| 2019-05-02 07:20:40 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION (FAULT |
| | CURRENT) FOR BOTH 600AMP SERVICES INCLUDING INFORMATION |
| | OF SHORT CIRCUIT CURRENT FROM POWER COMPANY. NEC 110.9, |
| | 110.10 |
| | |
| | 2. PROVIDE LOCATION OF TRANSFORMER AND APPROX DISTANCE |
| | AWAY FROM SERVICE. FBC 107.2.1 |
| | |
| | 3. IF YOU WISH TO DE-RATE GROUNDED CONDUCTOR (NEUTRAL) |
| | PROVIDE LOAD CALCULATION FOR NEUTRAL SHOWING MAXIMUN |
| | UNBALANCED LOAD NEUTRAL COULD BE EXPOSED TO. FBC |
| | 107.2.1 NEC 220 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |