2019-04-29 09:32:42PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE HOW THE SYSTEM WAS SIZED AND IS IN
 COMPLIANCE WITH EITHER PDI G101, PDI G102, OR FAC
 64E-6. FBC-P 1003.3.4
  
 2) AAV'S ARE NOT PERMITTED AS IT ALLOWS THE TANK TO
 BECOME AIR BOUND AND THE MANUFACTURE ALSO CALLS FOR A
 INTAKE VENT TO BE REVENTED TOGETHER AND VENT TO THE
 OUTDOORS. FBC 1003.2, 1003.9
  
 3) P-TRAP, INLET, OUTLET, AND HORIZONTAL BRANCH SHALL
 BE MIN 3". EACH OF THE COMPARTMENTS IS 2 DFU'S AND THE
 HAND SINK IS ANOTHER 2DFU'S TOTALING 8 DFU'S.MAX DFU'S
 PERMITTED ON 2" IS 6. FBC-P 710.1
  
 4) IS THIS INTERCEPTOR TO BE INSTALLED ABOVE OR BELOW
 GROUND? FBC 107.2.1
  
  