Plan Review Details - Permit 19041276
Plan Review Stops For Permit 19041276
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-10-23 Cont ID  
Sent By cthroop Date 2019-10-23 Time 13:41 Rev Time 0.00
Received By cthroop Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-10-11 Cont ID  
Sent By cthroop Date 2019-10-11 Time 13:54 Rev Time 0.00
Received By cthroop Date 2019-10-11 Time 13:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-07-30 Cont ID  
Sent By cthroop Date 2019-07-30 Time 17:02 Rev Time 0.00
Received By cthroop Date 2019-07-30 Time 17:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-06-28 Cont ID  
Sent By pvalenti Date 2019-06-28 Time 14:47 Rev Time 0.00
Received By pvalenti Date 2019-06-28 Time 14:47 Sent To  
Notes
2019-06-28 15:08:33***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING REVIEW DENIED:
  
 1. FBC B 107. RESUBMIT ENERGY CALCULATIONS (PROVIDE
 OWNER SIGNATURE ON FLORIDA ENERGY EFFICIENCY CODE FOR
 BUILDINGCONSTRUCTION).
  
 2. FBC B 107. RESUBMIT:PLANS (PROVIDE THE ARCHITECTS
 SIGNATURE AND SEAL ON REVISED SHEETS A-1 AND A-2).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-20 Cont ID  
Sent By shill Date 2019-05-20 Time 18:23 Rev Time 0.00
Received By shill Date 2019-05-20 Time 17:57 Sent To  
Notes
2019-05-20 18:23:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC EC R502, ALSO SEE DEFINITION OF ADDITION, REVISE
 PLAN TO SHOW COMPLIANCE, AND PROVIDE ENERGY CALCS OR
 SHOW COMPLIANCE WITH PRESCRIPTIVE REQUIREMENTS FOR
 BUILDING ENVELOPE.
  
 2. FBC 107, PROVIDE CEILING HEIGHT AND BUILDING SECTION
 TO CLARIFY CEILING CONSTRUCTION AND PROPOSED
 INSULATION.
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2019-10-23 Cont ID  
Sent By jpearson Date 2019-10-23 Time 13:32 Rev Time 0.00
Received By jpearson Date 2019-10-23 Time 13:32 Sent To  
Notes
2019-10-23 13:32:24DESIGN PROFESSIONAL CALLED, SEE PERMIT 19070338.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-07-25 Cont ID  
Sent By jpearson Date 2019-07-25 Time 10:00 Rev Time 0.00
Received By jpearson Date 2019-07-25 Time 10:00 Sent To  
Notes
2019-07-25 10:00:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481 (PLAN PROVIDED IS NOT
 SIGNED/SEALED.)
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 (IF PLAN
 SHOWS ELECTRICAL WORK, THIS IS REQUIRED.)
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1(NOT PROVIDED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-06-26 Cont ID  
Sent By jpearson Date 2019-06-26 Time 09:12 Rev Time 0.00
Received By jpearson Date 2019-06-26 Time 09:12 Sent To B
Notes
2019-06-26 08:58:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481 (PLAN PROVIDED IS NOT
 SIGNED/SEALED.)
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 (IF PLAN
 SHOWS ELECTRICAL WORK, THIS IS REQUIRED.)
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1(NOT PROVIDED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-15 Cont ID  
Sent By jpearson Date 2019-05-15 Time 12:43 Rev Time 0.00
Received By jpearson Date 2019-05-15 Time 12:43 Sent To  
Notes
2019-05-15 12:43:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 5 Status P Date 2019-10-23 Cont ID  
Sent By aborngra Date 2019-10-23 Time 08:52 Rev Time 0.00
Received By aborngra Date 2019-10-23 Time 08:52 Sent To B
Notes
2019-10-23 08:52:12THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
  
 1. ALL REPLACEMENT WINDOWS SHALL HAVE CLEAR GLASS OR
 CLEAR GLASS WITH LOW-E.
 2. ALL REPLACEMENT WINDOWS SHALL FIT THE ORIGINAL
 WINDOW FRAME SIZE.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected]
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2019-10-11 Cont ID  
Sent By aborngra Date 2019-10-11 Time 07:51 Rev Time 0.00
Received By aborngra Date 2019-10-11 Time 07:51 Sent To B
Notes
2019-10-11 07:51:16THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
  
 1. ALL REPLACEMENT WINDOWS SHALL HAVE CLEAR GLASS OR
 LOW-E GLASS.
 2. ALL REPLACEMENT WINDOWS SHALL FIT THE ORIGINAL
 WINDOW FRAME SIZE.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected]
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2019-07-16 Cont ID  
Sent By aborngra Date 2019-07-16 Time 15:04 Rev Time 0.00
Received By aborngra Date 2019-07-16 Time 14:54 Sent To PC
Notes
2019-07-16 14:55:06THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
  
 1. ALL REPLACEMENT WINDOWS SHALL HAVE CLEAR GLASS OR
 LOW-E GLASS.
 2. ALL REPLACEMENT WINDOWS SHALL FIT THE ORIGINAL
 WINDOW FRAME SIZE.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected]
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-06-25 Cont ID  
Sent By aborngra Date 2019-06-25 Time 09:56 Rev Time 0.00
Received By aborngra Date 2019-06-25 Time 09:56 Sent To E
Notes
2019-06-25 09:56:48THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
  
 1. ALL REPLACEMENT WINDOWS SHALL HAVE CLEAR GLASS OR
 LOW-E GLASS.
 2. ALL REPLACEMENT WINDOWS SHALL FIT THE ORIGINAL
 WINDOW FRAME SIZE.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected]
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-05-10 Cont ID  
Sent By aborngra Date 2019-05-10 Time 09:01 Rev Time 0.00
Received By aborngra Date 2019-05-10 Time 09:01 Sent To PC
Notes
2019-05-10 09:02:00THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
  
 1. ALL REPLACEMENT WINDOWS SHALL HAVE CLEAR GLASS OR
 LOW-E GLASS.
 2. ALL REPLACEMENT WINDOWS SHALL FIT THE ORIGINAL
 WINDOW FRAME SIZE.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected]
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-10-23 Cont ID  
Sent By cthroop Date 2019-10-23 Time 13:41 Rev Time 0.00
Received By cthroop Date 2019-10-21 Time 13:26 Sent To  
Notes
2019-10-22 13:26:28RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-10-11 Cont ID  
Sent By cthroop Date 2019-10-11 Time 13:54 Rev Time 0.00
Received By cthroop Date 2019-10-09 Time 13:46 Sent To  
Notes
2019-10-10 13:47:05ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-30 Cont ID  
Sent By cthroop Date 2019-07-30 Time 17:02 Rev Time 0.00
Received By cthroop Date 2019-07-10 Time 14:27 Sent To  
Notes
2019-07-11 14:27:51R22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-28 Cont ID  
Sent By pvalenti Date 2019-06-28 Time 15:08 Rev Time 0.00
Received By pvalenti Date 2019-06-20 Time 12:50 Sent To  
Notes
2019-06-24 12:50:27RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-21 Cont ID  
Sent By hmoser Date 2019-05-21 Time 10:15 Rev Time 0.00
Received By hmoser Date 2019-05-21 Time 09:59 Sent To  
Notes
2019-05-20 18:25:01TO HM DESK
  
  
2019-04-25 14:38:23R28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-11-01 Cont ID  
Sent By cthroop Date 2019-11-01 Time 14:39 Rev Time 0.00
Received By cthroop Date 2019-11-01 Time 14:36 Sent To  
Notes
2019-11-01 14:40:04MU-2019-033702-0000. CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-05-20 Cont ID  
Sent By shill Date 2019-05-20 Time 17:55 Rev Time 0.00
Received By shill Date 2019-05-20 Time 17:55 Sent To  
Notes
2019-05-20 17:56:54IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-07-22 Cont ID  
Sent By cmontell Date 2019-07-22 Time 14:28 Rev Time 0.00
Received By cmontell Date 2019-07-22 Time 14:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2019-05-21 Cont ID  
Sent By hmoser Date 2019-05-21 Time 10:15 Rev Time 0.00
Received By hmoser Date 2019-05-21 Time 10:12 Sent To I
Notes
2019-05-21 10:15:24PLAN CALLS FOR WALL UNIT FOR A/C PERMIT NOT REQUIRED
 HM.

Review Stop P PLUMBING
Rev No 2 Status N Date 2019-07-18 Cont ID  
Sent By lcrespo Date 2019-07-18 Time 16:22 Rev Time 0.00
Received By lcrespo Date 2019-07-18 Time 16:22 Sent To  
Notes
2019-07-18 16:26:01PLUMBING PERMITTED UNDER 18101016 THIS PERMIT IS
 APPROVED, PLAN REQUIRED TO BE ON JOBSITE FOR
 INSPECTIONS, HEATER IF ELECTRIC MAY NOT BE OUTSIDE PER
 MANUFACTURES SPECIFICATION UNLESS IT MADE FOR OUTSIDE
 ELEMENTS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2019-06-04 Cont ID  
Sent By gjohnson Date 2019-04-26 Time 16:34 Rev Time 0.00
Received By gjohnson Date 2019-04-26 Time 16:19 Sent To  
Notes
2019-04-26 16:50:46PLUMBING PERMITTED UNDER 18101016 PLAN REQUIRED TO BE
 ON JOBSITE FOR INSPECTIONS
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2019-05-10 Cont ID  
Sent By aborngra Date 2019-05-10 Time 08:59 Rev Time 0.00
Received By aborngra Date 2019-05-10 Time 08:59 Sent To PC
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy