Plan Review Details - Permit 19040938
Plan Review Stops For Permit 19040938
Review Stop AD ADDRESSING
Rev No 2 Status N Date 2019-09-24 Cont ID  
Sent By shill Date 2019-09-24 Time 07:46 Rev Time 0.00
Received By shill Date 2019-09-24 Time 07:46 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2019-07-31 Cont ID  
Sent By shill Date 2019-07-31 Time 06:10 Rev Time 0.00
Received By shill Date 2019-07-31 Time 06:10 Sent To  
Notes
2019-07-31 06:11:27FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-05-22 Cont ID  
Sent By rmcphers Date 2020-05-22 Time 13:36 Rev Time 0.00
Received By rmcphers Date 2020-05-22 Time 13:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-03-04 Cont ID  
Sent By rmcphers Date 2020-03-04 Time 10:09 Rev Time 0.00
Received By rmcphers Date 2020-03-03 Time 15:46 Sent To  
Notes
2020-03-04 09:06:54RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE FLOORING ON THE 2ND FLOOR (R2) AREA
 TO COMPLY WITH FBC 1207 (PLEASE SEE A AND B BELOW)
 (CARPET WOULD BE EXEMPT FROM THE REQUIREMENTS)
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 2) DRAWING S3 SHOWS THE ADDITION OF 5/8 INCH DRYWALL
 BEING ADDED TO THE BOTTOM OF THE FLOOR JOIST. PLEASE
 SHOW ON THE DRAWINGS THE EXISTING FIRE RATING (1HR ? )
 TO BE MAINTAINED PER FBC EXISTING BUILDING 703.1 AND
 803.6 ( FBC 420.3 )
  
 3) DOOR LABELED (DR19) AND (DR18) DOUBLE DOORS - AT
 LEAST ONE OF THE DOORS NEEDS TO PROVIDE A 32 INCH CLEAR
 OPENING TO COMPLY WITH FBC 1010.1.1 (MEANS OF EGRESS
 DOOR WIDTH).
  
 4) PLEASE SHOW THE EXIT ACCESS DOOR FROM SMALL ASSEMBLY
 ROOM IN THE 1ST FLOOR CREATED HALLWAY TO HAVE EXIT
 SIGNAGE TO COMPLY WITH FBC 1013.1
  
 5) PLEASE SHOW THE EMERGENCY LIGHTING FOR THE EGRESS
 THROUGH THE ENCLOSED HALLWAY TO COMPLY WITH FBC 1008.3
  
 6) LOCATION OF EXIT SIGNS AND EMERGENCY LIGHTING SHOWN
 ON THE FLOOR PLAN SHOULD MATCH THE LOCATIONS SHOWN ON
 THE ELECTRICAL PLAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-09-23 Cont ID  
Sent By shill Date 2019-09-23 Time 14:49 Rev Time 0.00
Received By shill Date 2019-09-23 Time 14:49 Sent To  
Notes
2019-09-23 14:49:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. PLAN TO BE REVISED TO NOTE COMPLIANCE WITH FBC 2017;
 REMOVE REFERENCES TO PREVIOUS CODES AND STAFF.
  
 2ND REVIEW: THIS WAS DONE, BUT THE FOLLOWING ISSUES
 WERE FOUND:
  
 LS1, BUILDING CODE SUMMARY 2, SEE FBC B 602.4, THIS
 BUILDING IS NOT HEAVY TIMBER TYPE IVB, REVISE.
 LS1, BUILDING CODE SUMMARY 5, SEE FBC B 302, EACH AREA
 IS TO BE CLASSIFIED AS TO OCCUPANCY CLASSIFICATION
 ("MIXED" IS NOT ONE OF THE CLASSIFICATIONS). THIS
 APPEARS TO BE BUSINESS AND A3 ON THE FIRST FLOOR, R2 ON
 THE SECOND FLOOR. REVISE SECTION 5 TO CLARIFY.
 LS1, BUILDING CODE SUMMARY 6, PROPOSED HEIGHT IS 1
 STORY; ISN'T THIS A 2 STORY BUILDING?
 LS1, BUILDING CODE SUMMARY 7, FLOOR CONSTRUCTION IS 0
 HOURS. AN OCCUPANCY SEPARATION BETWEEN RESIDENTIAL AND
 OTHER OCCUPANCIES IS REQUIRED AND WAS REQUIRED WHEN THE
 BUILDING WAS CONSTRUCTED, REVISE TO REFLECT SEPARATION
 REQUIREMENT.
  
 2-3. OK
  
 4. ONE BATHROOM ON THE 1ST FLOOR IS NOT ACCESSIBLE AND
 THE ENTRY DOORS TO THE MEDITATION ROOM ARE NOT
 ACCESSIBLE; APPLICANT TO DOCUMENT THAT THIS IS NOT
 REQUIRED DUE TO DISPROPORTIONATE COST. THIS MAY BE SENT
 VIA EMAIL FOR PRELIMINARY REVIEW.
  
 2ND REVIEW, IT IS NOT CLEAR HOW THIS WAS ADDRESSED.
  
 5-9. OK
  
 10. LIFE SAFETY AND ARCHITECTURAL SHEETS TO BE PREPARED
 BY AN ARCHITECT OR ENGINEER WILL OBTAIN A DETERMINATION
 FROM FBPE OR FLORIDA BOARD OF ARCHITECTS.
  
 2ND REVIEW, IT IS NOT CLEAR HOW THIS WAS ADDRESSED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-31 Cont ID  
Sent By shill Date 2019-07-31 Time 06:11 Rev Time 0.00
Received By shill Date 2019-07-31 Time 06:11 Sent To  
Notes
2019-07-31 06:13:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THIS IS A RECAP OF MEETING ON 7/30/19 WHEREIN DESIGN
 OPTIONS WERE DISCUSSED. FOR CODE REFERENCES, PLEASE SEE
 PREVIOUS BUILDING REVIEW. NOTE THAT ANY DESIGN WHICH
 COMPLIES WITH THE FBC/FFPC IS ACCEPTABLE; THE BELOW IS
 ONE DESIGN OPTION DISCUSSED IN THE MEETING WITH
 ENGINEER, OWNER AND CONTRACTOR.
  
 1. PLAN TO BE REVISED TO NOTE COMPLIANCE WITH FBC 2017;
 REMOVE REFERENCES TO PREVIOUS CODES AND STAFF.
  
 2. WORK AREA (SEE DEFINITION IN FBC 2017 EB) TO BE
 MODIFIED TO CLEARLY DEMONSTRATE THAT A LEVEL II
 ALTERATION IS PROPOSED; WORK AREA REDUCED ACCORDINGLY.
  
 3. 2ND FLOOR, CURRENTLY R2, UNDER THIS OPTION WOULD
 REMAIN R2 (NO CHANGE OF OCCUPANCY), PLAN TO BE MODIFIED
 TO CLARIFY; ACCESSIBILITY FOR 2ND FLOOR NOT REQUIRED
 (SEE DEFINITION OF PLACE OF PUBLIC ACCOMMODATION).
  
 4. ONE BATHROOM ON THE 1ST FLOOR IS NOT ACCESSIBLE AND
 THE ENTRY DOORS TO THE MEDITATION ROOM ARE NOT
 ACCESSIBLE; APPLICANT TO DOCUMENT THAT THIS IS NOT
 REQUIRED DUE TO DISPROPORTIONATE COST. THIS MAY BE SENT
 VIA EMAIL FOR PRELIMINARY REVIEW.
  
 5. PER FIRE, A FIRE ALARM SYSTEM WILL BE INSTALLED.
  
 6. A REMOTELY LOCATED EXIT IS TO BE INSTALLED FOR THE
 FIRST FLOOR MEDITATION AREA; IT IS ACCEPTABLE FOR THE
 MEANS OF EGRESS TO GO THROUGH THE ADJACENT ACCESSORY
 AREA.
  
 7. FOR ACCESSIBILITY TO THE PRIMARY FUNCTION AREA, ALL
 FIRST FLOOR DOORS TO BE MODIFIED TO MAINTAIN 18"
 CLEARANCE ON PULL SIDE TO COMPLY WITH ACCESSIBILITY.
  
 8. OCCUPANT LOAD IN THE MEDITATION AREATO BE REDUCED
 (INCLUDES TABLES AND CHAIRS).
  
 9. PER FIRE, ONLY ONE LIGHTWEIGHT ROOF CONSTRUCTION ID
 SIGN IS REQUIRED AT THE MAIN ENTRY; OTHERS ARE
 OPTIONAL.
  
 10. LIFE SAFETY AND ARCHITECTURAL SHEETS TO BE PREPARED
 BY AN ARCHITECT OR ENGINEER WILL OBTAIN A DETERMINATION
 FROM FBPE OR FLORIDA BOARD OF ARCHITECTS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-03 Cont ID  
Sent By jgomez Date 2019-06-03 Time 18:44 Rev Time 0.00
Received By jgomez Date 2019-06-03 Time 09:19 Sent To  
Notes
2019-05-23 18:03:28BUILDING ALTERATION/CHANGE OF OCCUPANCY, BUILDING
 REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING.
  
  
 1-SHEET SP-1:
 DESIGN PROFESSIONAL INDICATES ON THE FIRST PARAGRAPH OF
 THE SCOPE OF WORK THAT "THIS PROJECT CONSISTS OF AN
 INTERIOR ALTERATION TO AN EXISTING (1954) TWO STORY
 MIXED OCCUPANCY COMMERCIAL BUILDING. THERE ARE NO
 STRUCTURAL MODIFICATIONS INCLUDED WITHIN THIS
 ALTERATION PROJECT.
 THE EXISTING BUILDING PREVIOUS USE WAS MIXED. MORTUARY
 AT 1ST FLOOR WITH LIVING QUARTERS/APARTMENTS AT SECOND
 FLOOR.
 THE PROPOSED USE USE IS ALSO MIXED. THE GROUND FLOOR
 SERVING AS A PLACE OF WORSHIP/PRAYER WITH 2ND FLOOR
 BEING LIVING QUARTERS/APARTMENTS."
  
 THE SCOPE OF WORK SHOWN ON PLANS IS CONSIDERED A CHANGE
 OF OCCUPANCY AND ALTERATION LEVEL 3. PLANS SUBMITTED
 DON'T SHOW ANY INCIDENTAL WORK TO ENGINEERING. THE
 SCOPE OF WORK IS ARCHITECTURE NOT ENGINEERING. PLANS
 NEED TO BE PREPARED BY A LICENSE ARCHITECT. SEC.
 481.229(4) F.S.
  
 2- SCOPE OF WORK ON SHEET SP-1. THE DESIGN PROFESSIONAL
 NEEDS TO SELECT WHICH COMPLIANCE METHOD IS GOING TO BE
 APPLIED TO THE PROPOSED SCOPE OF WORK AS REQUIRED BY
 SEC. 301.1 FBC-EXISTING BUILDING CODE.
  
 DESIGN PROFESSIONAL INDICATES ON THE SCOPE OF WORK THAT
 "THIS ALTERATION UTILIZES CHAPTER 3 EXCEPTION FOR THE
 LAWS/CODE IN EXISTENCE AT THE TIME THE BUILDING WAS
 ORIGINALLY CONSTRUCTED IN 1954". THIS EXCEPTION DOESN'T
 APPLY BECAUSE THE EXCEPTION APPLIES ONLY TO
 "ALTERATIONS". THIS IS A CHANGE OF OCCUPANCY AND
 ALTERATION LEVEL 3.
  
 THE FOLLOWING ARE THE COMMENTS ABOUT THE PROPOSED SCOPE
 OF WORK:
 A) BASED ON SCOPE OF WORK SHOWN ON PLANS THE SCOPE OF
 WORK IS A CHANGE OF OCCUPANCY AND ALTERATION LEVEL 3.
 SOME AREAS ARE CHANGE OF USE GROUP WITHOUT CHANGE OF
 OCCUPANCY AND OTHER AREAS ARE CHANGE OF USE GROUP WITH
 A CHANGE OF OCCUPANCY CLASSIFICATION. SCOPE OF WORK
 WILL NEED TO COMPLY WITH THE PERTAINING REQUIREMENTS OF
 CHAPTER 10 FBC-EXISTING BUILDING.
  
 B) USE OF SECOND FLOOR NEEDS TO BE CLARIFIED ALSO.
 SCOPE OF WORK SAYS LIVING QUARTERS/APARTMENTS, WHILE
 LIFE SAFETY PLAN CALLS FOR BOARDING GROUP R-3. PROPOSED
 USE NEEDS TO BE CLEAR. NEED TO SPECIFY IF APARTMENTS OR
 BOARDING HOUSE. NEED TO SPECIFY NUMBER OF PEOPLE
 (COORDINATE WITH COMMENTS TO LIFE SAFETY PLAN) AND
 CLEARLY SPECIFY IF TRANSIENT OR NON-TRANSIENT. SEC.
 R310.5 FBC-BUILDING.
  
 3- THIS IS A COMMERCIAL BUILDING WITH MIXED USES. BASED
 ON THE PROPOSED CHANGE OF OCCUPANCY OF SECOND FLOOR
 FROM APARTMENTS TO "BOARDING GROUP R-3" AS SHOWN ON
 PLANS, THEN NEED TO COMPLY WITH THE FOLLOWING (OR
 PROVIDE COMPLY INFORMATION SHOWING WHY IT WILL EXEMPT
 OF THESE REQUIREMENTS):
  
 A)SECOND FLOOR NEEDS TO SHOW COMPLIANCE WITH THE
 VERTICAL ACCESSIBILITY AS REQUIRED BY SEC. 1006.1
 FBC-EXISTING BUILDING AND SEC. 201.1.1
 FBC-ACCESSIBILITY.
  
 B) SECOND FLOOR NEEDS TO COMPLY WITH THE REQUIREMENTS
 OF SEC. 233 FBC-ACCESSIBILITY.
  
 4- NEED TO SHOW COMPLIANCE WITH THE ACCESSIBLE ROUTE TO
 THE ENTRANCE OF THE EAST AREA OF THE BUILDING ON THE
 GROUND FLOOR AS REQUIRED BY SEC. 206 FBC-ACCESSIBILITY.
 (OR PROVIDE COMPLY INFORMATION SHOWING WHY IT WILL
 EXEMPT OF THESE REQUIREMENTS):
  
 5- SITE PLAN ON SHEET SP-1: PROVIDE THE TOTAL GROSS
 AREA OF THE BUILDING. PROVIDE THE FIRST FLOOR AREA AND
 THE SECOND FLOOR AREA. ONLY THE NET SQUARE FOOTAGE AREA
 WAS PROVIDED. SEC. 503.1 FBC-BUILDING.
  
  
 6- LIFE SAFETY PLAN SHEET LS-1: UPDATE BUILDING CODE
 SUMMARY INFORMATION. COORDINATE WITH ITEM #2 ABOVE.
 SEC. 107.2.1 CITY AMENDMENTS.
  
  
 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 FIRE RATED FLOOR CEILING ASSEMBLY SEPARATING THE GROUND
 FLOOR TO THE SECOND FLOOR. SPECIFICATIONS SHOWN ON THE
 FLOOR CEILING PLANS ON SHEET S-3 DON'T SEEM TO COMPLY.
 SEC. 1012.1.1.2 FBC-EXISTING BUILDING CODE.
  
 8- SECOND FLOOR LIFE SAFETY PLAN SHEET SL-1:
 CLARIFY/REVISE NUMBER OF OCCUPANTS ON THE SECOND FLOOR.
 CLARIFY IF THE BEDROOMS ARE DOUBLE OCCUPANCY OR SINGLE
 OCCUPANCY. PLANS SHOW LIKE DOUBLE BEDS. COORDINATE WITH
 NUMBER OF PEOPLE PER GROSS SQUARE FOOTAGE AS REQUIRED
 BY TABLE 1004.1.2 FBC-BUILDING.
  
 9-GROUND FLOOR LIFE SAFETY SHEET LS-1:
 A)BASED ON THE NUMBER OF PEOPLE SHOWN TWO MEANS OF
 EGRESS ARE REQUIRED FOR THE OCCUPANTS ON THE WEST PART
 AREA OF THE BUILDING. SEC. 1006.2.1 FBC-BUILDING.
  
 B)REVISE NUMBER OF OCCUPANTS SHOWN ON THE SMALL
 ASSEMBLY AREA ON THE EAST SIDE OF THE BUILDING. THE
 OCCUPANT LOAD CAN NOT BE MORE THAN ONE OCCUPANT PER 7
 SQUARE FEET OF OCCUPIABLE FLOOR SPACE AS REQUIRED BY
 SEC. 1004.2 FBC-BUILDING.
  
 C) CLARIFY/REVISE NUMBER OF OCCUPANTS ON THE PROPOSED
 COMPUTER/AFTER SCHOOL STUDY ROOM. NUMBER OF CHAIRS
 SHOWN AND NUMBER SPECIFIED DON'T MATCH. TABLE 1004.1.2
 FBC-BUILDING.
  
 D)CLARIFY/REVISE NUMBER OF OCCUPANTS ON THE PROPOSED
 RENOVATED BREAK ROOM/DINING AREA. NUMBER OF CHAIRS
 SHOWN AND NUMBER SPECIFIED DON'T MATCH. AND, PROVIDE
 THE NUMBER OF PEOPLE ON THE KITCHEN AREA. TABLE
 1004.1.2 FBC-BUILDING.
  
 E) CLARIFY/REVISE NUMBER OF OCCUPANTS ON THE PROPOSED
 LAUNDRY. WHY ONE OCCUPANT PER 300 SQUARE FEET. TABLE
 1004.1.2 FBC-BUILDING.
  
 F) CLARIFY/REVISE NUMBER OF OCCUPANTS ON THE PROPOSED
 LIBRARY/READING/OFFICE ROOM. NUMBER OF PEOPLE NEED TO
 BE ROUNDED UP0 NOT ROUNDED DOWN AND IS MISSING THE
 NUMBER OF PEOPLE IN THE LIBRARY MANAGER OFFICE. TABLE
 1004.1.2 FBC-BUILDING.
  
 G)BASED ON THE SWING OF DOOR IT LOOKS LIKE THE DOOR
 FROM THE RENOVATED BREAK ROOM/DINING IS REDUCING THE
 WIDTH OF THE EGRESS DOOR LEADING TOWARDS THE RECEPTION
 AREA. REVISE AS REQUIRED. SEC. 1003.6 FBC-BUILDING.
  
 H)IT LOOKS LIKE THE TWO EXITS FROM THE SMALL ASSEMBLY
 AREA ON THE EAST SIDE OF THE BUILDING ARE LOCATED LESS
 THAN HALF THE LENGTH OF THE AREA SERVED. REVISE AS
 REQUIRED BY SEC. 1007.1.1 FBC-BUILDING.
  
 10- SECOND FLOOR PLAN ON SHEET S-1:
 A)PROVIDE COMPLIANCE WITH THE WINDOW OPENING PROTECTION
 AS REQUIRED BY SEC. 1015.8 FBC-BUILDING.
  
 B) RENOVATED BEDROOM #7 DOESN'T COMPLY WITH THE MINIMUM
 ROOM DIMENSIONS REQUIRED BY SEC. 1208.1 FBC-BUILDING.
  
 11-FIRST FLOOR PLAN ON SHEET S-1:
 A)DOORS "DR22" AND "DR21" DON'T COMPLY WITH THE MIN.
 32" CLEAR OPENING REQUIRED BY SEC. 1010.1 FBC-BUILDING.
 NOTE: DOUBLE DOORS REQUIRE AT LEAST ONE LEAF TO HAVE
 32" CLEAR OPENING.
  
 B)LAUNDRY ROOM ON THE WEST SIDE OF THE BUILDING
 REQUIRES 1 HOUR FIRE SEPARATION PROTECTION AS REQUIRED
 BY TABLE 509 FBC-BUILDING. PROVIDE COMPLETE DETAILS ANS
 SPECIFICATIONS.
  
 C)RESTROOM ON THE WEST SIDE OF THE BUILDING DOESN'T
 COMPLY WITH SEC. 213.2 FBC-ACCESSIBILITY. ALSO,
 MANEUVERING DIMENSIONS AT THE FOYER AREA LEADING TO THE
 RESTROOM NEEDS TO BE REVISED. SEC. 404.2.4
 FBC-ACCESSIBILITY. PROVIDE COMPLETE COMPLIANCE OR
 DEMONSTRATE HOW IT IS EXEMPTED.
  
 D) RENOVATED BREAKROOM ON THE WEST SIDE OF THE BUILDING
 DOESN'T COMPLY WITH SEC. 212 FBC-ACCESSIBILITY. PROVIDE
 COMPLETE COMPLIANCE OR DEMONSTRATE HOW IT IS EXEMPTED.
  
 E) RESTROOMS ON THE EAST SIDE OF THE BUILDING DOESN'T
 COMPLY WITH SEC. 213.2 FBC-ACCESSIBILITY. THE DOOR
 SWING DOESN'T COMPLY WITH SEC. 603.2.3
 FBC-ACCESSIBILITY. ALSO, MANEUVERING DIMENSIONS AT THE
 FOYER AREA LEADING TO THE RESTROOM NEEDS TO BE REVISED.
 SEC. 404.2.4 FBC-ACCESSIBILITY. PROVIDE COMPLETE
 COMPLIANCE OR DEMONSTRATE HOW IT IS EXEMPTED.
  
 F) PROVIDE COMPLIANCE WITH THE PANIC HARDWARE ON DOORS
 AS REQUIRED BY SEC. 1010.1.10 FBC-BUILDING.
  
 12-RAMP DETAILS ON SHEET S-4: PROVIDE COMPLIANCE WITH
 THE EDGE PROTECTION AS REQUIRED BY SEC. 405.9
 FBC-ACCESSIBILITY.
  
 13- A NEW CERTIFICATE OF OCCUPANCY WILL BE REQUIRED.
 SEC. 1001.2 FBC-EXISTING BUILDING.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-09-24 Cont ID  
Sent By jleahy Date 2019-09-24 Time 07:38 Rev Time 0.00
Received By jleahy Date 2019-09-24 Time 07:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-05-17 Cont ID  
Sent By jleahy Date 2019-05-17 Time 16:32 Rev Time 0.00
Received By jleahy Date 2019-05-10 Time 09:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2020-05-14 Cont ID  
Sent By pleduc Date 2020-05-14 Time   Rev Time 0.00
Received By pleduc Date 2020-05-14 Time 16:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-03-05 Cont ID  
Sent By pleduc Date 2020-03-05 Time   Rev Time 0.00
Received By pleduc Date 2020-03-05 Time 12:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-09-18 Cont ID  
Sent By pleduc Date 2019-09-18 Time   Rev Time 0.00
Received By pleduc Date 2019-09-18 Time 09:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-05-10 Cont ID  
Sent By pleduc Date 2019-05-10 Time   Rev Time 0.00
Received By pleduc Date 2019-05-10 Time 10:27 Sent To  
Notes
2019-05-10 11:10:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHET A 1 - THERE ARE NO DIMENSIONS INDICATED FOR THE
 HALL(EXIT ACCESS CORRIDOR).
  
 PER NFPA 101 CH 12, NEW ASSEMBLY OCCUPANCIES.
  
 12.2.3.8 MINIMUM CORRIDOR WIDTH. THE WIDTH OF ANY EXIT
 ACCESS CORRIDOR SERVING 50 OR MORE PERSONS SHALL BE NOT
 LESS THAN
 44 IN. (1120 MM).
  
  
 2) SHEET LS 1 - THERE IS ONLY ONE EXIT INDICATED FROM
 THE WEST PORTION OF THE 1ST FLOOR
  
 PER NFPA 101 CH 12, NEW ASSEMBLY OCCUPANCIES.
  
 12.2.4* NUMBER OF MEANS OF EGRESS.
 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE
 WITH SECTION 7.4, OTHER THAN EXITS FOR FENCED OUTDOOR
 ASSEMBLY
 OCCUPANCIES IN ACCORDANCE WITH 12.2.4.4.
  
 7.4* NUMBER OF MEANS OF EGRESS.
 7.4.1 GENERAL.
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS
 THAN TWO,
 EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED
 IN CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE
 OR BALCONY WHERE THE COMMON PATH OF TRAVEL LIMITATIONS
 OF
 CHAPTERS 11 THROUGH 43 ARE MET.
  
 PLEASE REVIEW AND CORRECT.
  
  
 3) SHEET LS 1 - THE WEST 2ND FL UNIT SHOWS AN OCCUPANCY
 OF 6; HOWEVER, THERE ARE 4 BEDROOMS WITH DOUBLE BEDS
 INDICATING AN OCCUPANCY LOAD OF 8.
  
 PLEASE REVIEW AND CLARIFY.
  
  
 4) THERE ARE NO INDICATIONS OF STAIRS OR HANDRAILS
 DETAILS.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS
  
 7.2.2.4 GUARDS AND HANDRAILS.
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES,
 UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR
 7.2.2.4.1.6.
 7.2.2.4.1.2 IN ADDITION TO THE HANDRAILS REQUIRED AT
 THE SIDES OF
 STAIRS BY 7.2.2.4.1.1, BOTH OF THE FOLLOWING PROVISIONS
 SHALL APPLY:
 (1) FOR NEW STAIRS, HANDRAILS SHALL BE PROVIDED WITHIN
 30 IN. (760
 MM) OF ALL PORTIONS OF THE REQUIRED EGRESS WIDTH.
 (2) FOR EXISTING STAIRS, HANDRAILS SHALL MEET THE
 FOLLOWING CRITERIA:
 (A) THEY SHALL BE PROVIDED WITHIN 44 IN. (1120 MM) OF
 ALL
 PORTIONS OF THE REQUIRED EGRESS WIDTH.
 (B) SUCH STAIRS SHALL NOT HAVE THEIR EGRESS CAPACITY
 ADJUSTED
 TO A HIGHER OCCUPANT LOAD THAN PERMITTED BY THE
 CAPACITY
 FACTOR IN TABLE 7.3.3.1 IF THE STAIR?S CLEAR WIDTH
 BETWEEN
 HANDRAILS EXCEEDS 60 IN. (1525 MM).
  
 PLEASE REVIEW AND PROVIDE.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2020-05-26 Cont ID  
Sent By jpearson Date 2020-05-26 Time 07:25 Rev Time 0.00
Received By jpearson Date 2020-05-22 Time 14:59 Sent To  
Notes
2020-05-22 14:59:11REVIEWED BY JERRY SMITH.
 19040938 1803 N TAMARIND AVE
  
  
 GAS COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR
 MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL
 GAS INSPECTION.
 CALL 561-805-6692 FOR FURTHER INFORMATION.
  
 INSTALLATION MANUALS FOR ALL GAS EQUIPMENT SHALL BE
 ONSITE FOR GAS INSPECTION. A SEPARATE PERMIT IS
 REQUIRED FOR THE GAS
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 19040938 1803 N TAMARIND AVE
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-03-25 Cont ID  
Sent By jbaker Date 2020-03-25 Time 14:13 Rev Time 0.00
Received By shill Date 2020-03-22 Time 08:24 Sent To  
Notes
2020-03-25 14:14:03REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
 [email protected]
  
  
2020-03-22 08:24:36JBAKER

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-09-21 Cont ID  
Sent By gjohnson Date 2019-09-21 Time 13:17 Rev Time 0.00
Received By gjohnson Date 2019-09-21 Time 13:17 Sent To  
Notes
2019-09-21 13:28:00 
 2ND REVIEW: 19041429
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF
 THE APPLIANCE, A SEDIMENT TRAP SHALL BE INSTALLED
 DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO
 THE INLET OF THE APPLIANCE AS PRACTICAL.PER FBC FG
 408.4
  
 2. PIPING INSTALLED OUTDOORS SHALL BE ELEVATED NOT LESS
 THAN 31/2 INCHES (89 MM) ABOVE GROUND AND WHERE
 INSTALLED ACROSS ROOF SURFACES, SHALL BE ELEVATED NOT
 LESS THAN 31/2 INCHES (89 MM) ABOVE THE ROOF SURFACE.
 PIPING INSTALLED ABOVE GROUND, OUTDOORS, AND INSTALLED
 ACROSS THE SURFACE OF ROOFS SHALL BE SECURELY SUPPORTED
 AND LOCATED WHERE IT WILL BE PROTECTED FROM PHYSICAL
 DAMAGE. WHERE PASSING THROUGH AN OUTSIDE WALL, THE
 PIPING SHALL BE PROTECTED AGAINST CORROSION BY COATING
 OR WRAPPING WITH AN INERT MATERIAL. WHERE PIPING IS
 ENCASED IN A PROTECTIVE PIPE SLEEVE, THE ANNULAR SPACE
 BETWEEN THE PIPING AND THE SLEEVE SHALL BE SEALED.PER
 FBC FG 404.9
  
 3. GALVANIZED PIPING SHALL NOT RUN UNDERGROUND UNLESS
 IT IS SLEEVED. PER FBC FG 404.11
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-05-09 Cont ID  
Sent By gjohnson Date 2019-05-09 Time 13:43 Rev Time 0.00
Received By gjohnson Date 2019-05-09 Time 13:43 Sent To  
Notes
2019-05-09 14:40:15 
 1ST REVIEW: 19041429
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-R SEC. G2413.4.1, G2413.4.2.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
  
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
  
 6. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
  
 7. SHT G-1 DETAIL FOR THE VENT REQUIREMENTS ON TANKLESS
 HEATER IS SHOWING VENTING FOR A INDOOR UNIT THE FLOOR
 PLAN SHOWS AN OUT DOOR UNIT PLEASE CLARIFY. WPB AMEND
 TO FBC 107.2.1
  
 8. THE GAS NOTE IS LISTING FBC FG TABLE 402.4(21) WHICH
 IS FOR POLYETHYLENE PIPE THE PLAN IS SHOWING SCH 40
 METALLIC PIPE. WPB AMEND TO FBC 107.2.1
  
 9. THE TANKLESS WATER HEATER DETAIL IS SHOWING A SINGLE
 HEATER THE PLAN SHOWS TWO HEATERS. WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-02-25 Cont ID  
Sent By jleahy Date 2021-02-25 Time 08:48 Rev Time 0.00
Received By jleahy Date 2021-02-12 Time 10:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-09-09 Cont ID  
Sent By lmarchan Date 2020-09-09 Time 16:53 Rev Time 0.00
Received By lmarchan Date 2020-08-20 Time 10:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-05-28 Cont ID  
Sent By lmarchan Date 2020-05-28 Time 15:08 Rev Time 0.00
Received By lmarchan Date 2020-05-12 Time 11:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-31 Cont ID  
Sent By lmarchan Date 2020-03-31 Time 08:29 Rev Time 0.00
Received By lmarchan Date 2020-01-30 Time 11:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-24 Cont ID  
Sent By shill Date 2019-09-24 Time 07:45 Rev Time 0.00
Received By shill Date 2019-09-04 Time 09:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-03 Cont ID  
Sent By jgomez Date 2019-06-03 Time 18:47 Rev Time 0.00
Received By jgomez Date 2019-05-01 Time 14:39 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-03-18 Cont ID  
Sent By lmarchan Date 2021-03-18 Time 10:15 Rev Time 0.00
Received By lmarchan Date 2021-02-26 Time 13:58 Sent To  
Notes
2021-03-18 10:15:03RECEIPT MU-2021-11554 - $2424.28 - PAID
2021-02-26 13:59:1902/26/21 IMPACT FEES QUESTIONNAIRE UPLOADED. EMAILED
 PBC IMPACT FEES OFFICE. CC

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-06-03 Cont ID  
Sent By jgomez Date 2019-06-03 Time 18:47 Rev Time 0.00
Received By jgomez Date 2019-06-03 Time 18:46 Sent To  
Notes
2019-06-03 18:47:13IMPACT FEES - DIGITAL SUBMITTALS
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-09-20 Cont ID  
Sent By ccole Date 2019-09-20 Time 15:56 Rev Time 0.00
Received By ccole Date 2019-09-20 Time 14:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-15 Cont ID  
Sent By ccole Date 2019-05-15 Time 10:41 Rev Time 0.00
Received By ccole Date 2019-05-15 Time 10:41 Sent To  
Notes
2019-05-15 10:50:441ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040938
 5/15/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE LOUVERED AC CLOSET DOORS SHALL BE
 NON-COMBUSTIBLE IN ACCORDANCE WITH SECTION 602.2 AND
 606.2.2.1 FBC M . THE DOOR SCHEDULE INDICATES THE DOORS
 ARE WOOD.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYERS-
 SECTION 504.1 FBC M. PROVIDE A 100 SQ. IN. MAKEUP AIR
 OPENING FOR THE CLOSETS THAT ARE ENCLOSING DRYERS-
 SECTION 504.6
  
 3) SUBMIT MANUFACTURER'S SPECIFCATIONS FOR THE RANGE
 AND RANGE HOOD- SECTIONS 917.1 AND 505.1 FBC M . PLEASE
 SEE SECTION 505.2 FOR MAKEUP AIR REQUIREMENTS FOR THE
 HOOD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-05-22 Cont ID  
Sent By jpearson Date 2020-05-22 Time 13:25 Rev Time 0.00
Received By jpearson Date 2020-05-22 Time 12:13 Sent To  
Notes
2020-05-22 12:13:48REVIEW BY JERRY SMITH.
 19040938 1803 N TAMARIND AVE
  
 1ST REVIEW
 PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 PLUMBING PROVISO
 SHT. G-1: SANITARY RISER; GROUND FLOOR BACK TO BACK
 BATHROOMS. EXTEND THE VENT SYSTEM TO THE EXTERIOR IN
 ACCORDANCE WITH FBC PL 905.1
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 19040938 1803 N TAMARIND AVE
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-03-25 Cont ID  
Sent By jbaker Date 2020-03-25 Time 13:53 Rev Time 0.00
Received By shill Date 2020-03-22 Time 08:23 Sent To  
Notes
2020-03-22 08:24:07 
 1. 2017 FBC 107.2.1 PLEASE PROVIDE DETAILS FOR ALL
 ROOF PENETRATIONS AND ANY OTHER PENETRATIONS THAT MAY
 BE PLUMBING RELATED.
  
 REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-09-21 Cont ID  
Sent By gjohnson Date 2019-09-21 Time 13:15 Rev Time 0.00
Received By gjohnson Date 2019-09-21 Time 13:15 Sent To  
Notes
2019-09-21 13:15:472ND REVIEW: 19040938
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 212.2,
 804,
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 EXCEPTIONS:1.A PARALLEL APPROACH COMPLYING WITH 305
 SHALL BE PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE
 A COOK TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND
 TO WET BARS.
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 2. THE SINGLE USER BATHROOM ON THE FIRST FLOOR SHALL
 COMPLY WITH FBC ACC 213.2, 213.3.2, 213.3.4
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 3. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE FROM FINISHED FLOOR. PER FBC ACC 609.4
  
 4. SHT S-2 DETAIL #1 THE PLUMBING FIXTURE CLEARANCES
 SHALL COMPLY FBC PL
 405.3.1 WATER CLOSETS, URINALS, LAVATORIES AND BIDETS.
 A WATER CLOSET, URINAL, LAVATORY OR BIDET SHALL NOT BE
 SET CLOSER THAN 15 INCHES (381 MM) FROM ITS CENTER TO
 ANY SIDE WALL, PARTITION, VANITY OR OTHER OBSTRUCTION,
 OR CLOSER THAN 30 INCHES (762 MM) CENTER TO CENTER
 BETWEEN ADJACENT FIXTURES. THERE SHALL BE NOT LESS THAN
 A 21-INCH (533 MM) CLEARANCE IN FRONT OF THE WATER
 CLOSET, URINAL, LAVATORY OR BIDET TO ANY WALL, FIXTURE
 OR DOOR. WATER CLOSET COMPARTMENTS SHALL BE NOT LESS
 THAN 30 INCHES (762 MM) IN WIDTH AND NOT LESS THAN 60
 INCHES (1524 MM) IN DEPTH FOR FLOOR MOUNTED WATER
 CLOSETS AND NOT LESS THAN 30 INCHES (762 MM) IN WIDTH
 AND 56 INCHES (1422 MM) IN DEPTH FOR WALL-HUNG WATER
 CLOSETS. THE DISTANCE BETWEEN THE CENTER OF THE SHOWER
 AND THE CENTER OF THE LAVATORY AND FROM THE CENTER OF
 THE LAVATORY TO THE CENTER OF THE TOILET SHALL BE A MIN
 OF 30".
  
 5. SHT. G-1 THE SANITARY ISOMETRIC DRAWING, NO OTHER
 FIXTURE SHALL CONNECT TO THE WET VENT OF A BATHROOM
 GROUP OTHER THAN 2 TOILETS 2 LAVATORY'S AND 2 TUB OR
 SHOWER'S. THE URINAL IN THE MENS BATHROOM SHALL CONNECT
 DOWN STREAM OF THE BATHROOM GROUP.IN THE LAUNDRY ROOM
 ON THE FIRST FLOOR THE SERVICE SINK SHALL CONNECT DOWN
 STREAM OF THE BATHROOM GROUP. PER FBC PL 912.1
  
 6. THE VENT ON THE TOILET IN THE SINGLE USER BATHROOM
 ON THE FIRST FLOOR IS A HORIZONTAL DRY VENT NOT
 APPROVED, ALL VENTS SHALL CONNECT TO THE TOP OF THE
 HORIZONTAL PIPE AND RUN VERTICALLY UP TO A POINT ABOVE
 FLOOD LEVEL RIM OF THE FIXTURE. PER FBC PL 905.3, 905.4
  
 7. ON THE HOT WATER SYSTEM IF THE FURTHEST FIXTURE IS
 MORE THAN 50' FROM THE SOURCE OF HOT WATER A
 RECIRCULATING SYSTEM IS REQUIRED IT APPEARS THAT ONE OF
 THE BATHROOMS UPSTAIRS MAY BE OVER 50" .
 PER FBC PL 607.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-09 Cont ID  
Sent By gjohnson Date 2019-05-09 Time 13:41 Rev Time 0.00
Received By gjohnson Date 2019-05-09 Time 07:31 Sent To  
Notes
2019-05-09 13:43:131ST REVIEW: 19040938
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE EXCEPTION FROM THE FBC EXISTING 301.1 IS FOR THE
 STRUCTURAL REQUIREMENTS ALL THE NEW PLUMBING AND GAS
 SHALL COMPLY WITH THE FBC PL 2017 6TH EDITION.
  
 2. SHT LS-1 UNDER THE PLUMBING FIXTURE FOR THE FIRST
 FLOOR IT LIST 3 LAVATORY'S FOR MALE THE PLAN ONLY SHOWS
 1 FORE THE WOMEN IT LIST 3 TOILETS AND 3 LAVATORY'S THE
 PLAN ONLY SHOWS 2 INCLUDING THE UNISEX NEXT TO THE
 BREAK ROOM PLEASE CLARIFY SHALL COMPLY WITH FBC PL
 TABLE 403.1
  
 3. SHT. P-1 ALL NEW PLUMBING PLUMBING PIPING AND
 FIXTURES SHALL COMPLY WITH FBC PL 2017 6TH EDITION
  
 4. SHT G-1 THE SANITARY ISOMETRIC DRAWING HAS THE
 FOLLOWING CODE VIOLATIONS PLEASE REVISE. PER WPB AMEND
 TO FBC 107.2.1
 A) THE NEW WATER FOUNTAIN SHALL CONNECT TO THE BUILDING
 DRAIN DOWN STREAM OF THE BATHROOM GROUP. FBC PL 912.1
 B) THE NEW WATER FOUNTAIN IS NOT VENTED PROVIDE
 VENTING. FBC PL 910.1
 C) REMOVE FIXTURES FROM ISOMETRIC IT IS TO CONGESTED TO
 DETERMINE CODE COMPLIANCE.
 D) ON THE SECOND FLOOR THE WASHING MACHINE APPEARS TO
 BE TIED INTO THE TOILET THAT WAS DEMOED REMOVE ALL OLD
 FIXTURES AND CONNECTION PIPING.
 E) ON THE SECOND FLOOR THE LAUNDRY'S AND THE KITCHEN
 SHALL CONNECT DOWN STREAM OF THE BATHROOM GROUPS. FBC
 PL 912.1, 912.1.1
 F) GOOSENECK FITTING ARE NOT APPROVED FITTINGS P-TRAPS
 ARE THE APPROVED CONNECTION. PER WPB AMEND TO FBC
 107.2.1
 G) THE LAUNDRY AND KITCHEN ON THE FIRST FLOOR SHALL
 CONNECT DOWN STREAM OF ANY BATHROOM GROUP. FBC PL 912.1
  
 5. PROVIDE A WATER ISOMETRIC DRAWING. PER WPB AMEND TO
 FBC 107.2.1
  
 6. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC 416.5
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-05-22 Cont ID  
Sent By rmcphers Date 2020-05-22 Time 13:35 Rev Time 0.00
Received By rmcphers Date 2020-05-22 Time 13:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-03-25 Cont ID  
Sent By shill Date 2020-03-25 Time 14:15 Rev Time 0.00
Received By rmcphers Date 2020-05-22 Time 13:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-09-23 Cont ID  
Sent By shill Date 2019-09-23 Time 13:23 Rev Time 0.00
Received By shill Date 2019-09-23 Time 13:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-05-23 Cont ID  
Sent By shill Date 2019-05-23 Time 17:44 Rev Time 0.00
Received By shill Date 2019-05-23 Time 17:44 Sent To  
Notes
2019-05-23 17:51:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLANS DIGITALLY SIGNED BY AN ENGINEER IS TO INCLUDE
 ADDITIONAL LANGUAGE REQUIRED BY FAC61G15-23.004. THIS
 CAN BE VIEWED AT WWW.FBPE.ORG, LAWS AND RULES, FLORIDA
 ADMINISTRATIVE CODE; REVISE PLANS TO INCLUDE (COMMENT
 APPLIES TO ALL THREE ENGINEERS).
  
 2. ALL DIGITAL SIGNATURES ARE OK (PLANS, ENERGY CALC,
 MECHANICAL LOAD CALCS) BUT NEW PAGES SUBMITTED NEXT
 CYCLE REQUIRE VERIFICATION.
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 6 Status P Date 2021-02-24 Cont ID  
Sent By jroach Date 2021-02-24 Time 16:22 Rev Time 0.00
Received By jroach Date 2021-02-24 Time 16:22 Sent To  
Notes
2021-02-24 16:24:10THIS REVIEW IS FOR INTERIOR RENOVATION ONLY!!
 ALL SITE IMPROVEMENTS SHALL REQUIRE SEPARATE PERMITS!
 _______________________________________________________
 _____________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 P: 561.822.1448 | E: [email protected]

Review Stop Z ZONING
Rev No 5 Status F Date 2020-09-09 Cont ID  
Sent By jroach Date 2020-09-09 Time 16:37 Rev Time 0.00
Received By jroach Date 2020-09-09 Time 16:35 Sent To  
Notes
2020-09-09 16:50:09ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.28.2020
 PERMIT NO.: 19040938
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ SATISFIED ] - SITE PLAN (SHEET SP-1) SHOULD SHOW
 THE FINISHED PRODUCT. DEMOLITION CAN BE SHOWN ON THE
 DEMOLITION PLAN. THE SITE PLAN DENOTES A DETAIL FOR THE
 AREA OF THE NEW HANDICAP RAMP AS BEING DETAIL #3 ON
 SHEET D-1, WHICH IS CORRECT, BUT A DETAIL #1 ON SHEET
 SP-1 ALSO PERTAINS TO THIS AREA.
  
 1.1 [ SATISFIED ] - SITE PLAN SHALL SHOW THE PROPOSED
 HANDICAP RAMP. DIMENSIONS SHALL BE PROVIDED FOR THE
 SETBACK BETWEEN THE RAMP AND ADJACENT PROPERTY LINES.
 PROVIDED THAT THE RAMP IS LESS THAN 3 FEET ABOVE GRADE,
 IT MAY PROJECT TO A POINT NO CLOSER THAN 2 FEET TO THE
 PROPERTY LINE. IF THE RAMP IS IN EXCESS OF 3 FEET, IT
 SHALL CONFORM TO THE MINIMUM SETBACK REQUIREMENTS FOR
 THE MAIN BUILDING.
  
 1.2 [ NEW COMMENT ] - ONLY ONE SITE PLAN SHALL BE
 PROVIDED. THERE ARE TWO SHEETS THAT ARE BOTH LABELSED
 SHEET SP-1 AND SHOW DIFFERENT ELEMENTS.
  
 1.3 [ NEW COMMENT ] - SHEET SP-1 PREPARED BY SCHMIDT
 NICHOLS IS NOT THE CURRENT PROPOSED SITE PLAN AND DOES
 NOT ACCURATELY REFLECT THE SCOPE OF WORK THAT IS BEING
 PROPOSED.
  
 2. [ PARTIALLY SATISFIED ] - A CURRENT AND ACCURATE
 SURVEY SHALL BE PROVIDED.
  
 2.1 [ NEW COMMENT ] - THE SHEET FROM COMPASS SURVEYING
 IS SHOWING PROPOSED IMPROVEMENTS. THE IMPROVEMENTS
 SHOWN THEREON DO NOT MATCH THE CURRENT PROPOSED SITE
 IMPROVEMENTS.
  
 3. [ PARTIALLY SATISFIED ] - PURSUANT TO SECTION 94-441
 OF THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS), BECAUSE THE PROPOSED SCOPE OF WORK EXCEEDS 50
 PERCENT OF THE VALUE OF THE EXISTING STRUCTURE, THE
 SITE SHALL BE BROUGHT INTO COMPLIANCE WITH ARTICLE XIV
 (LANDSCAPING) OF THE ZLDRS, INCLUDING THE EXISTING
 PARKING LOT. PLANS SHALL BE SUBMITTED INDICATING SUCH.
 IF EXISTING MATERIAL IS SHOWN ON THE PLANS AND ALL
 PROVISIONS OF ARTICLE XIV HAVE BEEN MET, THEN NO
 ADDITIONAL PERMIT/INSTALLATION IS REQUIRED. IF THE
 EXISTING MATERIAL ON SITE DOES NOT CONFORM TO ALL OF
 THE REQUIREMENTS OF ARTICLE XIV, THEN ADDITIONAL
 MATERIAL WILL NEED TO BE SHOWN ON THE PLANS AND
 PERMITTED UNDER A SEPARATE LANDSCAPE PERMIT. PLEASE
 NOTE THAT PLANS SHOULD INCLUDE, BUT NOT BE LIMITED TO,
 THE FOLLOWING:
  
 3.1. [ SATISFIED ] - THE LOCATION OF ALL EXISTING AND
 PROPOSED STRUCTURES, IMPROVEMENTS, ETC.
  
 3.2. [ SATISFIED ] - THE LOCATION OF ALL EXISTING AND
 PROPOSED TREES, SHRUBS, GROUND COVERS, ETC.
  
 3.3. [ SATISFIED ] - THE LOCATION OF UTILITY AND
 DRAINAGE EASEMENTS, OVERHEAD LINES, WATER METERS,
 TRANSFORMERS, CHECK VALVES, CLEAN OUTS, FIRE HYDRANTS,
 LIGHT POLES, ETC. THAT MAY IMPACT LANDSCAPING.
  
 3.4. [ SATISFIED ] - TABULATION TABLE INDICATING HOW
 THE EXISTING AND PROPOSED PLANT MATERIAL COMPLIES WITH
 ARTICLE XIV.
  
 3.5. [ SATISFIED ] - SPECIES, QUANTITY, HEIGHT, SPREAD,
 SPACING, AND LOCATION OF THE EXISTING AND PROPOSED
 PLANT MATERIAL.
  
 3.6. [ SATISFIED ] - STATEMENT THAT ALL LANDSCAPE AREAS
 WILL BE PROVIDED WITH A PERMANENT AUTOMATIC IRRIGATION
 SYSTEM, INCLUDING THE ADJACENT RIGHT-OF-WAY (PLEASE
 NOTE THAT ANY NEW IRRIGATION SHALL BE DONE UNDER A
 SEPARATE PERMIT).
  
 3.7 [ NEW COMMENT ] - LANDSCAPE PLANS SHOULD NOT BE
 INCLUDED IN THE BUILDING PERMIT APPLICATION AS THEY
 HAVE BEEN SUBMITTED AS A SEPARATE PERMIT.
  
 4. [ NOT SATISFIED ] - A/C UNITS SHALL BE SHOWN ON THE
 SITE PLAN (THEY ARE SHOWN ON THE PLAN PREPARED BY
 SCHMIDT NICHOLS, BUT NOT DKK) AND SHALL NOT ENCROACH
 MORE THAN FOUR (4) FEET INTO THE REQUIRED SIDE SETBACK.
 ARE THERE EXISTING A/C UNITS IN THAT LOCATION?
  
 4.1 [ NEW COMMENT ] - DIMENSIONS WERE NOT PROVIDED TO
 INDICATE COMPLIANCE WITH THE MAXIMUM FOUR (4) FOOT
 ENCROACHMENT.
  
 5. [ SATISFIED ] - PLEASE PROVIDE A DETAIL/SECTION OF
 THE WINDOW INSTALLATION. PURSUANT TO SEC. 94-222(H)(6)
 OF THE CITY?S ZLDRS, WINDOWS SHALL BE RECESSED A
 MINIMUM OF TWO INCHES FROM THE EXTERIOR FACE OF THE
 FACADE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 4 Status F Date 2020-05-28 Cont ID  
Sent By jroach Date 2020-05-28 Time 13:40 Rev Time 0.00
Received By jroach Date 2020-05-28 Time 13:39 Sent To  
Notes
2020-05-28 14:11:58ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.28.2020
 PERMIT NO.: 19040938
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ SATISFIED ] - SITE PLAN (SHEET SP-1) SHOULD SHOW
 THE FINISHED PRODUCT. DEMOLITION CAN BE SHOWN ON THE
 DEMOLITION PLAN. THE SITE PLAN DENOTES A DETAIL FOR THE
 AREA OF THE NEW HANDICAP RAMP AS BEING DETAIL #3 ON
 SHEET D-1, WHICH IS CORRECT, BUT A DETAIL #1 ON SHEET
 SP-1 ALSO PERTAINS TO THIS AREA.
  
 1.1 [ SATISFIED ] - SITE PLAN SHALL SHOW THE PROPOSED
 HANDICAP RAMP. DIMENSIONS SHALL BE PROVIDED FOR THE
 SETBACK BETWEEN THE RAMP AND ADJACENT PROPERTY LINES.
 PROVIDED THAT THE RAMP IS LESS THAN 3 FEET ABOVE GRADE,
 IT MAY PROJECT TO A POINT NO CLOSER THAN 2 FEET TO THE
 PROPERTY LINE. IF THE RAMP IS IN EXCESS OF 3 FEET, IT
 SHALL CONFORM TO THE MINIMUM SETBACK REQUIREMENTS FOR
 THE MAIN BUILDING.
  
 2. [ NOT SATISFIED ] - A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED.
  
 3. [ NOT SATISFIED ] - PURSUANT TO SECTION 94-441 OF
 THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS), BECAUSE THE PROPOSED SCOPE OF WORK EXCEEDS 50
 PERCENT OF THE VALUE OF THE EXISTING STRUCTURE, THE
 SITE SHALL BE BROUGHT INTO COMPLIANCE WITH ARTICLE XIV
 (LANDSCAPING) OF THE ZLDRS, INCLUDING THE EXISTING
 PARKING LOT. PLANS SHALL BE SUBMITTED INDICATING SUCH.
 IF EXISTING MATERIAL IS SHOWN ON THE PLANS AND ALL
 PROVISIONS OF ARTICLE XIV HAVE BEEN MET, THEN NO
 ADDITIONAL PERMIT/INSTALLATION IS REQUIRED. IF THE
 EXISTING MATERIAL ON SITE DOES NOT CONFORM TO ALL OF
 THE REQUIREMENTS OF ARTICLE XIV, THEN ADDITIONAL
 MATERIAL WILL NEED TO BE SHOWN ON THE PLANS AND
 PERMITTED UNDER A SEPARATE LANDSCAPE PERMIT. PLEASE
 NOTE THAT PLANS SHOULD INCLUDE, BUT NOT BE LIMITED TO,
 THE FOLLOWING:
  
 3.1. [ NOT SATISFIED ] - THE LOCATION OF ALL EXISTING
 AND PROPOSED STRUCTURES, IMPROVEMENTS, ETC.
  
 3.2. [ NOT SATISFIED ] - THE LOCATION OF ALL EXISTING
 AND PROPOSED TREES, SHRUBS, GROUND COVERS, ETC.
  
 3.3. [ NOT SATISFIED ] - THE LOCATION OF UTILITY AND
 DRAINAGE EASEMENTS, OVERHEAD LINES, WATER METERS,
 TRANSFORMERS, CHECK VALVES, CLEAN OUTS, FIRE HYDRANTS,
 LIGHT POLES, ETC. THAT MAY IMPACT LANDSCAPING.
  
 3.4. [ NOT SATISFIED ] - TABULATION TABLE INDICATING
 HOW THE EXISTING AND PROPOSED PLANT MATERIAL COMPLIES
 WITH ARTICLE XIV.
  
 3.5. [ NOT SATISFIED ] - SPECIES, QUANTITY, HEIGHT,
 SPREAD, SPACING, AND LOCATION OF THE EXISTING AND
 PROPOSED PLANT MATERIAL.
  
 3.6. [ NOT SATISFIED ] - STATEMENT THAT ALL LANDSCAPE
 AREAS WILL BE PROVIDED WITH A PERMANENT AUTOMATIC
 IRRIGATION SYSTEM, INCLUDING THE ADJACENT RIGHT-OF-WAY
 (PLEASE NOTE THAT ANY NEW IRRIGATION SHALL BE DONE
 UNDER A SEPARATE PERMIT).
  
 4. [ NOT SATISFIED ] - A/C UNITS SHALL BE SHOWN ON THE
 SITE PLAN AND SHALL NOT ENCROACH MORE THAN FOUR (4)
 FEET INTO THE REQUIRED SIDE SETBACK. ARE THERE EXISTING
 A/C UNITS IN THAT LOCATION?
  
 5. [ SATISFIED ] - PLEASE PROVIDE A DETAIL/SECTION OF
 THE WINDOW INSTALLATION. PURSUANT TO SEC. 94-222(H)(6)
 OF THE CITY?S ZLDRS, WINDOWS SHALL BE RECESSED A
 MINIMUM OF TWO INCHES FROM THE EXTERIOR FACE OF THE
 FACADE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 3 Status F Date 2020-03-31 Cont ID  
Sent By jroach Date 2020-03-31 Time 08:21 Rev Time 0.00
Received By jroach Date 2020-03-31 Time 08:21 Sent To  
Notes
2020-03-31 08:23:10ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.31.2020
 PERMIT NO.: 19040938
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ NOT SATISFIED ] - SITE PLAN (SHEET SP-1) SHOULD
 SHOW THE FINISHED PRODUCT. DEMOLITION CAN BE SHOWN ON
 THE DEMOLITION PLAN. THE SITE PLAN DENOTES A DETAIL FOR
 THE AREA OF THE NEW HANDICAP RAMP AS BEING DETAIL #3 ON
 SHEET D-1, WHICH IS CORRECT, BUT A DETAIL #1 ON SHEET
 SP-1 ALSO PERTAINS TO THIS AREA.
  
 1.1 [ NEW COMMENT ] - SITE PLAN SHALL SHOW THE PROPOSED
 HANDICAP RAMP. DIMENSIONS SHALL BE PROVIDED FOR THE
 SETBACK BETWEEN THE RAMP AND ADJACENT PROPERTY LINES.
 PROVIDED THAT THE RAMP IS LESS THAN 3 FEET ABOVE GRADE,
 IT MAY PROJECT TO A POINT NO CLOSER THAN 2 FEET TO THE
 PROPERTY LINE. IF THE RAMP IS IN EXCESS OF 3 FEET, IT
 SHALL CONFORM TO THE MINIMUM SETBACK REQUIREMENTS FOR
 THE MAIN BUILDING.
  
 2. [ NOT SATISFIED ] - A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED.
  
 3. [ NOT SATISFIED ] - PURSUANT TO SECTION 94-441 OF
 THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS), BECAUSE THE PROPOSED SCOPE OF WORK EXCEEDS 50
 PERCENT OF THE VALUE OF THE EXISTING STRUCTURE, THE
 SITE SHALL BE BROUGHT INTO COMPLIANCE WITH ARTICLE XIV
 (LANDSCAPING) OF THE ZLDRS, INCLUDING THE EXISTING
 PARKING LOT. PLANS SHALL BE SUBMITTED INDICATING SUCH.
 IF EXISTING MATERIAL IS SHOWN ON THE PLANS AND ALL
 PROVISIONS OF ARTICLE XIV HAVE BEEN MET, THEN NO
 ADDITIONAL PERMIT/INSTALLATION IS REQUIRED. IF THE
 EXISTING MATERIAL ON SITE DOES NOT CONFORM TO ALL OF
 THE REQUIREMENTS OF ARTICLE XIV, THEN ADDITIONAL
 MATERIAL WILL NEED TO BE SHOWN ON THE PLANS AND
 PERMITTED UNDER A SEPARATE LANDSCAPE PERMIT. PLEASE
 NOTE THAT PLANS SHOULD INCLUDE, BUT NOT BE LIMITED TO,
 THE FOLLOWING:
  
 3.1. [ NOT SATISFIED ] - THE LOCATION OF ALL EXISTING
 AND PROPOSED STRUCTURES, IMPROVEMENTS, ETC.
  
 3.2. [ NOT SATISFIED ] - THE LOCATION OF ALL EXISTING
 AND PROPOSED TREES, SHRUBS, GROUND COVERS, ETC.
  
 3.3. [ NOT SATISFIED ] - THE LOCATION OF UTILITY AND
 DRAINAGE EASEMENTS, OVERHEAD LINES, WATER METERS,
 TRANSFORMERS, CHECK VALVES, CLEAN OUTS, FIRE HYDRANTS,
 LIGHT POLES, ETC. THAT MAY IMPACT LANDSCAPING.
  
 3.4. [ NOT SATISFIED ] - TABULATION TABLE INDICATING
 HOW THE EXISTING AND PROPOSED PLANT MATERIAL COMPLIES
 WITH ARTICLE XIV.
  
 3.5. [ NOT SATISFIED ] - SPECIES, QUANTITY, HEIGHT,
 SPREAD, SPACING, AND LOCATION OF THE EXISTING AND
 PROPOSED PLANT MATERIAL.
  
 3.6. [ NOT SATISFIED ] - STATEMENT THAT ALL LANDSCAPE
 AREAS WILL BE PROVIDED WITH A PERMANENT AUTOMATIC
 IRRIGATION SYSTEM, INCLUDING THE ADJACENT RIGHT-OF-WAY
 (PLEASE NOTE THAT ANY NEW IRRIGATION SHALL BE DONE
 UNDER A SEPARATE PERMIT).
  
 4. [ NOT SATISFIED ] - A/C UNITS SHALL BE SHOWN ON THE
 SITE PLAN AND SHALL NOT ENCROACH MORE THAN FOUR (4)
 FEET INTO THE REQUIRED SIDE SETBACK. ARE THERE EXISTING
 A/C UNITS IN THAT LOCATION?
  
 5. [ NOT SATISFIED ] - PLEASE PROVIDE A DETAIL/SECTION
 OF THE WINDOW INSTALLATION. PURSUANT TO SEC.
 94-222(H)(6) OF THE CITY?S ZLDRS, WINDOWS SHALL BE
 RECESSED A MINIMUM OF TWO INCHES FROM THE EXTERIOR FACE
 OF THE FACADE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-09-12 Cont ID  
Sent By jroach Date 2019-09-12 Time 13:51 Rev Time 0.00
Received By jroach Date 2019-09-12 Time 12:07 Sent To  
Notes
2019-09-12 13:51:08ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 09.12.2019
 PERMIT NO.: 19040938
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ NOT SATISFIED ] - SITE PLAN (SHEET SP-1) SHOULD
 SHOW THE FINISHED PRODUCT. DEMOLITION CAN BE SHOWN ON
 THE DEMOLITION PLAN. THE SITE PLAN DENOTES A DETAIL FOR
 THE AREA OF THE NEW HANDICAP RAMP AS BEING DETAIL #3 ON
 SHEET D-1, WHICH IS CORRECT, BUT A DETAIL #1 ON SHEET
 SP-1 ALSO PERTAINS TO THIS AREA.
  
 1.1 [ NEW COMMENT ] - SITE PLAN SHALL SHOW THE PROPOSED
 HANDICAP RAMP. DIMENSIONS SHALL BE PROVIDED FOR THE
 SETBACK BETWEEN THE RAMP AND ADJACENT PROPERTY LINES.
 PROVIDED THAT THE RAMP IS LESS THAN 3 FEET ABOVE GRADE,
 IT MAY PROJECT TO A POINT NO CLOSER THAN 2 FEET TO THE
 PROPERTY LINE. IF THE RAMP IS IN EXCESS OF 3 FEET, IT
 SHALL CONFORM TO THE MINIMUM SETBACK REQUIREMENTS FOR
 THE MAIN BUILDING.
  
 2. [ NOT SATISFIED ] - A CURRENT AND ACCURATE SURVEY
 SHALL BE PROVIDED.
  
 3. [ NOT SATISFIED ] - PURSUANT TO SECTION 94-441 OF
 THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS), BECAUSE THE PROPOSED SCOPE OF WORK EXCEEDS 50
 PERCENT OF THE VALUE OF THE EXISTING STRUCTURE, THE
 SITE SHALL BE BROUGHT INTO COMPLIANCE WITH ARTICLE XIV
 (LANDSCAPING) OF THE ZLDRS, INCLUDING THE EXISTING
 PARKING LOT. PLANS SHALL BE SUBMITTED INDICATING SUCH.
 IF EXISTING MATERIAL IS SHOWN ON THE PLANS AND ALL
 PROVISIONS OF ARTICLE XIV HAVE BEEN MET, THEN NO
 ADDITIONAL PERMIT/INSTALLATION IS REQUIRED. IF THE
 EXISTING MATERIAL ON SITE DOES NOT CONFORM TO ALL OF
 THE REQUIREMENTS OF ARTICLE XIV, THEN ADDITIONAL
 MATERIAL WILL NEED TO BE SHOWN ON THE PLANS AND
 PERMITTED UNDER A SEPARATE LANDSCAPE PERMIT. PLEASE
 NOTE THAT PLANS SHOULD INCLUDE, BUT NOT BE LIMITED TO,
 THE FOLLOWING:
  
 3.1. [ NOT SATISFIED ] - THE LOCATION OF ALL EXISTING
 AND PROPOSED STRUCTURES, IMPROVEMENTS, ETC.
  
 3.2. [ NOT SATISFIED ] - THE LOCATION OF ALL EXISTING
 AND PROPOSED TREES, SHRUBS, GROUND COVERS, ETC.
  
 3.3. [ NOT SATISFIED ] - THE LOCATION OF UTILITY AND
 DRAINAGE EASEMENTS, OVERHEAD LINES, WATER METERS,
 TRANSFORMERS, CHECK VALVES, CLEAN OUTS, FIRE HYDRANTS,
 LIGHT POLES, ETC. THAT MAY IMPACT LANDSCAPING.
  
 3.4. [ NOT SATISFIED ] - TABULATION TABLE INDICATING
 HOW THE EXISTING AND PROPOSED PLANT MATERIAL COMPLIES
 WITH ARTICLE XIV.
  
 3.5. [ NOT SATISFIED ] - SPECIES, QUANTITY, HEIGHT,
 SPREAD, SPACING, AND LOCATION OF THE EXISTING AND
 PROPOSED PLANT MATERIAL.
  
 3.6. [ NOT SATISFIED ] - STATEMENT THAT ALL LANDSCAPE
 AREAS WILL BE PROVIDED WITH A PERMANENT AUTOMATIC
 IRRIGATION SYSTEM, INCLUDING THE ADJACENT RIGHT-OF-WAY
 (PLEASE NOTE THAT ANY NEW IRRIGATION SHALL BE DONE
 UNDER A SEPARATE PERMIT).
  
 4. [ NOT SATISFIED ] - A/C UNITS SHALL BE SHOWN ON THE
 SITE PLAN AND SHALL NOT ENCROACH MORE THAN FOUR (4)
 FEET INTO THE REQUIRED SIDE SETBACK. ARE THERE EXISTING
 A/C UNITS IN THAT LOCATION?
  
 5. [ NOT SATISFIED ] - PLEASE PROVIDE A DETAIL/SECTION
 OF THE WINDOW INSTALLATION. PURSUANT TO SEC.
 94-222(H)(6) OF THE CITY?S ZLDRS, WINDOWS SHALL BE
 RECESSED A MINIMUM OF TWO INCHES FROM THE EXTERIOR FACE
 OF THE FACADE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-05-21 Cont ID  
Sent By jroach Date 2019-05-21 Time 14:18 Rev Time 0.00
Received By jroach Date 2019-05-21 Time 14:18 Sent To  
Notes
2019-05-21 14:18:38ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.21.2019
 PERMIT NO.: 19040938
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. SITE PLAN (SHEET SP-1) SHOULD SHOW THE FINISHED
 PRODUCT. DEMOLITION CAN BE SHOWN ON THE DEMOLITION
 PLAN. THE SITE PLAN DENOTES A DETAIL FOR THE AREA OF
 THE NEW HANDICAP RAMP AS BEING DETAIL #3 ON SHEET D-1,
 WHICH IS CORRECT, BUT A DETAIL #1 ON SHEET SP-1 ALSO
 PERTAINS TO THIS AREA.
  
 2. A CURRENT AND ACCURATE SURVEY SHALL BE PROVIDED.
  
 3. PURSUANT TO SECTION 94-441 OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS), BECAUSE THE
 PROPOSED SCOPE OF WORK EXCEEDS 50 PERCENT OF THE VALUE
 OF THE EXISTING STRUCTURE, THE SITE SHALL BE BROUGHT
 INTO COMPLIANCE WITH ARTICLE XIV (LANDSCAPING) OF THE
 ZLDRS, INCLUDING THE EXISTING PARKING LOT. PLANS SHALL
 BE SUBMITTED INDICATING SUCH. IF EXISTING MATERIAL IS
 SHOWN ON THE PLANS AND ALL PROVISIONS OF ARTICLE XIV
 HAVE BEEN MET, THEN NO ADDITIONAL PERMIT/INSTALLATION
 IS REQUIRED. IF THE EXISTING MATERIAL ON SITE DOES NOT
 CONFORM TO ALL OF THE REQUIREMENTS OF ARTICLE XIV, THEN
 ADDITIONAL MATERIAL WILL NEED TO BE SHOWN ON THE PLANS
 AND PERMITTED UNDER A SEPARATE LANDSCAPE PERMIT. PLEASE
 NOTE THAT PLANS SHOULD INCLUDE, BUT NOT BE LIMITED TO,
 THE FOLLOWING:
  
 3.1. THE LOCATION OF ALL EXISTING AND PROPOSED
 STRUCTURES, IMPROVEMENTS, ETC.
  
 3.2. THE LOCATION OF ALL EXISTING AND PROPOSED TREES,
 SHRUBS, GROUND COVERS, ETC.
  
 3.3. THE LOCATION OF UTILITY AND DRAINAGE EASEMENTS,
 OVERHEAD LINES, WATER METERS, TRANSFORMERS, CHECK
 VALVES, CLEAN OUTS, FIRE HYDRANTS, LIGHT POLES, ETC.
 THAT MAY IMPACT LANDSCAPING.
  
 3.4. TABULATION TABLE INDICATING HOW THE EXISTING AND
 PROPOSED PLANT MATERIAL COMPLIES WITH ARTICLE XIV.
  
 3.5. SPECIES, QUANTITY, HEIGHT, SPREAD, SPACING, AND
 LOCATION OF THE EXISTING AND PROPOSED PLANT MATERIAL.
  
 3.6. STATEMENT THAT ALL LANDSCAPE AREAS WILL BE
 PROVIDED WITH A PERMANENT AUTOMATIC IRRIGATION SYSTEM,
 INCLUDING THE ADJACENT RIGHT-OF-WAY (PLEASE NOTE THAT
 ANY NEW IRRIGATION SHALL BE DONE UNDER A SEPARATE
 PERMIT).
  
 4. A/C UNITS SHALL BE SHOWN ON THE SITE PLAN AND SHALL
 NOT ENCROACH MORE THAN FOUR (4) FEET INTO THE REQUIRED
 SIDE SETBACK. ARE THERE EXISTING A/C UNITS IN THAT
 LOCATION?
  
 5. PLEASE PROVIDE A DETAIL/SECTION OF THE WINDOW
 INSTALLATION. PURSUANT TO SEC. 94-222(H)(6) OF THE
 CITY?S ZLDRS, WINDOWS SHALL BE RECESSED A MINIMUM OF
 TWO INCHES FROM THE EXTERIOR FACE OF THE FACADE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH