53 Rev Time 0.00
Received By thunt Date 2019-05-07 Time 11:53 Sent To  
Notes
2019-05-07 11:58:42PLUMBING 1ST REVIEW**DENIED**
  
  
 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD
 CALCULATION IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS
 MUST INCLUDE ALL OF THE SYSTEM COMPONENTS INCLUDING
 SUCTION AND RETURN PIPING, FITTINGS, VALVES, HEATER,
 FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT
 THE PUMP.
  
 2) PROVIDE WHICH GAS POOL HEATER YOU ARE USING AND
 SUBMIT THE COMPLETE INSTALLATION MANUAL. PROPOSAL CALLS
 OUT FOR A 335,000 BTU HEATER, SHT #2 LIST HEATER AS
 400,00 BTU WHILE SHT #5 CALLS OUT 350,00 BTU. PLEASE
 CLARIFY. FBC 107.2.1
  
 3) ADD NOTE THAT A VAPOR-RETARDANT COVER TO LIMIT HEAT
 LOSS IS REQUIRED. 2017 FBC- ENERGY- SEC. R 403.10.3.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-05-06 Cont ID  
Sent By ajones Date 2019-05-06 Time 11:49 Rev Time 0.00
Received By ajones Date 2019-05-06 Time 11:49 Sent To  
Notes
***NONE***