Plan Review Details - Permit 19041007
Plan Review Stops For Permit 19041007
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-15 Cont ID  
Sent By jwitmer Date 2019-07-15 Time 12:52 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-06 Cont ID  
Sent By jwitmer Date 2019-05-06 Time 13:13 Rev Time 0.00
Received By jwitmer Date 2019-05-06 Time 11:39 Sent To  
Notes
2019-05-06 13:13:172017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19041007
 ADD: 1125, 1127, 1129 & 1131 N. ROSEMARY
 CONT: WALL TO WALL WE DO IT ALL
 TEL: 561-463-9708
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MAY, MON. 06/ 2019
 ACTION: DENIED
  
 1) THE BUILDING PERMIT APPLICATION WAS SUBMITTED WITH A
 PORTION OF THE WORK WAS THE RE-DO ROOFING. PLEASE NOTE
 THIS IS A 2 STORY APARTMENT BUILDING. THE CONTRACTOR
 WALL TO WALL WE DO IT ALL CANNOT APPLY FOR A ROOFING
 PERMIT, THEY ARE NOT A LICENSED ROOFING CONTRACTOR. SEE
 FLORIDA STATUTE 489.113.3(G)
 NO GENERAL, BUILDING, OR RESIDENTIAL CONTRACTOR
 CERTIFIED AFTER 1973 SHALL ACT AS, HOLD HIMSELF OR
 HERSELF OUT TO BE, OR ADVERTISE HIMSELF OR HERSELF TO
 BE A ROOFING CONTRACTOR UNLESS HE OR SHE IS CERTIFIED
 OR REGISTERED AS A ROOFING CONTRACTOR.
  
 2) THE SUBMITTED PLAN DOES NOT MEET THE QUALITY OF
 PLANS FOR RECORD RETENTION.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.3 QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 3) IF THE CONTRACTOR CBC DRAWS THEIR OWN PLAN THEY MUST
 SIGN THEIR NAME (QUALIFIER) PRINT THEIR NAME AND
 LICENSE NUMBER OF THEIR FIRM. 107.3.4.2 CERTIFICATIONS
 BY CONTRACTORS AUTHORIZED UNDER THE PROVISIONS OF
 SECTION. 489.115 FLORIDA STATUTES, SHALL BE CONSIDERED
 EQUIVALENT TO SEALED PLANS AND SPECIFICATIONS
 BY A PERSON LICENSED UNDER CHAPTER 471, FLORIDA
 STATUTES, OR CHAPTER 481 FLORIDA STATUTES, BY LOCAL
 ENFORCEMENT AGENCIES FOR PLANS REVIEW FOR PERMITTING
 PURPOSES.
  
 4) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY
 THE BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING
 MINIMUM CRITERIA AND DOCUMENTS: A SCALED FLOOR PLAN;
 AND ROUGH WALL/ OR FINISHED WALL TO WALL DIMENSIONS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-09-25 Cont ID  
Sent By jleahy Date 2019-09-25 Time 10:21 Rev Time 0.00
Received By jleahy Date 2019-09-25 Time 10:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-14 Cont ID  
Sent By jpearson Date 2019-07-14 Time 08:59 Rev Time 0.00
Received By jpearson Date 2019-07-14 Time 08:59 Sent To  
Notes
2019-07-14 08:59:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. A MINIMUM OF TWO SMALL APPLIANCE BRANCH CIRCUITS
 FOR KITCHEN ARE REQUIRED. PANEL SCHEDULES STATE THAT
 THE SQUARE FOOTAGE IS 1676, BUT THE LOAD CALCULATION
 STATES THAT IT IS 766, WHICH IS IT? IN ADDITIONA TO
 EACH PANEL LOAD, PROVIDE LOAD CALCULATION FOR ENTIRE
 SERVICE. NEC 220
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 4. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9
 5. PLAN SHOWS THE MAIN DISCONNECT AND METERS IN THE
 METER ROOM. WHERE IS THIS ROOM, IT IS NOT SHOWN ON
 PLAN? PROVIDE LOCATION OF SERVICE. WPB FBC 107.2.1
 6. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. THE
 RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR
 PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN
 COUNTERTOP, LOCATED ON THE COUNTERTOP, OR INSTALLED ON
 THE SIDE OR FACE OF THE BASIN CABINET. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D)
 7. CODE REQUIRES A MINIMUM OF TWO SMALL APPLIANCE
 CIRCUITS TO COUNTER RECEPTACLE OUTLETS IN THE KITCHEN.
 PROVIDE CORRECTION. NEC 210.11(C)(1), 210.52(B)(3)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By fgiaquin Date 2019-05-14 Time 06:40 Rev Time 0.00
Received By fgiaquin Date 2019-05-14 Time 06:36 Sent To I
Notes
2019-05-14 06:40:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN PROVIDED IS NOT LEGIBLE. PLEASE SUBMIT CLEARLY
 DRAWN PLAN THAT SHOWS ALL ELECTRICAL WORK TO BE
 PERFORMED. PERMIT APPLICATION SIMPLY SAYS "FIX
 ELECTRIC". WHAT IS THE PROPOSED ELECTRICAL WORK? FBC
 107.2.1
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
 2. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-01 Cont ID  
Sent By pleduc Date 2019-07-01 Time   Rev Time 0.00
Received By pleduc Date 2019-06-28 Time 15:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-04-26 Cont ID  
Sent By scaldero Date 2019-04-26 Time 09:51 Rev Time 0.00
Received By scaldero Date 2019-04-26 Time 09:44 Sent To  
Notes
2019-04-26 09:51:23PERMIT # 19041007
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL COMMENTS:
  
 1) PERMIT HAS 4 DIFFERENT ADDRESSES LISTED. PLEASE
 CLARIFY THE EXACT LOCATION OF THIS PROJECT.
  
 2) INSUFFICIENT DETAILS PROVIDED REGARDING RENOVATIONS
 BEING MADE. THE SCOPE OF WORK NEEDS TO BE CLEARLY
 OUTLINED. WHAT IS EXACTLY IS BEING REMODELED AND WHERE.
  
 3) IS THIS STRUCTURE PROTECTED BY A FIRE SPRINKLER
 SYSTEM AND/OR A FIRE ALARM SYSTEM?
  
 4) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By pleduc Date 2019-07-15 Time   Rev Time 0.00
Received By pleduc Date 2019-06-28 Time 11:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-14 Cont ID  
Sent By fgiaquin Date 2019-05-14 Time 06:41 Rev Time 0.00
Received By fgiaquin Date 2019-04-19 Time 13:27 Sent To  
Notes
2019-04-22 13:27:16B28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-05-06 Cont ID  
Sent By jwitmer Date 2019-05-06 Time 13:13 Rev Time 0.00
Received By jwitmer Date 2019-05-06 Time 11:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-07-02 Cont ID  
Sent By thunt Date 2019-07-02 Time 13:27 Rev Time 0.00
Received By thunt Date 2019-07-02 Time 13:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By thunt Date 2019-04-30 Time 13:35 Rev Time 0.00
Received By thunt Date 2019-04-30 Time 13:35 Sent To  
Notes
2019-04-30 13:34:57PLUMBING 1ST REVIEW**DENIED**
  
 1) YOU LISTED 4 DIFFERENT ADDRESS ON THE PERMIT
 APPLICATION AND ONLY SUBMITTED 1 PLAN. PER PUBLIC
 RECORD IT DOESNT APPEAR THAT ALL 4 UNIT ARE THE SAME.
 PLEASE CLARIFY AND OR PROVIDE A SEPERATE PLAN FOR EACH.
 FBC 107.2.1
  
 2) IS THE LOCATION OF THE SINK IN ANY OF THE UNITS
 CHANGING OR TO REMAIN IN EXISTING LOCATION. PLEASE
 CLARIFY. FBC 107.2.1
  
 3) PERSON DESIGN PLAN SHALL SIGN AND TAKE
 RESPOSABILITY. FAC 471, 481,
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
  
  
  