| Plan Review Stops For Permit 19041480 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-06-07 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-06-07 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-06-07 |
Time |
12:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-06-03 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-06-03 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-06-03 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2019-06-03 11:24:04 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 2ND BUILDING PLAN REVIEW DENIED: | | | | | | FBC B 107. | | | 1. PROVIDE 2ND SET OF SUBMITTED PLANS/DETAILS. | | | 2. PROVIDE DESIGN PROFESSIONAL SIGNATURES ON SUBMITTED | | | PLANS/DETAILS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-05-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-05-09 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-05-13 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2019-05-13 15:58:46 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 19041480 | | | REVIEWED: MAY 13, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | | | | 1) 3306.6 BARRIER DESIGN. PLEASE PROVIDE DETAILS OF | | | BARRIER: | | | BARRIER HEIGHT (3306.5 BARRIERS), POST TYPE, POST | | | DEPTH, METHOD OF INSTALL, LOCATION OF ACCESS POINTS AND | | | GATE POST DETAILS. | | | | | | 2) 3306.1 PROTECTION REQUIRED. AT WHAT POINT IN | | | CONSTRUCTION WILL PHASE TWO BE IMPLEMENTED? | | | ENGINEERING DEPARTMENT WILL NEED TO APPROVE ALL WORK | | | THAT INVOLVES RIGHT OF WAY. CONTACT ENGINEERING AT | | | 561-494-1040 FOR MORE INFO. | | | | | | NOTES: | | | | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-05-31 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-05-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-05-31 |
Time |
14:58 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-05-09 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-05-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-05-09 |
Time |
10:48 |
Sent To |
B |
|
| Notes |
| 2019-05-09 10:55:04 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THERE ARE NO INDICATIONS OF FIRE DEPARTMENT | | | ACCESS/GATES. A 20' FIRE LANE ACCESS WIDTH IS REQUIRED | | | FOR SITE ACCESS. | | | | | | PER NFPA 1 | | | | | | 18.2.3 FIRE DEPARTMENT ACCESS ROADS. | | | 18.2.3.1 REQUIRED ACCESS. | | | 18.2.3.1.1 APPROVED FIRE DEPARTMENT ACCESS ROADS SHALL | | | BE PROVIDED | | | FOR EVERY FACILITY, BUILDING, OR PORTION OF A BUILDING | | | HEREAFTER | | | CONSTRUCTED OR RELOCATED. | | | 18.2.3.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL CONSIST | | | OF ROADWAYS, FIRE | | | LANES, PARKING LOT LANES, OR A COMBINATION THEREOF. | | | | | | 18.2.3.4.1 DIMENSIONS. | | | 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN | | | UNOBSTRUCTED | | | WIDTH OF NOT LESS THAN 20 FT (6.1 M). | | | | | | | | | PLEASE REVIEW AND PROVIDE LOCATION(S) | | | | | | | | | 2) IT IS HIGHLY RECOMMENDED THAT THESE GATES BE | | | PROVIDED WITH A KNOX PADLOCK FOR EMERGENCY INCIDENT | | | ACCESS SHOULD THE GATE BE LOCAKED AT ANY TIME. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-06-07 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-06-07 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-06-07 |
Time |
12:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-06-03 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-06-03 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-05-15 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2019-05-30 11:44:02 | ROUTED FROM ZONING TO PERMIT LIBRARIAN 5/30/19 EL | | 2019-05-16 14:35:58 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-05-13 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-05-13 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-04-29 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2019-05-03 16:37:13 | ROUTED FROM ZONING TO PERMIT LIBRARIAN 5/3/2019 EL | | 2019-04-30 14:02:30 | ROUTED TO FIRE INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-05-30 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
2019-05-22 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2019-05-30 |
Time |
11:43 |
Sent To |
FIRE |
|
| Notes |
| 2019-05-30 11:43:42 | PROVISOS: | | | 1. PHASE II NOT TO BE INSTALLED UNTIL ROW PERMIT IS | | | PAID FOR IN FULL | | | | | | 2. NO MORE THAN 200 SF OF RENDERING/PROJECT INFO ON | | | FENCE SCREEN PER STREET FRONTAGE | | | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | | 561 822 1426 | | | [email protected] | | 2019-05-22 10:58:31 | MEETING WITH APPLICANT ON 5/30/19 EL |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-05-03 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
2019-05-03 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2019-05-03 |
Time |
16:33 |
Sent To |
FIRE |
|
| Notes |
| 2019-05-03 16:36:57 | SECTION 94-316: NO TEMPORARY CONSTRUCTION FENCE MAY BE | | | ERECTED UNTIL A SITE PLAN DEPICTING THE MATERIALS, | | | LOCATION AND ACCESS GATES HAS BEEN APPROVED AS PART OF | | | THE FENCE PERMIT ISSUANCE. | | | | | | PLEASE PROVIDE INFORMATION ON FENCE MATERIAL AND | | | LOCATION OF ACCESS GATES. | | | | | | SCREENING DETAILS SHALL BE SUBMITTED WITH THE TEMPORARY | | | CONSTRUCTION FENCE PERMIT APPLICATION. WIND SCREENING | | | SHALL BE SUBSTANTIAL ENOUGH TO AVOID RIPS OR TEARS DUE | | | TO WIND OR SUN, AND SHALL HAVE NO LESS THAN 85 PERCENT | | | OPACITY. | | | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | | [email protected] | | | | | | |
|
|