| 2019-05-01 16:50:31 | GAS 1ST REVIEW**DENIED** |
| | |
| | |
| | 1) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 2) THE SIZING CHART YOU REFERANCE 402.4 (5) IS A 2LB |
| | WITH 1 POUND PRESSURE DROP LEAVING 27.67 IN W.C.. THIS |
| | IS ALMOST 3 TIMES MORE THEN THE DESIGNED PREESURE OF |
| | THE TANKLESS. PLEASE CLARIFY. FBC 107.2.1 |
| | |
| | 3) YOUR PLAN LIST INCOMING PRESSURE AS 10 PSI. SUBMIT |
| | MANUFACTURER?S SPECIFICATIONS FOR BOTH 1ST AND 2ND |
| | STAGEOF THE PRESSURE REGULATORS. REGULATORS INSTALLED |
| | ON THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR |
| | OUTDOOR INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. |
| | SEC. G2421.1. |
| | |
| | 4) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 5) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS |
| | REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT |
| | REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT |
| | BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE |
| | ON THE APPLICATION IN THE DESCRIPTION OF WORK. |
| | |
| | 6) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |
| | 7) . A RISER ISOMETRIC IS REQUIRED. PLEASE SHOW SHUTOFF |
| | VALVE AND DRIP LEG. FBC 107.3.5 |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | BUILDING DIVISION |