Plan Review Details - Permit 19041340
Plan Review Stops For Permit 19041340
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-21 Cont ID  
Sent By dbattles Date 2019-05-21 Time 09:59 Rev Time 0.00
Received By dbattles Date 2019-05-21 Time 09:58 Sent To  
Notes
2019-05-21 09:59:55ENERGY CALCULATIONS NEED TO BE SIGNED BY PREPARER AND
 OWNER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-06 Cont ID  
Sent By dbattles Date 2019-05-06 Time 13:45 Rev Time 0.00
Received By dbattles Date 2019-05-06 Time 12:50 Sent To  
Notes
2019-05-06 13:45:25****CORRECTIONS****
 W.P.B. PERMIT: 19041340
 REVIEWED: MAY 6, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.2.1FBC[AMENDED] ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  -PLEASE SIGN AND SEAL DRAWINGS
  
 2) 103.1.1.2 FBC[RE] THE BUILDINGS OWNER, THE OWNERS
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA
 STATUTES.
  -PLEASE HAVE THE PERSON WHO PRODUCED AND THE OWNER
 SIGN THE ENERGY CALCULATIONS.
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-29 Cont ID  
Sent By jpearson Date 2019-05-29 Time 10:43 Rev Time 0.00
Received By ppetty Date 2019-05-29 Time 10:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-15 Cont ID  
Sent By jpearson Date 2019-05-15 Time 15:54 Rev Time 0.00
Received By jpearson Date 2019-05-15 Time 12:55 Sent To  
Notes
2019-05-15 15:10:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
 2. PROVIDE NARRATIVE OF CHANGES FOR REVISION. CLOUDING
 THE WHOLE ELECTRICAL PLAN AS A REVISION WITH NO
 EXPLANATION IS NOT ACCEPTABLE. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2019-06-05 Cont ID  
Sent By gjohnson Date 2019-06-05 Time 15:14 Rev Time 0.00
Received By gjohnson Date 2019-06-05 Time 15:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2019-05-28 Cont ID  
Sent By gjohnson Date 2019-05-28 Time 18:53 Rev Time 0.00
Received By gjohnson Date 2019-05-28 Time 18:53 Sent To  
Notes
2019-05-28 19:33:423RD REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: IN ORDER TO GET THE GAS PLAN
 APPROVED I SUGGEST A MEETING PLEASE CONNECT ME TO SET
 UP TIME AND DATE SEE INFO BELOW.
  
 1. THE PLAN SHEETS SHALL MATCH SHT. P-1 SHOWS PE
 UNDERGROUND GAS PIPING SHT. G-1 SHOWS A DIFFERENT TYPE
 OF PIPING GMP IT ALSO DOES NOT SHOW FUTURE BBQ, THE
 WATER HEATER IS NOT SHOWN IN SAME LOCATION. PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT G-1 LIST THE SYSTEM AS LP GAS IS THIS CORRECT IF
 SO SHOW LOCATION OF LP TANK AND NOTE A SEPARATE PERMIT
 IS REQUIRED FOR THE LP TANK. PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 3. PLEASE PROVIDE AN ABBREVIATION LEGEND I DO NOT
 RECOGNIZE THESE GMP, IHWH, MBTUH, FUT. PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE CLARIFY ON PLAN IF PIPING IS RUNNING UNDER
 GROUND, GALVANIZED SHALL NOT BE BURIED DIRECTLY UNDER
 GROUND IT SHALL BE SLEEVED SHOW SLEEVE DETAIL ON PLAN.
 PER FBC RES G2415.11, G2415.11.1
  
 5. NOTE ON THE PLANPLUMBING AND GAS SHALL COMPLY WITH
 FLORIDA BUILDING CODE RESIDENTIAL 2017 6TH EDITION
  
 6. 2ND REQUEST SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
  
 7. 2ND REQUEST SHOW TANKLESS HEATER MOUNTED A MIN OF
 4FT FROM OPERABLE OPENING IN BUILDING. PER WPB AMEND TO
 FBC 107.2.1
  
 8. A DRIP LEG IS REQUIRED AT EACH APPLIANCES PLEASE
 SHOW ON PLAN. PER FBC RES G2419.4
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-05-17 Cont ID  
Sent By thunt Date 2019-05-17 Time 16:11 Rev Time 0.00
Received By gjohnson Date 2019-05-17 Time 16:10 Sent To  
Notes
2019-05-17 16:42:001ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH.
  
  
 1) A PARTIAL GAS PLAN HAS BEEN SUBMITTED WITH OUT A GAS
 PERMIT AGAIN. GAS PERMIT IS REQUIRED AND THE FOLLOWING
 COMMENTS BELOW NEED TO BE ADDRESSED. FBC 105.1
  
 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
  
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2
  
 6) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE RANGE/
 STOVE. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL
 GAS SEC.304.9.3 OR FBCR G2407.9.3.
  
 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 8) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 9) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 10) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 11) BOTH THE WATER HEATER AND STOVE HAS GAS PIPE TO
 THEM ON SHT. P-1 BUT ON SHT. E-1 ON THE PANEL SCHDULE
 IT CALLS FOR BOTH AS ELEC POWER. PLEASE CLEARIFY. FBC
 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By thunt Date 2019-04-30 Time 16:20 Rev Time 0.00
Received By thunt Date 2019-04-30 Time 16:20 Sent To  
Notes
2019-04-30 16:20:02GAS 1ST REVISION REVIEW**DENIED** NONE OF THE PLANS
 PROVIDE HAVE BEEN SIGN AND SEALED AS REQUIRED BY THE
 DESIGN PROFESSIONAL. 61G1-16.001 ARCHITECT?S AND
 INTERIOR DESIGNER?S SEAL. EACH ARCHITECT AND INTERIOR
 DESIGNER SHALL ACQUIRE A SEAL WITH WHICH SHE OR HE
 SHALL IDENTIFY ALL PLANS, SPECIFICATIONS OR REPORTS
 PREPARED OR ISSUED BY HER OR HIM AND FILED FOR PUBLIC
 RECORD. THE SEAL SHALL BE CAPABLE OF LEAVING A
 PERMANENT INK REPRESENTATION OR OTHER FORM OF EMBOSSING
 OR OPAQUE AND PERMANENT IMPRESSION, WHICH ALSO MAY BE
 COMPUTER GENERATED IMPRESSIONS, ON THE SURFACE OF
 PRINTS OR OTHER DUPLICATIONS OF DRAWINGS, AND, AS
 APPROPRIATE, UPON SPECIFICATION PAGES, AND OTHER
 ARTICLES OF SERVICE.
  
  
 A CHANGE IN THE VALUE OF WORK NEEDS TO BE ADJUSTED FOR
 THE REVISION CHANGES.
  
 1) A PARTIAL GAS PLAN HAS BEEN SUBMITTED WITH OUT A GAS
 PERMIT AGAIN. GAS PERMIT IS REQUIRED AND THE FOLLOWING
 COMMENTS BELOW NEED TO BE ADDRESSED. FBC 105.1
  
 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
  
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2
  
 6) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE RANGE/
 STOVE. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL
 GAS SEC.304.9.3 OR FBCR G2407.9.3.
  
 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 8) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 9) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 10) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 11) BOTH THE WATER HEATER AND STOVE HAS GAS PIPE TO
 THEM ON SHT. P-1 BUT ON SHT. E-1 ON THE PANEL SCHDULE
 IT CALLS FOR BOTH AS ELEC POWER. PLEASE CLEARIFY. FBC
 107.2.1
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-30 Cont ID  
Sent By cmontell Date 2019-06-05 Time 14:23 Rev Time 0.00
Received By cmontell Date 2019-05-30 Time 05:51 Sent To  
Notes
2019-05-16 15:27:01R02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-16 Cont ID  
Sent By lmarchan Date 2019-05-16 Time 15:26 Rev Time 0.00
Received By lmarchan Date 2019-04-25 Time 16:02 Sent To  
Notes
2019-04-26 16:03:09R02

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-05 Cont ID  
Sent By cmontell Date 2019-05-30 Time 05:50 Rev Time 0.00
Received By cmontell Date 2019-06-05 Time 14:22 Sent To  
Notes
2019-05-30 05:50:49 
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-25 Cont ID  
Sent By ccole Date 2019-05-25 Time 04:49 Rev Time 0.00
Received By cmontell Date 2019-05-25 Time 04:42 Sent To  
Notes
2019-05-25 04:49:03MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED RETURN IN MASTER BEDROOM PER 2017 - FLORIDA
 BUILDING CODE - RESIDENTIAL SEC. M1602.3 BALANCED
 RETURN AIR.
  
 CHRIS MONTELLO
 805-6733
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-05-28 Cont ID  
Sent By gjohnson Date 2019-05-28 Time 19:33 Rev Time 0.00
Received By gjohnson Date 2019-05-28 Time 19:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-05-17 Cont ID  
Sent By thunt Date 2019-05-17 Time 16:42 Rev Time 0.00
Received By gjohnson Date 2019-05-17 Time 09:01 Sent To  
Notes
2019-05-17 16:42:50SEE GAS COMMENTS

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By gjohnson Date 2019-04-30 Time 16:31 Rev Time 0.00
Received By thunt Date 2019-04-30 Time 16:31 Sent To  
Notes
2019-05-13 10:53:34SEE GAS COMMENTS