| 2019-04-23 15:37:41 | PLUMBING 1ST REVIEW**DENIED**PROVIDE 2 COPIES FOR EACH |
| | PERMIT APPLICATION |
| | |
| | 1) PLANS THAT BEAR THE TITLE BLOCK OF A DESIGN |
| | PROFESSIONAL SHALL BE SIGNED AND SEALED. FAC |
| | 61G1-16.001 |
| | |
| | 2) PLAN DOES NOT SHOW PIPE SIZE OF MAIN LINE OR GPM |
| | REQUIREMENTS ON THE SYSTEM. FBC 107.2.1 |
| | |
| | 3) CITY RECORD DO NOT SHOW AN EXISTING PERMITTED |
| | BACKFLOW OR IRRAGATION SYSTMEM. PROVIDE THE BACKFLOW |
| | MAKE, MODEL , AND SIZE. IS THIS A SEPERATE IRRAGATION |
| | METER FEEDING THIS SYSTEM? PLEASE CLARIFY. FBC 107.3.5. |
| | WPB CROSS CONNECTION MANUAL. |
| | |
| | 4) VALUE SEEMS LOW. PROVIDE A BONA FIDE SIGNED |
| | CONTRACT. 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE |
| | OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION |
| | OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS |
| | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE |
| | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION |
| | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE |
| | |