| 2019-04-24 14:17:42 | GAS 1ST REVIEW**DENIED** |
| | |
| | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL |
| | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT |
| | THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A |
| | CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE |
| | COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS |
| | WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1. |
| | |
| | 1) THE PIPING INTENDED FOR THE GENERATOR INSTALLED |
| | UNDER PERMIT#18081434 WAS ONLY SIZED FOR 790,000 BTU'S. |
| | YOU GENERATOR BASED ON THE SPEC SUPPLIED IS 890,000 |
| | BTU'S. YOU MUST SUBMIT A COMPLETE GAS PLAN SHOWING HOW |
| | THIS EXTRA LOAD ON THE EXISTING SYSTEM IS GOING TO BE |
| | HANDLED TO INLCUDE. FBC 107.3.5 |
| | |
| | 2) VALUE SEEMS LOW. PROVIDE A SIGN BONA FIDE |
| | CONTRACT.109.3 BUILDING PERMIT VALUATIONS. IF, IN THE |
| | OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION |
| | OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS |
| | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE |
| | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION |
| | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | |
| | 3) PLAN SHOW GENERATOR TO BE INSTALLED UNDER A COVERED |
| | CONC. PLEASE CLARIFY. SUBMIT TWO COPIES OF A HOUSE PLAN |
| | SHOWING THE LOCATION OF THE GENERATORR AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE GENERATORR. THE LOCATION OF THE |
| | GENERATORSHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |