Plan Review Details - Permit 19041261
Plan Review Stops For Permit 19041261
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-29 Cont ID  
Sent By jwitmer Date 2019-07-29 Time 16:18 Rev Time 0.00
Received By jwitmer Date 2019-07-29 Time 15:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-06 Cont ID  
Sent By jwitmer Date 2019-05-06 Time 14:32 Rev Time 0.00
Received By jwitmer Date 2019-05-06 Time 13:15 Sent To  
Notes
2019-05-06 14:31:582017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19041261
 ADD: 415 50TH ST. / BUILDING #3 / (3) DWELLING UNITS
 CONT: PREMIER BUILDERS & DEVELOPMENT
 TEL: 561-891-1607
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MAY MON. 06/2019
 ACTION: DENIED
  
 1) THE COVERSHEET THE DESIGNER OF RECORD HAS NOT
 INDICATED AS TO WHICH METHOD THE PLANS WERE DEVELOPED
 UNDER THE 2017 FBC-EXISTING BUILDING CODE, SEE SECTION
 301.1. THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY,
 ADDITION OR RELOCATION OF ALL EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
 SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED
 IN COMBINATION WITH EACH OTHER.
  
 301.1.1 PRESCRIPTIVE COMPLIANCE METHOD.
  
 301.1.2 WORK AREA COMPLIANCE METHOD.
  
 301.1.3 PERFORMANCE COMPLIANCE METHOD.
  
 2) SHEET A1 :
  
 2A) UNDER THE HEADING OF GENERAL NOTE # 07 THE PLAN
 INDICATES WINDOW AND DOORS ARE TO BE REPLACED UNDER
 SEPARATE PERMIT, TO DATE NO PERMIT HAS BEEN APPLIED
 FOR. NOTE # 12 INDICATES THE EGRESS WINDOWS ARE LOCATED
 AS SHOWN PER FBC-R 310. THIS IS A 3 DWELLING UNIT
 BUILDING AND DOES NOT FALL UNDER THE 1 & 2 FAMILY
 RESIDENTIAL CODE. THIS BUILDING FALLS UNDER THE 2017
 FBC-B.
  
 2B) NOTE # 12 INDICATES THE EGRESS WINDOWS ARE LOCATED
 AS SHOWN PER FBC-R 310, PLEASE UPDATE PLAN NOTE FOR
 EGRESS WINDOWS MUST MEET THE REQUIREMENTS OF THE 2017
 FBC-B SECTION 1030 EMERGENCY ESCAPE AND RESCUE OPENINGS
 IN R-2 OCCUPANCIES.
 1030.2 MINIMUM SIZE
 1030.2.1 MINIMUM DIMENSIONS.
 1030.3 MAXIMUM HEIGHT FROM FLOOR.
 1030.4 OPERATIONAL CONSTRAINTS.
  
 2C) NOTE # 12 INDICATES THE EGRESS WINDOWS ARE TO BE
 SHOWN ON THE PLANS, THE EGRESS WINDOWS ARE NOT SHOWN.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2D) THERE IS A DETAIL FOR CBS WALL INFILL WITH WOOD
 FRAMING, 5/8 INCH PLYWOOD AND WIRE LATH AND STUCCO. THE
 FLOOR PLAN DOES NOT INDICATE WHERE THIS DETAIL IS TO BE
 USED. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2E) THERE IS A DETAIL FOR CBS WALL INFILL WITH WOOD
 FRAMING, 5/8 INCH PLYWOOD AND WIRE LATH AND STUCCO.
 THE DETAIL IS LACKING COMPLIANCE WITH 2017 FBC-B 2510.6
 WATER-RESISTIVE BARRIERS. WATER-RESISTIVE BARRIERS
 SHALL BE INSTALLED AS REQUIRED IN SECTION 1404.2 AND,
 WHERE APPLIED OVER WOOD-BASED SHEATHING, SHALL INCLUDE
 A WATER-RESISTIVE VAPOR-PERMEABLE BARRIER WITH A
 PERFORMANCE AT LEAST EQUIVALENT TO TWO LAYERS OF
 WATER-RESISTIVE BARRIER COMPLYING WITH ASTM E2556, TYPE
 I. THE INDIVIDUAL LAYERS SHALL BE INSTALLED
 INDEPENDENTLY SUCH THAT EACH LAYER PROVIDES A SEPARATE
 CONTINUOUS PLANE AND ANY FLASHING (INSTALLED IN
 ACCORDANCE WITH SECTION 1405.4) INTENDED TO DRAIN TO
 THE WATER-RESISTIVE BARRIER IS DIRECTED BETWEEN THE
 LAYERS.
  
 2F) THE PLAN SHOWS SEPARATION WALLS BETWEEN EACH OF THE
 DWELLING UNITS. STATED FROM THE PLAN: THE REPAIRS TO
 THE PARTY WALL MUST BE MADE WITH 5/8 INCH DRYWALL AND 3
 ? INCH BATT INSULATION.
  
 THESE WALLS WERE TO BE BUILT AS FIRE PARTITIONS, PLEASE
 PROVIDE THE WALL RATING AND ASSEMBLY FOR THIS WALL
 SYSTEM. THE 2017 FBC-B SECTION 708.3 FIRE RESISTANCE
 RATING. FIRE PARTITIONS SHALL HAVE A FIRE RESISTANCE
 RATING OF NOT LESS THAN 1 HOUR. PLEASE PROVIDE THE UL
 OR GYPSUM WALL ASSEMBLY.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-01-07 Cont ID  
Sent By ppetty Date 2021-01-07 Time 11:00 Rev Time 0.00
Received By ppetty Date 2021-01-07 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-09-24 Cont ID  
Sent By ppetty Date 2019-09-24 Time 12:36 Rev Time 0.00
Received By ppetty Date 2019-09-24 Time 12:36 Sent To  
Notes
2019-09-24 12:36:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.
 2.
 3.
 4.
 5.
 6.
 7.
 8. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-31 Cont ID  
Sent By ppetty Date 2019-07-31 Time 14:39 Rev Time 0.00
Received By ppetty Date 2019-07-31 Time 14:39 Sent To  
Notes
2019-07-31 14:38:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. ARE PANELS BEING
 REPLACED MAIN BREAKER OR MAIN LUG TYPE PANELS? PROVIDE
 CLARIFICATIONS. NEC 215.5, 230, 250.50, 250.94, 408.30
 2.
 3.
 4.
 5.
 6.
 7.
 8. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By jpearson Date 2019-05-16 Time 14:01 Rev Time 0.00
Received By jpearson Date 2019-05-16 Time 11:12 Sent To  
Notes
2019-05-16 14:01:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. ARE PANELS BEING
 REPLACED MAIN BREAKER OR MAIN LUG TYPE PANELS? PROVIDE
 CLARIFICATIONS. NEC 215.5, 230, 250.50, 250.94, 408.30
 2. KITCHENS REQUIRE A MINUMUM OF TWO SMALL APPLIANCE
 BRANCH CIRCUITS. PROVIDE CORRECTION. NEC 210.11(C)(1)
 3. PROVIDE ACCURATE LOAD CALCULATION. A MINUMUM OF TWO
 SMALL APPLIANCE BRANCH CIRCUITS ARE REQUIRED. NEC 220
 4. PANEL SCHEDULE FOR UNITS STATE THAT THE ELECTRICAL
 SERVICE IS 120/208 VOLT. LOAD CALCULATION STATES THE
 SERVICE IS 120/240 VOLT. CORRECT DISCREPANCY. WPB FBC
 107.2.1
 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 6. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 7. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
 8. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-18 Cont ID  
Sent By pleduc Date 2019-07-18 Time   Rev Time 0.00
Received By pleduc Date 2019-07-18 Time 15:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By pleduc Date 2019-05-16 Time   Rev Time 0.00
Received By pleduc Date 2019-05-16 Time 14:09 Sent To I
Notes
2019-05-16 14:10:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET CVR - THERE NO INDICATIONS OF COMPLIANCE WITH
 ANY FIRE CODE.
  
 THE PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF
 THE 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101.
  
 SPECIFICALLY, CH 31 EXISTING APARTMENT OCCUANCIES.
  
 PLEASE REVIEW NAD ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE OF CODE REFERENCE.
  
  
  
  
 2) SHEET A 1 - THE ARE REFERENCES TO EXISTING PARTY
 WALLS BETWEEN EACH UNIT(S).
  
 DO THESE PARTY WALLS HAVE A FIRE RATING? DO THEY GO ALL
 THE WAY TO THE UNDER SIDE OF THE ROOF SHEATHING?
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-07-23 Cont ID  
Sent By fmittner Date 2019-07-23 Time 16:06 Rev Time 0.00
Received By fmittner Date 2019-07-23 Time 16:06 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-05-14 Cont ID  
Sent By fmittner Date 2019-05-14 Time 15:00 Rev Time 0.00
Received By fmittner Date 2019-05-14 Time 14:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-01-07 Cont ID  
Sent By ppetty Date 2021-01-07 Time 11:01 Rev Time 0.00
Received By ppetty Date 2021-01-07 Time 11:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-24 Cont ID  
Sent By ppetty Date 2019-09-24 Time 12:36 Rev Time 0.00
Received By ppetty Date 2019-09-20 Time 14:58 Sent To  
Notes
2019-09-23 14:59:06RESUB ROUTED TO PPETTY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-06 Cont ID  
Sent By cmontell Date 2019-08-06 Time 14:14 Rev Time 0.00
Received By cmontell Date 2019-08-06 Time 14:14 Sent To  
Notes
2019-08-05 07:53:57TO CM DESK
  
2019-07-17 15:25:02B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By pleduc Date 2019-05-16 Time 14:10 Rev Time 0.00
Received By lmarchan Date 2019-04-24 Time 14:48 Sent To  
Notes
2019-04-25 14:48:56B06

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-08-06 Cont ID  
Sent By cmontell Date 2019-08-06 Time 14:14 Rev Time 0.00
Received By cmontell Date 2019-08-06 Time 14:14 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-06 Cont ID  
Sent By ccole Date 2019-05-06 Time 12:13 Rev Time 0.00
Received By ccole Date 2019-05-06 Time 11:59 Sent To  
Notes
2019-05-06 12:18:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19041261
 5/6/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE NOTE THERE ARE NO WPB BUILDING DEPARTMENT
 RECORDS OF LEGALLY PERMITTED AC SYSTEMS BEING INSTALLED
 AT THE APARTMENTS. REFER TO SECTION C503.2 FBC EC- FULL
 COMPLIANCE WITH THE ENERGY CODE IS REQUIRED, WHICH
 MEANS THAT THE FORM R402 MUST BE COMPLETELY FILLED OUT
 AND THREE PAGES ARE MISSING. PLEASE REVIEW THE "SCOPE"
 OF THE FORM LISTED IN THE TOP PRAGRAPH. IN ADDITION,
 PLEASE NOTE THAT THE ENERGY FORM R402 AND THE AC
 CALCULATIONS MUST BE SIGNED BY THE PERSON WHO PREPARED
 THE FORM AND THE OWNER/AGENT- SECTION R103.1.1.2 FBC
 EC.
  
 2) SHEET M/P1: PROVIDE AC DUCT LAYOUT PLANS SHOWING
 DUCT RUNS, DUCT SIZES, AND RETURNS. PLEASE NOTE THAT
 ALTHOUGH THE PLAN IS INDICATING EXISTING DUCTWORK,
 THERE ARE NO WPB BUILDING DEPARTMENT RECORDS OF ANY
 PRIOR DUCT INSTALLATIONS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-01 Cont ID  
Sent By jesmith Date 2019-08-01 Time 16:21 Rev Time 0.00
Received By jesmith Date 2019-08-01 Time 16:21 Sent To  
Notes
2019-08-01 16:21:24PLUMBING COMMEMTS: APPROVED WITH PROVISO
 1. SUBMIT AS DEFERRED SUBMITTALS, SEE WPB FBC
 107.3.4.1, STORAGE TYPE WATER HEATER SPECS.SPECS SHALL
 BE SUBMITTED, APPROVED AND IN PLACE PRIOR TO FINAL
 PLUMBING INSPECTION.
 2. PER FBC PL 607.3, THERMAL EEXPANSION CONTROL SHALL
 BE PROVIDED FOR STORAGE TYPE WATER HEATERS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-05-02 Cont ID  
Sent By tklarge Date 2019-05-02 Time 14:48 Rev Time 0.00
Received By tklarge Date 2019-05-02 Time 14:23 Sent To  
Notes
***NONE***