Plan Review Details - Permit 19041166
Plan Review Stops For Permit 19041166
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-06-19 Cont ID  
Sent By thunt Date 2019-06-19 Time 15:07 Rev Time 0.00
Received By thunt Date 2019-06-19 Time 15:07 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-06-10 Cont ID  
Sent By thunt Date 2019-06-10 Time 14:19 Rev Time 0.00
Received By thunt Date 2019-06-10 Time 14:19 Sent To  
Notes
2019-06-10 14:19:28GAS 2ND REVIEW**DENIED**FL ST 553.80 (B)2B WITH RESPECT
 TO EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) 109.3 BUILDING PERMIT VALUATIONS. MASTER PERMIT #
 18050588 WAS NOT APPROVED FOR ANY GAS FIXTURE THEREFOR
 THE VALUE MUST INCLUDE THE COST DIFFERENCE FROM
 ELECTRIC TO GAS FOR THE TANKLESS WATER HEATER, DRYER,
 AND STOVE. THE OVEN, POOL HEATER AND BBQ MUST HAVE FULL
 VALUE LISTED AS THIS WAS NOT ON THE MASTER OR 1ST GAS
 PLAN SUBMITTED. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATIONOF BUILDING, ALTERATION,
 STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE.
  
 2) PROVIDE AVAILABLE COMBUSTIBLE AIR. YOU ONLY PROVIDE
 WHAT IS REQUIRED. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER THE 2017 FBC-FUEL GAS CODE SEC.304.1, 614.6
 (CLOTHES DRYERS) OR 2017 FBC-RES. SEC. G 2407.1 AND
 G2439.4 (CLOTHES DRYERS).
  
 3) PROVIDE AVAILABLE COMBUSTIBLE AIR. YOU ONLY PROVIDE
 WHAT IS REQUIRED. SUBMIT COMBUSTION AIR CALCULATIONS
 FOR THE STOVE. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL
 GAS SEC.304.9.3 OR FBCR G2407.9.3.
  
 4) PER PLAN PROVIDE THE PRESSURE REGULATOR IS DIRECTLY
 AFTER THE METER MAKING THIS A .5 LB SYSTEM THAT IS
 UNDERSIZED. INDICATE THE DELIVERY PRESSURE (PSI) OF THE
 SYSTEM ON THE PLAN PER 2017 FBC RES. SEC. G2413.2,
 G2413.4.3.
  
 5) **NONE PROVIDE AGAIN: SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. , FBC-RES. SEC.G2408.1.\
  
 6) **NONE PROVIDE AGAIN: SUBMIT TWO COPIES OF A HOUSE
 PLAN SHOWING THE LOCATION OF THE TANKLESS WATER HEATER
 AND THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 7) ANSWERD
  
 8) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR.FBC-RESIDENTIAL SEC. G
 2420.4.
  
 9) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD
  
 10) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 NEW COMMENT:
  
 11) THIS PLAN IS NOW SHOWING A BBQ GRILL. IS THIS UNDER
 A COVERED AREA? FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-24 Cont ID  
Sent By thunt Date 2019-04-24 Time 16:40 Rev Time 0.00
Received By thunt Date 2019-04-24 Time 16:28 Sent To  
Notes
2019-04-24 16:40:01GAS 1ST REVIEW**DENIED**
  
 1) 109.3 BUILDING PERMIT VALUATIONS. MASTER PERMIT #
 18050588 WAS NOT APPROVED FOR ANY GAS FIXTURE THEREFOR
 THE VALUE MY INCLUDE THE COST DIFFERENCE FROM ELECTRIC
 TO GAS FOR THE TANKLESS WATER HEATER, DRYER, AND STOVE.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATIONOF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT
 SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
  
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE STOVE.
 WHERE COMBUSTION AIR IS PROVIDED BY THE BUILDING?S
 MECHANICAL VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE
 THE SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. 2017 FBC-FUEL GAS SEC.304.9.3
 OR FBCR G2407.9.3.
  
 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 5) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. , FBC-RES. SEC.G2408.1.\
  
 6) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 7) YOU ONLY PROVIDE 1 SIZING TABLE BUT SHOW 3 DIFFERENT
 PIPING MATERIALS. SUBMIT TWO COPIES OF THE APPLICABLE
 SIZING TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A
 NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING
 TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE
 USED IN THE DESIGN OF THIS GAS SYSTEM. REFER TO THE
 2017 FBC-RES. SEC. G2413.3, G2412.8, G2413.1, G2413.2,
 & G2413
  
 8) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR.FBC-RESIDENTIAL SEC. G
 2420.4.
  
 9) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD
  
 10) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-19 Cont ID  
Sent By thunt Date 2019-06-19 Time 15:07 Rev Time 0.00
Received By thunt Date 2019-06-17 Time 14:39 Sent To  
Notes
2019-06-18 14:39:50RESUB ROTUED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-10 Cont ID  
Sent By thunt Date 2019-06-10 Time 14:21 Rev Time 0.00
Received By thunt Date 2019-06-06 Time 13:48 Sent To  
Notes
2019-06-07 13:48:28RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-24 Cont ID  
Sent By thunt Date 2019-04-24 Time 16:40 Rev Time 0.00
Received By thunt Date 2019-04-23 Time 13:57 Sent To  
Notes
2019-04-24 13:58:01PLUMB <5K