Plan Review Details - Permit 19041425
Plan Review Stops For Permit 19041425
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-24 Cont ID  
Sent By cthroop Date 2019-07-24 Time 11:05 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 06:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-09 Cont ID  
Sent By cthroop Date 2019-05-09 Time 11:41 Rev Time 0.00
Received By cthroop Date 2019-05-01 Time 07:23 Sent To  
Notes
2019-05-09 11:49:57BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGNER OF RECORD TO REVIEW AND APPROVE PRODUCT
 APPROVALS. THIS DOES NOT REQUIRE DIGITAL SIGNATURE AND
 SEAL.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 2. OWNER/AGENT SHALL SIGN ENERGY SUBMITTAL.
  
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
  
 3. VALUE ADJUSTED FROM $145,000 TO $163,493 BASED ON
 THE ICC BUILDING VALUATION DATA PUBLISHED FEB. 2019. CT
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-15 Cont ID  
Sent By jpearson Date 2019-08-15 Time 09:54 Rev Time 0.00
Received By jpearson Date 2019-08-15 Time 09:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-24 Cont ID  
Sent By cthroop Date 2019-07-24 Time 11:09 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 06:52 Sent To  
Notes
2019-07-24 11:11:29ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ELECTRICAL PLAN REQUIRES A SIGNATURE FROM EITHER AN
 ELECTRICAL CONTRACTOR OR A DESIGN PROFESSIONAL.
  
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By cthroop Date 2019-05-14 Time 09:43 Rev Time 0.00
Received By cthroop Date 2019-05-01 Time 07:23 Sent To  
Notes
2019-05-14 10:09:21ELECTRIC PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THERE ARE TWO GENERAL NOTES ON PLAN PAGE E-1 THAT
 ARE NOT VALID. THE FIRST STATES THAT AN OVERHEAD
 SERVICE MIGHT BE INSTALLED INSTEAD OF THE PROPOSED
 UNDERGROUND. THE SECOND STATEMENT IS A NOTE ON THE
 ELECTRICAL RISER DIAGRAHM THAT STATES THE ELECTRICAL
 SUBCONTRACTOR MAY ADJUST RISER AND PANEL SCHEDULE FROM
 MINIMUM SHOWN. EITHER REMOVE THESE STATEMENTS OR ADD
 THE FOLLOWING: NO CHANGE SHALL BE MADE TO PERMITTED
 DOCUMENTS WITHOUT A REVISION REVIEWED AND APPROVED BY
 THE AUTHORITY HAVING JURISDICTION.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PROVIDE AIC RATING FROM UTILITY COMPANY.
 AIC RATING OF SERVICE DISCONNECT AND PANEL
 FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT.
 SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM
 FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT
 NOT LESS THAN 10,000 AMPERES. (110.9) - PROVIDED
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3
  
 3. SHOW SIZE OF BARE COPPER GROUNDING CONDUCTOR.
 PROVIDE DETAILS ON PLAN OF GROUNDING ELECTRODE SYSTEM
 AND WIRING. NEC 250.32; FBC RE E3607.3
  
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE.
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1
  
 5. CORRECT NOTE FOR ARCH-FAULT CIRCUTS TO INCLUDE
 KITCHEN.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC
 210.12; FBC RE E3902.16.
  
 6. PROVIDE COMPLIANCE NOTE FOR HIGH EFFICACY LAMPS.
 PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1.
  
 7. INSTALL A GFCI PROTECTED OUTLET AT REAR OF
 STRUCTURE.
 FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE E3903.3.
  
 8. DISHWASHER OUTLET SHALL BE GFCI PROTECTED.
 PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC 210.8(D);
 FBC RE E3902.10.
  
 9. GARAGE DOOR OPENER SHALL BE GFCI PROTECTED.
 GFCI PROTECTION IS REQUIRED FOR ALL OUTLETS IN GARAGE,
 INCLUDING THE GARAGE DOOR OPENER. PROVIDE CORRECTION.
 NEC 210.8; FBC RE E3902.2.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-21 Cont ID  
Sent By lmarchan Date 2019-08-21 Time 09:50 Rev Time 0.00
Received By lmarchan Date 2019-07-29 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-24 Cont ID  
Sent By cthroop Date 2019-07-24 Time 11:22 Rev Time 0.00
Received By cthroop Date 2019-06-25 Time 08:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-14 Cont ID  
Sent By shill Date 2019-05-14 Time 18:07 Rev Time 0.00
Received By shill Date 2019-04-29 Time 10:45 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-07-30 Cont ID  
Sent By lmarchan Date 2019-07-30 Time 09:07 Rev Time 0.00
Received By lmarchan Date 2019-07-26 Time 11:13 Sent To  
Notes
2019-07-30 09:07:52RECEIPT MU-2019-023455-000 - NO FEES DUE
2019-07-26 11:13:557/26/19 SENT TO IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By cthroop Date 2019-05-14 Time 10:09 Rev Time 0.00
Received By cthroop Date 2019-05-01 Time 07:23 Sent To  
Notes
2019-05-14 10:10:38IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-08-21 Cont ID  
Sent By cmontell Date 2019-08-20 Time   Rev Time 0.00
Received By cmontell Date 2019-08-21 Time 13:15 Sent To  
Notes
2019-08-20 14:23:54MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED FLEX SIZE ON PLAN PER FBC 107
  
 CHRIS MONTELLO
 561-805-6733

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-07-24 Cont ID  
Sent By cthroop Date 2019-07-24 Time 11:07 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 06:52 Sent To  
Notes
2019-07-24 11:09:39MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. MECHANICAL PLAN REQUIRES SIGNATURE BY EITHER A
 MECHANICAL CONTRACTOR OR A DESIGN PROFESSIONAL.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-13 Cont ID  
Sent By cthroop Date 2019-05-13 Time 15:12 Rev Time 0.00
Received By cthroop Date 2019-05-01 Time 07:23 Sent To  
Notes
2019-05-13 15:26:59MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE COPY OF MIAMI DADE NOA 15-0903.08 FOR
 EQUIPMENT TIE DOWN.
  
 2. PROVIDE DETAIL OF AH CONDENSATE DISPOSAL LINE.
 PROVIDE A CONDENSATE DISPOSAL PLAN- FBC R M1411.3
 M1411.3 CONDENSATE DISPOSAL.
 CONDENSATE FROM COOLING COILS AND EVAPORATORS SHALL BE
 CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE
 OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM
 HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT
 LESS THAN 1/8 UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (1-PERCENT SLOPE). CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A
 NUISANCE.
  
 3. PROVIDE DETAIL OF BATHROOM EXHAUST DUCTS.
 M1506.3 EXHAUST OPENINGS.
 AIR EXHAUST OPENINGS SHALL TERMINATE NOT LESS THAN 3
 FEET (914 MM) FROM PROPERTY LINES; 3 FEET (914 MM) FROM
 OPERABLE AND NON OPERABLE OPENINGS INTO THE BUILDING
 AND 10 FEET (3048 MM) FROM MECHANICAL AIR INTAKES
 EXCEPT WHERE THE OPENING IS LOCATED 3 FEET (914 MM)
 ABOVE THE AIR INTAKE. OPENINGS SHALL COMPLY WITH
 SECTIONS R303.5.2 AND R303.6.
  
 4. PROVIDE LOCKING PORT CAPS AT EXTERIOR CU.
 M1411.8 LOCKING ACCESS PORT CAPS.
 REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL
 BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR
 SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED
 ACCESS.
 EXCEPTION: NO LOCKING-TYPE TAMPER-RESISTANT CAPS ARE
 REQUIRED IF PORTS ARE LOCATED INSIDE THE CONDENSING
 UNIT CABINET.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-07-09 Cont ID  
Sent By jesmith Date 2019-07-09 Time 15:21 Rev Time 0.00
Received By jesmith Date 2019-07-09 Time 14:18 Sent To  
Notes
2019-07-09 15:21:19APPROVED
 SEE REDLINED COMMENTS ON PLAN SHEET S-1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-13 Cont ID  
Sent By thunt Date 2019-05-13 Time 10:41 Rev Time 0.00
Received By thunt Date 2019-05-13 Time 09:49 Sent To  
Notes
2019-05-13 10:41:48PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE LOCATION OF ACCESSIBLE SHUT OFF VALVES FOR
 THE STACK WASHER AND DRYER. FBC-RES P2903.9.3
  
 2) DISHWASHER SHALL NOT DIRECTLY CONNECT INTO THE
 SANITARY DRAINAGE SYSTEM. THE DISHWASHER DISCHARGE PIPE
 OR TUBING SHALL RISE TO THE UNDERSIDE OF THE COUNTER
 AND BE FASTENED OR OTHERWISE HELD IN THAT POSITION
 BEFORE CONNECTING TO THE HEAD OF THE FOOD-WASTE
 DISPOSER OR TO A WYE FITTING IN THE SINK TAILPIECE.
 FBC-RES P2717.2. APPROVED DIRECTIONAL-TYPE BRANCH
 FITTINGS SHALL BE INSTALLED IN FIXTURE TAILPIECES
 RECEIVING THE DISCHARGE FROM FOOD-WASTE DISPOSER UNITS
 OR DISHWASHERS.FBC-RES P2707.1
  
 3) PROVIDE NOTE ON PLANS THAT TUB/ SHOWER VALVES SHALL
 BE ASSE 1016 APPROVED. FBC-RES P 2708.4
  
 4) PROVIDE SHOWER PAN DETAIL. FBC-RES P2709.3
  
 5) PROVIDEWATER HEATER DISCHARGE DETAIL SHOWING RELIEF
 DISCHARGING INTO PAN. FBC-RES P2804.6.1 (5) AND PAN
 DRAIN WILL DISCHARGE TO THE OUTSIDE MIN 6" ABOVE GROUND
 SURFACE. FBC-RES P2801.6.2
  
 6) PROVIDE NOTE THAT ALL HOT WATER PIPING SHALL BE
 INSULATED MIN R-3 VALUE. FBC-ENERGY R403.5.3
  
 7) MIN E.F RATING OF WATER HEATER SHALL BE .97. YOUR
 R405-2017 FORM CALLS OUT ONLY .95. MOST MANUFACTURES
 HAVE GONE TO THE NEW UEF RATING SYSTEM WHICH THE MIN IS
 .92 UEF. FBC-ENERGY R403.5.6.2, C404.2.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-07-24 Cont ID  
Sent By cthroop Date 2019-07-24 Time 11:06 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 06:52 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-05-09 Cont ID  
Sent By cthroop Date 2019-05-09 Time 11:50 Rev Time 0.00
Received By cthroop Date 2019-05-01 Time 07:23 Sent To  
Notes
2019-05-09 11:52:13BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGNER OF RECORD TO REVIEW AND APPROVE PRODUCT
 APPROVALS. THIS DOES NOT REQUIRE DIGITAL SIGNATURE AND
 SEAL.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-08-29 Cont ID  
Sent By skennedy Date 2019-08-29 Time 13:18 Rev Time 0.00
Received By skennedy Date 2019-08-29 Time 13:18 Sent To  
Notes
2019-08-29 13:19:442ND REVIEW NOTES BELOW NOW COMPLIED WITH.
  
 ***PLEASE NOTE SOILS REPORT SIGNATURE RECEIVED
 07/26/2019 AND VERIFIED AS CONSISTANT WITH UPLOADED
 VERSION. S/S IS GOOD. ON FILE WITH APPLICATION IN
 LIBRARY.***
  
 1. COMPLIED, SEE NOTE ABOVE. CANNOT VERIFY ENGINEER'S
 SIGNATURE ON SOILS REPORT. REVIEW RESPONSE INDICATES A
 HARD COPY HAS BEEN PROVIDED. CANNOT LOCATE THIS HARD
 COPY. PROVIDE A HARD COPY OF THE SOILS REPORT WITH
 ORIGINAL SIGNATURE AND SEAL OF ENGINEER AT TIME OF
 PERMIT PICK-UP.
  
 2. COMPLIED, MECHANICAL & ELECTRIC ARE SIGNED BY
 CONTRACTOR OF RECORD. PLUMBING IS SIGNEG BY PE,
 ALTHOUGH SELF CERTIFIED, SEE ONE TIME EXCEPTION BELOW.
 MECHANICAL, ELECTRICAL AND PLUMBING PLANS REQUIRE
 EITHER A SIGNATURE FROM A CONTRACTOR OR SIGNATURE AND
 SEAL OF A DESIGN PROFESSIONAL.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 3. COMPLIED, SEE ONE TIME EXCEPTION, BELOW. PLAN PAGES
 A-1, S-1 & S-2 HAVE BEEN SIGNED AND SEALED BY A
 LICENSED PROFESSIONAL ENGINEER. THIS SIGNATURE AND SEAL
 HAS BEEN SELF CERTIFIED BY THE ENGINEER. PER FS
 668.003, PROFESSIONAL ENGINEER'S CANNOT SELF CERTIFIY
 THEIR SIGNATURE AND SEAL.
 PLEASE ACCEPT THIS AS NOTICE THAT THE BUILDING OFFICIAL
 HAS DECIDED TO ACCEPT THE ENGINEER'S SELF CERTIFIED
 SIGNATURE AND SEAL ON A ONE TIME BASIS. ENGINEER SHALL
 EMPLOY THE SERVICES OF A THIRD PARTY ENTITY TO CERTIFY
 THEIR SIGNATURE AND SEAL.
  
 FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-08-29 Cont ID  
Sent By lmarchan Date 2019-08-29 Time 09:22 Rev Time 0.00
Received By lmarchan Date 2019-08-29 Time 09:22 Sent To  
Notes
2019-08-29 09:23:02MECHANICAL, ELECTRICAL AND PLUMBING PLANS REQUIRE
 EITHER A SIGNATURE FROM A CONTRACTOR OR SIGNATURE AND
 SEAL OF A DESIGN PROFESSIONAL.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 REGARDING PLUMBING, DIGITAL SIGNATURE IS NOT ISSUED IN
 A MANNER WHICH IS ACCEPTABLE TO EITHER FBPE OR FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS. THIS TYPE OF SELF
 CERTIFICATION IS NOT INTENDED TO BE USED FOR
 PROFESSIONAL PURPOSES. THIRD PARTY CERTIFICATION IS
 REQUIRED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-07-24 Cont ID  
Sent By cthroop Date 2019-07-24 Time 11:12 Rev Time 0.00
Received By cthroop Date 2019-07-19 Time 06:52 Sent To  
Notes
2019-07-26 11:27:19***PLEASE NOTE SOILS REPORT SIGNATURE RECEIVED
 07/26/2019 AND VERIFIED AS CONSISTANT WITH UPLOADED
 VERSION. S/S IS GOOD. ON FILE WITH APPLICATION IN
 LIBRARY.***
2019-07-24 11:22:01BUILDING PLAN REVIEW - SIGNATURE AND SEAL
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CANNOT VERIFY ENGINEER'S SIGNATURE ON SOILS REPORT.
 REVIEW RESPONSE INDICATES A HARD COPY HAS BEEN
 PROVIDED. CANNOT LOCATE THIS HARD COPY. PROVIDE A HARD
 COPY OF THE SOILS REPORT WITH ORIGINAL SIGNATURE AND
 SEAL OF ENGINEER AT TIME OF PERMIT PICK-UP.
  
 2. MECHANICAL, ELECTRICAL AND PLUMBING PLANS REQUIRE
 EITHER A SIGNATURE FROM A CONTRACTOR OR SIGNATURE AND
 SEAL OF A DESIGN PROFESSIONAL.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 3. PLAN PAGES A-1, S-1 & S-2 HAVE BEEN SIGNED AND
 SEALED BY A LICENSED PROFESSIONAL ENGINEER. THIS
 SIGNATURE AND SEAL HAS BEEN SELF CERTIFIED BY THE
 ENGINEER. PER FS 668.003, PROFESSIONAL ENGINEER'S
 CANNOT SELF CERTIFIY THEIR SIGNATURE AND SEAL.
 PLEASE ACCEPT THIS AS NOTICE THAT THE BUILDING OFFICIAL
 HAS DECIDED TO ACCEPT THE ENGINEER'S SELF CERTIFIED
 SIGNATURE AND SEAL ON A ONE TIME BASIS. ENGINEER SHALL
 EMPLOY THE SERVICES OF A THIRD PARTY ENTITY TO CERTIFY
 THEIR SIGNATURE AND SEAL.
  
 FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
2019-07-09 14:17:38REGARDING PLUMBING, DIGITAL SIGNATURE IS NOT ISSUED IN
 A MANNER WHICH IS ACCEPTABLE TO EITHER FBPE OR FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS. THIS TYPE OF SELF
 CERTIFICATION IS NOT INTENDED TO BE USED FOR
 PROFESSIONAL PURPOSES. THIRD PARTY CERTIFICATION IS
 REQUIRED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-05-09 Cont ID  
Sent By cthroop Date 2019-05-09 Time 11:26 Rev Time 0.00
Received By cthroop Date 2019-05-01 Time 07:23 Sent To  
Notes
2019-05-09 11:30:18DIGITAL SIGNATURE REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ENGINEER'S SIGNATURE AND SEAL ON SOILS REPORT IS
 INVALID.
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 THE SUBMITTED DOCUMENT IS SIGNED AND SEALED AS A PAPER
 DOCUMENT, THERE IS NO ELECTRONIC SIGNATURE TO THIS
 DOCUMENT. THE ENGINEER HAS 2 OPTIONS, EITHER COMPLY
 WITH FLORIDA ADMINISTRATIVE CODE 61G15-23.005
 PROCEDURES FOR SIGNING AND SEALING ELECTRONICALLY
 TRANSMITTED PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS OR SUBMIT 1 ORIGINAL PAPER DOCUMENT SIGNED
 AND SEALED.
  
  
  
  
  
  
2019-04-29 10:45:024/29/19 DIGITALLY SIGNED COPY OF SURVEY LOCATED IN
 "SIGNATURES"

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-05 Cont ID  
Sent By awooten Date 2019-07-05 Time   Rev Time 0.00
Received By awooten Date 2019-07-05 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By awooten Date 2019-05-14 Time   Rev Time  
Received By awooten Date 2019-05-14 Time   Sent To  
Notes
2019-05-14 11:07:27****************************ZONING REVIEW
 FAILED************************
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE/BUILDING/IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 GROSS LOT SQUARE FOOTAGE MINUS
 BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
 ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 THE PROPOSED CONCRETE SLAB AND DRIVEWAY REQUIRE A
 SEPARATE PERMIT.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  