Plan Review Details - Permit 19041063
Plan Review Stops For Permit 19041063
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-04-24 Cont ID  
Sent By jduprey Date 2019-04-24 Time 14:04 Rev Time 0.00
Received By jduprey Date 2019-04-24 Time 14:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-23 Cont ID  
Sent By jduprey Date 2019-04-23 Time 16:10 Rev Time 0.00
Received By jduprey Date 2019-04-23 Time 15:34 Sent To  
Notes
2019-04-23 16:15:23BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE DRAWINGS AND SPECSIFICATION IN ACCORDANCE
 WITH R703.7.
  
 R703.7 EXTERIOR PLASTER. INSTALLATION OF THESE
 MATERIALS SHALL BE IN COMPLIANCE WITH ASTM C926, ASTM
 C1063 AND THE PROVISIONS OF THIS CODE.
  
 R703.7.1 LATH.
  
 LATH AND LATH ATTACHMENTS SHALL BE OF
 CORROSION-RESISTANT MATERIALS. EXPANDED METAL OR WOVEN
 WIRE LATH SHALL BE ATTACHED WITH 11/2-INCH-LONG (38
 MM), 11 GAGE NAILS HAVING A 7/16-INCH (11.1 MM) HEAD,
 OR 7/8-INCHLONG (22.2 MM), 16 GAGE STAPLES, SPACED NOT
 MORE THAN 6 INCHES (152 MM), OR AS OTHERWISE APPROVED.
  
 R703.7.2 PLASTER.
  
 PLASTERING WITH PORTLAND CEMENT PLASTER SHALL BE NOT
 LESS THAN THREE COATS WHERE APPLIED OVER METAL LATH OR
 WIRE LATH AND SHALL BE NOT LESS THAN TWO COATS WHERE
 APPLIED OVER MASONRY, CONCRETE,
 PRESSURE-PRESERVATIVETREATED WOOD OR DECAY-RESISTANT
 WOOD AS SPECIFIED IN SECTION R317.1 OR GYPSUM BACKING.
 IF THE PLASTER SURFACE IS COMPLETELY COVERED BY VENEER
 OR OTHER FACING MATERIAL OR IS COMPLETELY CONCEALED,
 PLASTER APPLICATION NEED BE ONLY TWO COATS, PROVIDED
 THE TOTAL THICKNESS IS AS SET FORTH IN TABLE R702.1(1).
  
 ON WOOD-FRAME CONSTRUCTION WITH AN ON-GRADE FLOOR SLAB
 SYSTEM, EXTERIOR PLASTER SHALL BE APPLIED TO COVER, BUT
 NOT EXTEND BELOW, LATH, PAPER AND SCREED.
  
 THE PROPORTION OF AGGREGATE TO CEMENTITIOUS MATERIALS
 SHALL BE AS SET FORTH IN TABLE R702.1(3).
  
 R703.7.2.1 WEEP SCREEDS.
  
 A MINIMUM 0.019-INCH (0.5 MM) (NO. 26 GALVANIZED SHEET
 GAGE), CORROSION-RESISTANT WEEP SCREED OR PLASTIC WEEP
 SCREED, WITH A MINIMUM VERTICAL ATTACHMENT FLANGE OF
 31/2 INCHES (89 MM) SHALL BE PROVIDED AT OR BELOW THE
 FOUNDATION PLATE LINE ON EXTERIOR STUD WALLS IN
 ACCORDANCE WITH ASTM C926. THE WEEP SCREED SHALL BE
 PLACED NOT LESS THAN 4 INCHES (102 MM) ABOVE THE EARTH
 OR 2 INCHES (51 MM) ABOVE PAVED AREAS AND SHALL BE OF A
 TYPE THAT WILL ALLOW TRAPPED WATER TO DRAIN TO THE
 EXTERIOR OF THE BUILDING. THE WEATHER-RESISTANT BARRIER
 SHALL LAP THE ATTACHMENT FLANGE. THE EXTERIOR LATH
 SHALL COVER AND TERMINATE ON THE ATTACHMENT FLANGE OF
 THE WEEP SCREED.
  
 R703.7.3 WATER-RESISTIVE BARRIERS.
  
 WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED
 IN SECTION R703.2 AND, WHERE APPLIED OVER WOOD-BASED
 SHEATHING, SHALL INCLUDE A WATER-RESISTIVE
 VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST
 EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE
 INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH
 THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE
 AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION
 R703.4) INTENDED TO DRAIN TO THE WATER-RESISTIVE
 BARRIER IS DIRECTED BETWEEN THE LAYERS.
  
 EXCEPTION: WHERE THE WATER-RESISTIVE BARRIER THAT IS
 APPLIED OVER WOOD-BASED SHEATHING HAS A WATER
 RESISTANCE EQUAL TO OR GREATER THAN THAT OF 60-MINUTE
 GRADE D PAPER AND IS SEPARATED FROM THE STUCCO BY AN
 INTERVENING, SUBSTANTIALLY NONWATER-ABSORBING LAYER OR
 DESIGNED DRAINAGE SPACE.
  
 R703.7.4 APPLICATION.
  
 EACH COAT SHALL BE KEPT IN A MOIST CONDITION FOR AT
 LEAST 48 HOURS PRIOR TO APPLICATION OF THE NEXT COAT.
  
 EXCEPTION: APPLICATIONS INSTALLED IN ACCORDANCE WITH
 ASTM C926 INCLUDING THE REFERENCE IN ASTM C926 SECTION
 8 TO SECTION X1.4.2 OF THE APPENDIX.
  
 R703.7.5 CURING.
  
 THE FINISH COAT FOR TWO-COAT CEMENT PLASTER SHALL NOT
 BE APPLIED SOONER THAN SEVEN DAYS AFTER APPLICATION OF
 THE FIRST COAT. FOR THREE-COAT CEMENT PLASTER, THE
 SECOND COAT SHALL NOT BE APPLIED SOONER THAN 48 HOURS
 AFTER APPLICATION OF THE FIRST COAT. THE FINISH COAT
 FOR THREECOAT CEMENT PLASTER SHALL NOT BE APPLIED
 SOONER THAN SEVEN DAYS AFTER APPLICATION OF THE SECOND
 COAT.
  
 EXCEPTION: APPLICATIONS INSTALLED IN ACCORDANCE WITH
 ASTM C926 INCLUDING THE REFERENCE IN ASTM C926 SECTION
 8 TO SECTION X1.4.2 OF THE APPENDIX.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-24 Cont ID  
Sent By jduprey Date 2019-04-24 Time 14:04 Rev Time 0.00
Received By jduprey Date 2019-04-24 Time 14:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-23 Cont ID  
Sent By jduprey Date 2019-04-23 Time 16:15 Rev Time 0.00
Received By jduprey Date 2019-04-22 Time 10:26 Sent To  
Notes
2019-04-23 10:26:50BLDG <5K