Plan Review Details - Permit 19041454
Plan Review Stops For Permit 19041454
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-06-14 Cont ID  
Sent By pvalenti Date 2021-06-14 Time 10:07 Rev Time 0.00
Received By pvalenti Date 2021-06-14 Time 09:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-01-24 Cont ID  
Sent By pvalenti Date 2020-01-24 Time 14:10 Rev Time 0.00
Received By pvalenti Date 2020-01-24 Time 14:10 Sent To  
Notes
2020-01-24 14:12:28***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
  
 1.THIS PROPERTY HAS EXPIRED PERMITS, PLEASE ADDRESS.
  
 2. THE STRUCTURAL DETAIL FOR THE GENERATOR
 ANCHORING, FBC 1609 INCLUDING THE WIND DESIGN
 CRITERIA NEEDS TO BE SIGNED AND SAELED BY THE ENGINEER
 OF RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-04 Cont ID  
Sent By shill Date 2019-06-04 Time 17:32 Rev Time 0.00
Received By shill Date 2019-06-04 Time 17:32 Sent To  
Notes
2019-06-04 17:32:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THIS PROPERTY HAS EXPIRED PERMITS, PLEASE ADDRESS.
  
 2. PROVIDE A STRUCTURAL DETAIL FOR THE GENERATOR
 ANCHORING, FBC 1609. THIS SHOULD BE PREPARED BY A
 DESIGN PROFESSIONAL AND SHOULD INCLUDE WIND DESIGN
 CRITERIA.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-06-14 Cont ID  
Sent By jleahy Date 2021-06-14 Time 16:07 Rev Time 0.00
Received By jleahy Date 2021-06-01 Time 14:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-01-21 Cont ID  
Sent By jleahy Date 2020-01-21 Time 14:23 Rev Time 0.00
Received By jleahy Date 2020-01-21 Time 14:23 Sent To G
Notes
2020-01-21 14:24:03PLANS HAVE TWO (2) PAGE E-1 PLEASE REMOVE THE ONE WE
 ARE NOT TO USE FOR THIS PERMIT JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By jleahy Date 2019-05-16 Time 10:45 Rev Time 0.00
Received By jleahy Date 2019-05-16 Time 10:45 Sent To  
Notes
2019-05-16 10:48:09FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 600 KCMIL CAN NOT FEED A 600A BREAKER OR SWITCH
 TRANSFRER SWITCH
  
 600 KCMIL CAN NOT FEED A 400A BREAKER IN THE MAIN
  
 ANOTHER PAGE SHOWS 400 KCMIL WIRE PLEASE CHECK RISER
 DIAGRAM FOR MISTAKES

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-05-27 Cont ID  
Sent By pleduc Date 2021-05-27 Time   Rev Time 0.00
Received By pleduc Date 2021-05-26 Time 13:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-14 Cont ID  
Sent By pleduc Date 2020-01-14 Time   Rev Time 0.00
Received By pleduc Date 2020-01-14 Time 12:20 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By pleduc Date 2019-06-05 Time   Rev Time 0.00
Received By pleduc Date 2019-06-05 Time 10:27 Sent To I
Notes
2019-06-05 10:33:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF WHAT THIS GENERATOR WILL
 PROVIDE POWER TO; THE ENTIRE BUILDING, INCLUDING ALL
 LIFE SAFETY EQUIPMENT AND SYSTEMS?
  
 PLEASE PROVIDE A DESCRIPTION OF POWER SERVICE
  
  
 1A) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY
 FIRE PREVENTION CODE.
  
 THE INSTALL SHALL COMPLY WITH NFPA 37 STANDARD FOR THE
 INSTALLATION AND USE OF STATIONARY COMBUSTION ENGINES
 AND GAS TURBINES 2015 EDITION AND NFPA 110 STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS2013 EDITION
  
 PLEASE REVIEW , ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE.
  
  
  
 2) THERE IS INSUFFICIENT DETAIL INDICATED FOR THE
 LOCATION, BOTH DIMENSIONS FROM THE BUILDING AND ALSO
 FROM WALL OPENINGS.
  
 PLEASE PROVIDE SPECIFIC DETAILS, LOCATIONS AND
 DIMENSIONS.
  
  
 3) THERE ARE NO INDICATIONS OF THE FOUNDATION AND/OR
 HOLD DOWN DETAILS
  
 PLEASE PROVIDE DETAILS.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-07-26 Cont ID  
Sent By lcrespo Date 2021-07-26 Time 11:34 Rev Time 0.00
Received By lcrespo Date 2021-07-26 Time 11:34 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-06-15 Cont ID  
Sent By tklarge Date 2021-06-15 Time 06:55 Rev Time 0.00
Received By tklarge Date 2021-06-15 Time 06:07 Sent To  
Notes
2021-06-15 06:37:251) THE GAS DRAWING SHOWS THE 2 PSI LINE GOING TO THE
 EXISTING KITCHEN. HOW WILL THE EXISTING APPLIANCES BE
 PROTECTED FROM OVERPRESSURE? WILL EACH APPLIANCE BE
 PROTECTED WITH A REGULATOR OR WILL ONE REGULATOR BE
 INSTALLED ON THE LINE TO THE KITCHEN? CLEARLY SHOW ON
 THE PLANAS TO WHAT WILL BE DONE.
 2) A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH REGULATOR. FBC-FUEL GAS
 SEC.409.4.
 3) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP
 REGULATOR. FBC-FUEL GAS SEC. 410.2 (7).2ND REQUEST.
 4) A REGULATOR, SHUTOFF VALVE AND UNION IS REQUIRED AT
 THE BOILER.FBC-FUEL GAS SEC.409.4, FBC-FUEL GAS SEC.
 410.2 (7), 410.1.
 5) SUBMIT A PIPING DETAIL FOR THE PIPING AT THE
 GENERATORS.WPB AMEND. TO FBC SEC. 107.2.1.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE
 REGULATORS.REGULATORS SHALL BE APPROVED FOR OUTDOOR
 USE. FBC-FUEL GAS SEC. 410.1.2ND REQUEST.
 7) SHOW THE DISTANCE FROM THE REGULATORS TOTHE FURTHEST
 OUTLET ON THE LOW PRESSURE SIDE OF EACH REGULAOR. THIS
 IS REQUIRED TO ENSURE CORRECT SIZING OF THE EXISTING
 SYSTEM. FBC-FUEL GAS SEC.401.3, 401.4.401.8.
 8) IDENTIFY ON THE REGULATOR SPECIFICATIONS WHICH
 REGULATOR MODEL IS BEING INSTALLED.THE REGULATOR SHALL
 BE CAPABLE OF HANDLING THE BTU LOAD OF THE APPLIANCE OR
 THE EQUIPMENT. 2017 FBC-FUEL GAS SEC.410.2 (3). 2ND
 REQUEST.
 9) IDENTIFY EACH APPLIANCE IN THE KITCHEN AND THE
 CORRESPONDING BTU LOAD. WPB AMEND. TO FBC SEC. 107.2.1.
 10) PLACE THE ENTIRE BTU LOAD OF THE SYSTEM ON THE
 PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-01-22 Cont ID  
Sent By tklarge Date 2020-01-22 Time 11:23 Rev Time 0.00
Received By tklarge Date 2020-01-22 Time 05:27 Sent To  
Notes
2020-01-22 10:45:351) THE GAS RISER SHOWS A DISTANCE OF 150 FEET FROM THE
 GAS METER TO THE GENERATOR. ON THE GAS SIZING TABLE FOR
 THE METALLIC PIPING THE 150 FEET ROW IS HIGHLIGHTED BUT
 ON THE PE SIZING TABLE THE 80 FEET ROW IS HIGHLIGHTED.
 WHERE ARE YOU GETTING THIS 80 FEET FROM? THE 150 FEET
 ROW MUST BE USED FOR SIZING OF THE GAS SYSTEM. 2017
 FBC-FUEL GAS SEC.402.4.1.
 2) THE GAS RISER AND GENERATOR SPECIFICATIONS CALL OUT
 THE BTU LOAD OF THE GENERATOR AS OVER ONE MILLION BTU'S
 YET THE SIZING TABLES FOR THE PE AND METALLIC PIPING AT
 150 FEET CAN ONLY CARRY 860 BTU'S AND 751 BTU'S
 RESPECTIVELY. CLARIFY. WPB AMEND.TO FBC SEC. 107.2.1,
 TABLES 402.4 (5), 402.4(22).
 3) SUBMIT TWO COPIES OF THE SIZING TABLE FOR THE LOW
 PRESSURE SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1, 2017
 FBC-FUEL GAS SEC.402.3.
 4) WHERE CONNECTED TO RIDGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN ONE FOOT OF EITHER SIDE OF THE MP
 REGULAROR. 410.2 (7).
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MP
 REGULATOR. REGULAOTRS SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION.
 6) IDENTIFY ON THE REGULATOR SPECIFICATIONS WHICH
 REGULATOR MODEL IS BEING INSTALLED. THE REGULATOR SHALL
 BE CAPABLE OF HANDLING THE BTU LOAD OF THE APPLIANCE OR
 THE THE EQUIPMENT. 2017 FBC-FUEL GAS SEC.410.2 (3).
 7) CITY RECORDS SHOW THAT THERE IS AN EXISTING GAS
 WATER HEATER AT THIS LOCATION. THE BTU LOAD OF THE
 EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU
 LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. FGC SECS. 401.4, 401.8, 402.1, 402.2,
 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-05-02 Cont ID  
Sent By thunt Date 2019-05-02 Time 13:51 Rev Time 0.00
Received By thunt Date 2019-05-02 Time 12:40 Sent To  
Notes
2019-05-02 13:51:43GAS 1ST REVIEW**DENIED**EMAILED TOYA TO DISCUSS
  
 I AM NOT ABLE TO PERFORM A THOROUGH REVIEW AT THIS
 TIME. YOUR PLAN LIST INSTALLATION MANUALS/
 SPECIFICATION FOR FOR 3 DIFFERENT KW GENERATORS AND 1
 DIESEL 80 KW ( 60,70,80, 80 DIESEL) YOUR GAS ISOMETRIC
 SHOWS 60KW 925BTU'S WITH 150' 3/4 P.E BUT SIZING CHART
 PROVIDED IS HIGHLIGHT @ 80' AND THE 2ND SIZING CHART
 PROVIDED IS 2LB SCH 40 PIPE HIGHLIGHTED @ 150' BUT NO
 METAL PIPE IS SHOWN ON PLAN
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-26 Cont ID  
Sent By lcrespo Date 2021-07-26 Time 11:35 Rev Time 0.00
Received By lcrespo Date 2021-07-15 Time 07:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-07-14 Cont ID  
Sent By medwards Date 2021-07-14 Time 07:46 Rev Time 0.00
Received By medwards Date 2021-05-25 Time 13:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-24 Cont ID  
Sent By pvalenti Date 2020-01-24 Time 14:16 Rev Time 0.00
Received By pvalenti Date 2020-01-08 Time 14:09 Sent To  
Notes
2020-01-09 14:09:48RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-05 Cont ID  
Sent By pleduc Date 2019-06-05 Time 10:33 Rev Time 0.00
Received By cpuell Date 2019-04-29 Time 13:22 Sent To  
Notes
2019-06-04 17:33:14TO FIRE
  
2019-04-30 13:22:13ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-07-26 Cont ID  
Sent By lcrespo Date 2021-07-26 Time 11:34 Rev Time 0.00
Received By lcrespo Date 2021-07-26 Time 11:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-07-26 Cont ID  
Sent By lcrespo Date 2021-07-26 Time 11:34 Rev Time 0.00
Received By lcrespo Date 2021-07-26 Time 11:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-21 Cont ID  
Sent By jgomez Date 2021-06-21 Time 13:33 Rev Time 0.00
Received By jgomez Date 2021-06-21 Time 13:32 Sent To  
Notes
2021-06-21 13:35:33THE (25KW GENERATOR PAD SUBMITTAL) WITH ENGINEER'S
 EMBOSSED SEAL AND ORIGINAL SIGNATURE MATCHES APPROVED
 ONE. JG.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-14 Cont ID  
Sent By pvalenti Date 2021-06-14 Time 10:08 Rev Time 0.00
Received By pvalenti Date 2021-06-14 Time 10:08 Sent To  
Notes
2021-06-14 16:17:13ELECTRICAL PLAN NOT SIGNED JLEAHY
2021-06-14 10:13:18PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SIGNATURE REVIEW DENIED:
  
 THE (25KW GENERATOR PAD SUBMITTAL) NEEDS TO BE
 DIGITALLY (3RD PARTY VERIFIED) SIGNED/SEALED OR HAND
 SIGNED/SEALED AS PER NOTES BELOW.
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD/EMAIL A DIGITALLY SIGNED (THIRD PARTY VERIFIED)
 PLAN OR YOU CAN MAIL/HAND DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 401 CLEMATIS STREET
 P.O. BOX 3147
 WEST PALM BEACH, FL 33402
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES/BUILDING DEPT.
 561 805 6673
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-07-13 Cont ID  
Sent By ajones Date 2021-07-13 Time 13:59 Rev Time 0.00
Received By ajones Date 2021-07-13 Time 13:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-05-01 Cont ID  
Sent By mcruz Date 2019-05-01 Time 17:01 Rev Time 0.00
Received By mcruz Date 2019-05-01 Time 16:58 Sent To  
Notes
***NONE***