Plan Review Details - Permit 19041280
Plan Review Stops For Permit 19041280
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-16 Cont ID  
Sent By cthroop Date 2019-08-16 Time 13:34 Rev Time 0.00
Received By cthroop Date 2019-08-16 Time 08:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-17 Cont ID  
Sent By shill Date 2019-05-17 Time 15:15 Rev Time 0.00
Received By shill Date 2019-05-17 Time 15:15 Sent To  
Notes
2019-05-17 15:18:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, PROVIDE PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD FOR THE DOORS, WINDOWS.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-16 Cont ID  
Sent By cthroop Date 2019-08-16 Time 13:34 Rev Time 0.00
Received By cthroop Date 2019-08-16 Time 08:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-24 Cont ID  
Sent By jpearson Date 2019-07-24 Time 15:53 Rev Time 0.00
Received By jpearson Date 2019-07-24 Time 15:27 Sent To  
Notes
2019-07-24 15:36:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2 (NOT PROVIDED.)
 2. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1 (NOT PROVIDED.)
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3 (NOT PROVIDED.)
 4. NOTE 2 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14 (NOT PROVIDED.)
 5. BATH 1 AND BATH 2 SHOW CIRCUIT A-9 FEEDING THE
 LIGHTS AND RECEPTACLES IN BOTH BATHROOMS. THIS IS A
 CODE VIOLATION, PROVIDE CORRECTION. NEC 210.11(C)(3) ,
 FBC RE E3703.4 (NOT PROVIDED.)
 6. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET AND ADJACENT TO EACH
 BASIN. PROVIDE CORRECTION FOR BATH 1. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6 (NOT PROVIDED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By jpearson Date 2019-05-14 Time 10:10 Rev Time 0.00
Received By jpearson Date 2019-05-14 Time 08:41 Sent To  
Notes
2019-05-14 10:10:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
 2. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 4. NOTE 2 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 5. BATH 1 AND BATH 2 SHOW CIRCUIT A-9 FEEDING THE
 LIGHTS AND RECEPTACLES IN BOTH BATHROOMS. THIS IS A
 CODE VIOLATION, PROVIDE CORRECTION. NEC 210.11(C)(3) ,
 FBC RE E3703.4
 6. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET AND ADJACENT TO EACH
 BASIN. PROVIDE CORRECTION FOR BATH 1. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2019-04-26 Cont ID  
Sent By gjohnson Date 2019-04-26 Time 17:07 Rev Time 0.00
Received By gjohnson Date 2019-04-26 Time 17:07 Sent To  
Notes
2019-04-26 17:11:34GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-05-13 Cont ID  
Sent By aborngra Date 2019-05-13 Time 14:35 Rev Time 0.00
Received By aborngra Date 2019-05-09 Time 16:54 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-16 Cont ID  
Sent By cthroop Date 2019-08-16 Time 13:35 Rev Time 0.00
Received By cthroop Date 2019-08-15 Time 15:17 Sent To  
Notes
2019-08-15 15:17:49GIVEN TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-26 Cont ID  
Sent By skennedy Date 2019-07-26 Time 14:11 Rev Time 0.00
Received By skennedy Date 2019-07-10 Time 15:29 Sent To  
Notes
2019-07-11 15:30:16R15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-20 Cont ID  
Sent By hmoser Date 2019-05-20 Time 10:57 Rev Time 0.00
Received By hmoser Date 2019-04-24 Time 14:36 Sent To  
Notes
2019-05-17 15:37:36TO HM DESK
  
  
2019-04-25 14:36:37R09

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-08-16 Cont ID  
Sent By cthroop Date 2019-08-16 Time 13:35 Rev Time 0.00
Received By cthroop Date 2019-08-16 Time 08:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-20 Cont ID  
Sent By hmoser Date 2019-05-20 Time 10:57 Rev Time 0.00
Received By hmoser Date 2019-05-20 Time 09:51 Sent To I
Notes
2019-05-20 10:56:53PLAN DENIED
 1) SHOW SUPPLY DUCT SIZE FOR DEN ON PLAN. PER SECTION
 107 FBC 2017.
 2) SHOW RETURN AIR DUCT FOR DEN AND MASTER BEDROOM
 PER SECTION M1602.3 RESIDENTIAL CODE 2017
 3) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR
 THE DESIGN. 2017 CITY AMENDMENTS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-806-6676
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-16 Cont ID  
Sent By cthroop Date 2019-08-16 Time 13:35 Rev Time 0.00
Received By cthroop Date 2019-08-16 Time 08:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-04-26 Cont ID  
Sent By gjohnson Date 2019-04-26 Time 17:05 Rev Time 0.00
Received By gjohnson Date 2019-04-26 Time 16:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-05-17 Cont ID  
Sent By aborngra Date 2019-05-13 Time 14:33 Rev Time 0.00
Received By aborngra Date 2019-05-13 Time 14:33 Sent To PC
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved