Plan Review Details - Permit 19041096
Plan Review Stops For Permit 19041096
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-03-10 Cont ID  
Sent By jbrooks Date 2020-03-10 Time 07:50 Rev Time 0.00
Received By jbrooks Date 2020-03-10 Time 07:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-12-17 Cont ID  
Sent By jbrooks Date 2019-12-17 Time 08:44 Rev Time 0.00
Received By jbrooks Date 2019-12-17 Time 08:44 Sent To  
Notes
2019-12-17 08:48:19JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1.FBC B 107.2.1. SUBMITTED MIAMI-DADE NOA 16-0808.14
 AND MIAMI-DADE NOA 18-1109.03 ARE BOTH UNDERLAYMENT?S
 USED IN A SLOPED ROOF SYSTEM. PROVIDE TWO SETS OF
 PRODUCT APPROVALS/NOAS FOR AN APPROVED ROOF ASSEMBLY
 FOR A FLAT WOOD DECK ASSEMBLY. ALL APPLICABLE DETAILS
 AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE
 PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. AS PER RULE 61G20-3. SECOND
 REQUEST.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-10-10 Cont ID  
Sent By jbrooks Date 2019-10-10 Time 09:29 Rev Time 0.00
Received By jbrooks Date 2019-10-10 Time 09:29 Sent To E
Notes
2019-10-10 09:29:40JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 YOU MAY RESUBMIT PRINTABLE DOCUMENTS ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1.FBC B 107.2.1. PLEASE PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION ON SUBMITTED DRAWINGS:
 CONSTRUCTION TYPE; OCCUPANCY GROUP; CLASSIFICATION OF
 WORK (ADDITION); BUILDING HEIGHT. SECOND REQUEST.
 2.FBC B 107.2.1 PROVIDE A DRAWING DETAIL SHOWING
 INTERSECTION OF NEW STORAGE ROOM ROOF WITH EXISTING
 LAUNDRY ROOM ROOF/WALL WITH FLASHING (IF APPLICABLE);
 ALONG WITH DRAWING DETAILS OF THE CONSTRUCTION METHOD
 USED OF MATING NEW STORAGE ROOM ROOF, WALLS, FOOTINGS,
 SLAB, COLUMNS AND BEAMS TO THE EXISTING RESIDENTIAL
 STRUCTURE. SECOND REQUEST.
 3.FBC B 107.2.1. REVISE ELEVATION DETAIL DRAWINGS TO
 SHOW EXISTING RESIDENTIAL STRUCTURE AND NEW PROPOSED
 STORAGE ROOM TOGETHER.
 4.FBC B 107.2.1. SUBMITTED MIAMI-DADE NOA 16-0808.14
 AND MIAMI-DADE NOA 18-1109.03 ARE BOTH UNDERLAYMENT?S;
 PROVIDE TWO SETS OF PRODUCT APPROVALS/NOA?S FOR AN
 APPROVED ROOF ASSEMBLY FOR A FLAT WOOD DECK ASSEMBLY.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER
 RULE 61G20-3
 5. FBC B 105.1. SEPARATE PERMIT APPLICATION REQUIRED
 FOR ROOF WORK.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-02 Cont ID  
Sent By jbrooks Date 2019-07-02 Time 13:31 Rev Time 0.00
Received By jbrooks Date 2019-07-02 Time 13:31 Sent To  
Notes
2019-07-02 13:32:39JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. FBC B 107.2.1. PLEASE PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION ON SUBMITTED DRAWINGS:
 CONSTRUCTION TYPE; OCCUPANCY GROUP; CLASSIFICATION OF
 WORK (ADDITION); BUILDING HEIGHT.
 2. FBC B 107.2.1 PROVIDE A DRAWING DETAIL SHOWING
 INTERSECTION OF NEW STORAGE ROOM ROOF WITH EXISTING
 LAUNDRY ROOM ROOF/WALL WITH FLASHING (IF APPLICABLE);
 ALONG WITH DRAWING DETAILS OF THE CONSTRUCTION METHOD
 USED OF MATING NEW STORAGE ROOM ROOF, WALLS, FOOTINGS,
 SLAB, COLUMNS AND BEAMS TO THE EXISTING RESIDENTIAL
 STRUCTURE.
 3. FBC EB 1104.1 SMOKE ALARMS IN EXISTING PORTIONS OF A
 BUILDING. WHERE AN ADDITION IS MADE TO A BUILDING OR
 STRUCTURE OF A GROUP R OR I-1 OCCUPANCY, THE EXISTING
 BUILDING SHALL BE PROVIDED WITH SMOKE ALARMS AS
 REQUIRED BY THE FLORIDA FIRE PREVENTION CODE OR SECTION
 R314 OF THE FLORIDA BUILDING CODE, RESIDENTIAL AS
 APPLICABLE. PROVIDE FLOOR PLANS OF EXISTING RESIDENCE
 SHOWING COMPLIANCE.
 4. PROVIDE TWO SETS OF PRODUCT APPROVALS/NOA?S FOR THE
 PROPOSED ROOFING SYSTEM TO BE USED. ALL APPLICABLE
 DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON
 THE PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS
 NOT SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. AS PER RULE 61G20-3
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-07 Cont ID  
Sent By jduprey Date 2019-05-07 Time 16:46 Rev Time 0.00
Received By jduprey Date 2019-05-07 Time 16:37 Sent To  
Notes
2019-05-07 16:47:06BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE DOOR AND ROOF PRODUCTS APPROVALS. FBC 107

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2020-03-06 Cont ID  
Sent By jleahy Date 2020-03-06 Time 14:37 Rev Time 0.00
Received By jleahy Date 2020-03-06 Time 14:37 Sent To  
Notes
2020-03-06 14:39:03SENT TO J BROOKS DESK JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-12-13 Cont ID  
Sent By jbrooks Date 2019-12-17 Time 08:48 Rev Time 0.00
Received By jleahy Date 2019-12-13 Time 09:03 Sent To  
Notes
2019-12-13 09:08:01SEE COMMENTS FROM FIRST REVIEW JL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-11-04 Cont ID  
Sent By jleahy Date 2019-11-04 Time 15:00 Rev Time 0.00
Received By jleahy Date 2019-11-04 Time 15:00 Sent To  
Notes
2019-11-04 15:02:29NO ELECTRIC SHOWN LIGHTING IS REQUIRED BY CODE SECTION
 210.70

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-03-10 Cont ID  
Sent By jbrooks Date 2020-03-10 Time 07:50 Rev Time 0.00
Received By jbrooks Date 2020-02-26 Time 13:36 Sent To  
Notes
2020-03-03 15:19:183/3 ROUTED TO JLEAHY
2020-02-27 13:36:24RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-12-17 Cont ID  
Sent By jbrooks Date 2019-12-17 Time 08:48 Rev Time 0.00
Received By jbrooks Date 2019-12-06 Time 14:44 Sent To E
Notes
2019-12-09 14:44:23RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-11-04 Cont ID  
Sent By rfalcone Date 2019-11-04 Time 15:02 Rev Time  
Received By jleahy Date 2019-10-07 Time 13:35 Sent To  
Notes
2019-10-08 13:36:06ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-02 Cont ID  
Sent By jbrooks Date 2019-07-02 Time 13:35 Rev Time 0.00
Received By jbrooks Date 2019-06-24 Time 14:46 Sent To  
Notes
2019-06-25 14:46:45RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-07 Cont ID  
Sent By jduprey Date 2019-05-07 Time 16:47 Rev Time 0.00
Received By jduprey Date 2019-04-22 Time 10:31 Sent To  
Notes
2019-04-23 10:31:42ROUTED TO ZONING INBOX

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2020-03-11 Cont ID  
Sent By shill Date 2020-03-11 Time 08:31 Rev Time 0.00
Received By shill Date 2020-03-10 Time 07:50 Sent To  
Notes
2020-03-10 07:52:45ROOFING PERMIT APPPLICATION REQUIRED ALONG WITH TWO
 SETS OF PRODUCT APPROVALS FOR THE ROOFING SYSTEM USED.

Review Stop Z ZONING
Rev No 5 Status P Date 2020-03-02 Cont ID  
Sent By rfalcone Date 2020-03-02 Time 15:42 Rev Time 0.00
Received By rfalcone Date 2020-03-02 Time 15:42 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2019-12-10 Cont ID  
Sent By rfalcone Date 2019-12-10 Time 13:54 Rev Time 0.00
Received By rfalcone Date 2019-12-10 Time 13:54 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2019-10-09 Cont ID  
Sent By rfalcone Date 2019-10-09 Time 11:14 Rev Time 0.00
Received By rfalcone Date 2019-10-09 Time 11:14 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-06-28 Cont ID  
Sent By ajones Date 2019-06-28 Time 09:42 Rev Time 0.00
Received By ajones Date 2019-06-28 Time 09:41 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By mcruz Date 2019-04-30 Time 16:10 Rev Time 0.00
Received By mcruz Date 2019-04-30 Time 10:14 Sent To B
Notes
2019-04-30 16:09:58ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
 2) PROVIDE THE SETBACK DIMENSIONS FROM THE PROPOSED
 ADDITION TO ALL ADJACENT PROPERTY LINES.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER
 THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO
 SCHEDULE AN APPOINTMENT.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]