| 2019-06-10 14:19:28 | GAS 2ND REVIEW**DENIED**FL ST 553.80 (B)2B WITH RESPECT |
| | TO EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A |
| | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | 1) 109.3 BUILDING PERMIT VALUATIONS. MASTER PERMIT # |
| | 18050588 WAS NOT APPROVED FOR ANY GAS FIXTURE THEREFOR |
| | THE VALUE MUST INCLUDE THE COST DIFFERENCE FROM |
| | ELECTRIC TO GAS FOR THE TANKLESS WATER HEATER, DRYER, |
| | AND STOVE. THE OVEN, POOL HEATER AND BBQ MUST HAVE FULL |
| | VALUE LISTED AS THIS WAS NOT ON THE MASTER OR 1ST GAS |
| | PLAN SUBMITTED. IF, IN THE OPINION OF THE BUILDING |
| | OFFICIAL, THE CLAIMED VALUATIONOF BUILDING, ALTERATION, |
| | STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR PLUMBING |
| | SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE |
| | APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| | MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. |
| | |
| | 2) PROVIDE AVAILABLE COMBUSTIBLE AIR. YOU ONLY PROVIDE |
| | WHAT IS REQUIRED. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR PER THE 2017 FBC-FUEL GAS CODE SEC.304.1, 614.6 |
| | (CLOTHES DRYERS) OR 2017 FBC-RES. SEC. G 2407.1 AND |
| | G2439.4 (CLOTHES DRYERS). |
| | |
| | 3) PROVIDE AVAILABLE COMBUSTIBLE AIR. YOU ONLY PROVIDE |
| | WHAT IS REQUIRED. SUBMIT COMBUSTION AIR CALCULATIONS |
| | FOR THE STOVE. WHERE COMBUSTION AIR IS PROVIDED BY THE |
| | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL |
| | GAS SEC.304.9.3 OR FBCR G2407.9.3. |
| | |
| | 4) PER PLAN PROVIDE THE PRESSURE REGULATOR IS DIRECTLY |
| | AFTER THE METER MAKING THIS A .5 LB SYSTEM THAT IS |
| | UNDERSIZED. INDICATE THE DELIVERY PRESSURE (PSI) OF THE |
| | SYSTEM ON THE PLAN PER 2017 FBC RES. SEC. G2413.2, |
| | G2413.4.3. |
| | |
| | 5) **NONE PROVIDE AGAIN: SUBMIT MANUFACTURER?S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| | THE TIME OF INSPECTION. , FBC-RES. SEC.G2408.1.\ |
| | |
| | 6) **NONE PROVIDE AGAIN: SUBMIT TWO COPIES OF A HOUSE |
| | PLAN SHOWING THE LOCATION OF THE TANKLESS WATER HEATER |
| | AND THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR |
| | WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION |
| | OF THE WATER HEATER SHALL COMPLY WITH THE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE |
| | PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 7) ANSWERD |
| | |
| | 8) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR.FBC-RESIDENTIAL SEC. G |
| | 2420.4. |
| | |
| | 9) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1 |
| | OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE |
| | PROPER PIPE SIZE AND BTU LOAD |
| | |
| | 10) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. |
| | |
| | NEW COMMENT: |
| | |
| | 11) THIS PLAN IS NOW SHOWING A BBQ GRILL. IS THIS UNDER |
| | A COVERED AREA? FBC 107.2.1 |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | [email protected] |
| | [email protected] |