| Plan Review Stops For Permit 19041454 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2021-06-14 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-06-14 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-06-14 |
Time |
09:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-01-24 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-24 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-24 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2020-01-24 14:12:28 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 2ND BUILDING REVIEW DENIED: | | | | | | | | | 1.THIS PROPERTY HAS EXPIRED PERMITS, PLEASE ADDRESS. | | | | | | 2. THE STRUCTURAL DETAIL FOR THE GENERATOR | | | ANCHORING, FBC 1609 INCLUDING THE WIND DESIGN | | | CRITERIA NEEDS TO BE SIGNED AND SAELED BY THE ENGINEER | | | OF RECORD. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-06-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-06-04 |
Time |
17:32 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-06-04 |
Time |
17:32 |
Sent To |
|
|
| Notes |
| 2019-06-04 17:32:57 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THIS PROPERTY HAS EXPIRED PERMITS, PLEASE ADDRESS. | | | | | | 2. PROVIDE A STRUCTURAL DETAIL FOR THE GENERATOR | | | ANCHORING, FBC 1609. THIS SHOULD BE PREPARED BY A | | | DESIGN PROFESSIONAL AND SHOULD INCLUDE WIND DESIGN | | | CRITERIA. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2021-06-14 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-06-14 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-06-01 |
Time |
14:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-01-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-01-21 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-01-21 |
Time |
14:23 |
Sent To |
G |
|
| Notes |
| 2020-01-21 14:24:03 | PLANS HAVE TWO (2) PAGE E-1 PLEASE REMOVE THE ONE WE | | | ARE NOT TO USE FOR THIS PERMIT JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-05-16 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-05-16 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-05-16 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2019-05-16 10:48:09 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 600 KCMIL CAN NOT FEED A 600A BREAKER OR SWITCH | | | TRANSFRER SWITCH | | | | | | 600 KCMIL CAN NOT FEED A 400A BREAKER IN THE MAIN | | | | | | ANOTHER PAGE SHOWS 400 KCMIL WIRE PLEASE CHECK RISER | | | DIAGRAM FOR MISTAKES |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2021-05-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-05-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-05-26 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2020-01-14 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-01-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-01-14 |
Time |
12:20 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-06-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-06-05 |
Time |
10:27 |
Sent To |
I |
|
| Notes |
| 2019-06-05 10:33:42 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE NO INDICATIONS OF WHAT THIS GENERATOR WILL | | | PROVIDE POWER TO; THE ENTIRE BUILDING, INCLUDING ALL | | | LIFE SAFETY EQUIPMENT AND SYSTEMS? | | | | | | PLEASE PROVIDE A DESCRIPTION OF POWER SERVICE | | | | | | | | | 1A) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY | | | FIRE PREVENTION CODE. | | | | | | THE INSTALL SHALL COMPLY WITH NFPA 37 STANDARD FOR THE | | | INSTALLATION AND USE OF STATIONARY COMBUSTION ENGINES | | | AND GAS TURBINES 2015 EDITION AND NFPA 110 STANDARD FOR | | | EMERGENCY AND STANDBY POWER SYSTEMS2013 EDITION | | | | | | PLEASE REVIEW , ENSURE COMPLIANCE AND PROVIDE AN | | | APPLICABLE NOTE. | | | | | | | | | | | | 2) THERE IS INSUFFICIENT DETAIL INDICATED FOR THE | | | LOCATION, BOTH DIMENSIONS FROM THE BUILDING AND ALSO | | | FROM WALL OPENINGS. | | | | | | PLEASE PROVIDE SPECIFIC DETAILS, LOCATIONS AND | | | DIMENSIONS. | | | | | | | | | 3) THERE ARE NO INDICATIONS OF THE FOUNDATION AND/OR | | | HOLD DOWN DETAILS | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2021-07-26 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-07-26 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-07-26 |
Time |
11:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2021-06-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2021-06-15 |
Time |
06:55 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2021-06-15 |
Time |
06:07 |
Sent To |
|
|
| Notes |
| 2021-06-15 06:37:25 | 1) THE GAS DRAWING SHOWS THE 2 PSI LINE GOING TO THE | | | EXISTING KITCHEN. HOW WILL THE EXISTING APPLIANCES BE | | | PROTECTED FROM OVERPRESSURE? WILL EACH APPLIANCE BE | | | PROTECTED WITH A REGULATOR OR WILL ONE REGULATOR BE | | | INSTALLED ON THE LINE TO THE KITCHEN? CLEARLY SHOW ON | | | THE PLANAS TO WHAT WILL BE DONE. | | | 2) A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH REGULATOR. FBC-FUEL GAS | | | SEC.409.4. | | | 3) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE | | | INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP | | | REGULATOR. FBC-FUEL GAS SEC. 410.2 (7).2ND REQUEST. | | | 4) A REGULATOR, SHUTOFF VALVE AND UNION IS REQUIRED AT | | | THE BOILER.FBC-FUEL GAS SEC.409.4, FBC-FUEL GAS SEC. | | | 410.2 (7), 410.1. | | | 5) SUBMIT A PIPING DETAIL FOR THE PIPING AT THE | | | GENERATORS.WPB AMEND. TO FBC SEC. 107.2.1. | | | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE PRESSURE | | | REGULATORS.REGULATORS SHALL BE APPROVED FOR OUTDOOR | | | USE. FBC-FUEL GAS SEC. 410.1.2ND REQUEST. | | | 7) SHOW THE DISTANCE FROM THE REGULATORS TOTHE FURTHEST | | | OUTLET ON THE LOW PRESSURE SIDE OF EACH REGULAOR. THIS | | | IS REQUIRED TO ENSURE CORRECT SIZING OF THE EXISTING | | | SYSTEM. FBC-FUEL GAS SEC.401.3, 401.4.401.8. | | | 8) IDENTIFY ON THE REGULATOR SPECIFICATIONS WHICH | | | REGULATOR MODEL IS BEING INSTALLED.THE REGULATOR SHALL | | | BE CAPABLE OF HANDLING THE BTU LOAD OF THE APPLIANCE OR | | | THE EQUIPMENT. 2017 FBC-FUEL GAS SEC.410.2 (3). 2ND | | | REQUEST. | | | 9) IDENTIFY EACH APPLIANCE IN THE KITCHEN AND THE | | | CORRESPONDING BTU LOAD. WPB AMEND. TO FBC SEC. 107.2.1. | | | 10) PLACE THE ENTIRE BTU LOAD OF THE SYSTEM ON THE | | | PLANS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-01-22 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-01-22 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-01-22 |
Time |
05:27 |
Sent To |
|
|
| Notes |
| 2020-01-22 10:45:35 | 1) THE GAS RISER SHOWS A DISTANCE OF 150 FEET FROM THE | | | GAS METER TO THE GENERATOR. ON THE GAS SIZING TABLE FOR | | | THE METALLIC PIPING THE 150 FEET ROW IS HIGHLIGHTED BUT | | | ON THE PE SIZING TABLE THE 80 FEET ROW IS HIGHLIGHTED. | | | WHERE ARE YOU GETTING THIS 80 FEET FROM? THE 150 FEET | | | ROW MUST BE USED FOR SIZING OF THE GAS SYSTEM. 2017 | | | FBC-FUEL GAS SEC.402.4.1. | | | 2) THE GAS RISER AND GENERATOR SPECIFICATIONS CALL OUT | | | THE BTU LOAD OF THE GENERATOR AS OVER ONE MILLION BTU'S | | | YET THE SIZING TABLES FOR THE PE AND METALLIC PIPING AT | | | 150 FEET CAN ONLY CARRY 860 BTU'S AND 751 BTU'S | | | RESPECTIVELY. CLARIFY. WPB AMEND.TO FBC SEC. 107.2.1, | | | TABLES 402.4 (5), 402.4(22). | | | 3) SUBMIT TWO COPIES OF THE SIZING TABLE FOR THE LOW | | | PRESSURE SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1, 2017 | | | FBC-FUEL GAS SEC.402.3. | | | 4) WHERE CONNECTED TO RIDGID PIPING, A UNION SHALL BE | | | INSTALLED WITHIN ONE FOOT OF EITHER SIDE OF THE MP | | | REGULAROR. 410.2 (7). | | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MP | | | REGULATOR. REGULAOTRS SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. | | | 6) IDENTIFY ON THE REGULATOR SPECIFICATIONS WHICH | | | REGULATOR MODEL IS BEING INSTALLED. THE REGULATOR SHALL | | | BE CAPABLE OF HANDLING THE BTU LOAD OF THE APPLIANCE OR | | | THE THE EQUIPMENT. 2017 FBC-FUEL GAS SEC.410.2 (3). | | | 7) CITY RECORDS SHOW THAT THERE IS AN EXISTING GAS | | | WATER HEATER AT THIS LOCATION. THE BTU LOAD OF THE | | | EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU | | | LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS | | | PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST | | | BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A | | | GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF | | | EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE | | | PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE | | | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT | | | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF | | | THE SECTION. FGC SECS. 401.4, 401.8, 402.1, 402.2, | | | 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2, | | | G2413.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-05-02 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-05-02 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-05-02 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2019-05-02 13:51:43 | GAS 1ST REVIEW**DENIED**EMAILED TOYA TO DISCUSS | | | | | | I AM NOT ABLE TO PERFORM A THOROUGH REVIEW AT THIS | | | TIME. YOUR PLAN LIST INSTALLATION MANUALS/ | | | SPECIFICATION FOR FOR 3 DIFFERENT KW GENERATORS AND 1 | | | DIESEL 80 KW ( 60,70,80, 80 DIESEL) YOUR GAS ISOMETRIC | | | SHOWS 60KW 925BTU'S WITH 150' 3/4 P.E BUT SIZING CHART | | | PROVIDED IS HIGHLIGHT @ 80' AND THE 2ND SIZING CHART | | | PROVIDED IS 2LB SCH 40 PIPE HIGHLIGHTED @ 150' BUT NO | | | METAL PIPE IS SHOWN ON PLAN | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-07-26 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-07-26 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-07-15 |
Time |
07:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-07-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-14 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-25 |
Time |
13:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-01-24 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-24 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-08 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2020-01-09 14:09:48 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-06-05 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-04-29 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2019-06-04 17:33:14 | TO FIRE | | | | | 2019-04-30 13:22:13 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2021-07-26 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-07-26 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-07-26 |
Time |
11:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-07-26 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-07-26 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-07-26 |
Time |
11:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-06-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-06-21 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-06-21 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2021-06-21 13:35:33 | THE (25KW GENERATOR PAD SUBMITTAL) WITH ENGINEER'S | | | EMBOSSED SEAL AND ORIGINAL SIGNATURE MATCHES APPROVED | | | ONE. JG. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-06-14 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-06-14 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-06-14 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2021-06-14 16:17:13 | ELECTRICAL PLAN NOT SIGNED JLEAHY | | 2021-06-14 10:13:18 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | SIGNATURE REVIEW DENIED: | | | | | | THE (25KW GENERATOR PAD SUBMITTAL) NEEDS TO BE | | | DIGITALLY (3RD PARTY VERIFIED) SIGNED/SEALED OR HAND | | | SIGNED/SEALED AS PER NOTES BELOW. | | | | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | | UPLOAD/EMAIL A DIGITALLY SIGNED (THIRD PARTY VERIFIED) | | | PLAN OR YOU CAN MAIL/HAND DELIVER AN ORIGINAL | | | SIGNED/SEALED PAPER ORIGINAL TO: | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | 401 CLEMATIS STREET | | | P.O. BOX 3147 | | | WEST PALM BEACH, FL 33402 | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES/BUILDING DEPT. | | | 561 805 6673 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2021-07-13 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2021-07-13 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2021-07-13 |
Time |
13:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-05-01 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2019-05-01 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2019-05-01 |
Time |
16:58 |
Sent To |
|
|
| Notes |
|
|