Plan Review Details - Permit 19040937
Plan Review Stops For Permit 19040937
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-07-11 Cont ID  
Sent By dbattles Date 2019-07-11 Time 08:23 Rev Time 0.00
Received By dbattles Date 2019-07-11 Time 08:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-06-28 Cont ID  
Sent By dbattles Date 2019-06-28 Time 16:28 Rev Time 0.00
Received By dbattles Date 2019-06-28 Time 16:28 Sent To  
Notes
2019-06-28 16:32:38BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19040937
 REVIEWED: JUNE 28, 2019
  
 PREVIOUS COMMENT NOT ADDRESSED.
 PLEASE SUPPLY THE GEOTECHNICAL REPORT. ADD TO
 SUPPORTING DOCUMENTS IN PROJECTDOX.
 I E-MAILED [email protected] TO GET VIA E-MAIL AND
 UPLOAD THIS REVIEW CYCLE, BUT I DIDN'T RECEIVE A
 RESPONSE.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-24 Cont ID  
Sent By jduprey Date 2019-04-24 Time 11:40 Rev Time 0.00
Received By jduprey Date 2019-04-24 Time 10:32 Sent To  
Notes
2019-04-24 11:39:55BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE GEOTECHNICAL REPORT. THE SOIL COMPACTION
 REQUIREMENT IS NOT SPECIFY ON THE STRUCTURAL DRAWINGS.
 THE GENERAL NOTES ONLY MAKE REFERENCE TO THE
 GEOTECHNICAL REPORT. FBC 107
  
 2. THE DRAWING SHEET S-100 DETAIL #2 SHOW THE
 CONNECTION BETWEEN THE PRE-CAST COLUMN AND FOUNDATION
 APPEARS TO BE THRU ANCHOR BOLTS AND STEEL PLATE.
 HOWEVER SPECIFICATIONS FOR THIS ANCHOR BOLTS AND PLATES
 WERE NOT PROVIDED. PLEASE PROVIDE STEEL GRADE,
 DIAMETER, AND DIMENSIONS FOR THE CONNECTION. FBC 107
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-09 Cont ID  
Sent By jpearson Date 2019-07-09 Time 09:38 Rev Time 0.00
Received By jpearson Date 2019-07-09 Time 09:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By jpearson Date 2019-05-14 Time 14:24 Rev Time 0.00
Received By jpearson Date 2019-05-14 Time 14:24 Sent To I
Notes
2019-05-14 14:23:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 2. INDICATE WIRE SIZES ON PLAN. PROVIDE VOLTAGE DROP
 INFORMATION. WPB FBC 107.2.1
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-13 Cont ID  
Sent By pleduc Date 2019-06-13 Time   Rev Time 0.00
Received By pleduc Date 2019-06-11 Time 14:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-05-08 Cont ID  
Sent By pleduc Date 2019-05-08 Time   Rev Time 0.00
Received By pleduc Date 2019-05-08 Time 09:59 Sent To  
Notes
2019-05-08 10:24:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET C 1.1, A 101 & 102 - THERE ARE INDICATIONS OF
 A NEW GATE WITH INGRESS-EGRESS LANES. THERE LANE ARE
 INDICATED WITH DIMENSIONS LESS THAN THE REQUIRED
 20'(2'9" INGRESS AND 13'6" EGRESS) FIRE LANES FOR FIRE
 DEPARTMENT APPARATUS ACCESS.
  
 PER NFPA 1
  
 18.2.3.4 SPECIFICATIONS.
 18.2.3.4.1 DIMENSIONS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FT (6.1 M).
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 2) SHEET C 1.1, A 101 & 102 - THERE ARE INDICATIONS OF
 A NEW GATE WITH INGRESS-EGRESS LANES. GATES ARE
 REQUIRED TO BE ACCESSIBLE FOR THE FD.
  
 18.2.2* ACCESS TO STRUCTURES OR AREAS.
 18.2.2.1 ACCESS BOX(ES). THE AHJ SHALL HAVE THE
 AUTHORITY TO REQUIRE
 AN ACCESS BOX(ES) TO BE INSTALLED IN AN ACCESSIBLE
 LOCATION WHERE
 ACCESS TO OR WITHIN A STRUCTURE OR AREA IS DIFFICULT
 BECAUSE OF SECURITY.
 THE ACCESS BOX(ES) SHALL BE OF AN APPROVED TYPE LISTED
 IN ACCORDANCE
 WITH UL 1037.
  
 A KNOX KEY SWITCH SYSTEM IS RECOMMENDED.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-11 Cont ID  
Sent By dbattles Date 2019-07-11 Time 08:23 Rev Time 0.00
Received By dbattles Date 2019-07-09 Time 07:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-07-09 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-10 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-05-14 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-19 Time 15:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-20 Cont ID  
Sent By gjohnson Date 2019-06-20 Time 12:51 Rev Time 0.00
Received By gjohnson Date 2019-06-20 Time 11:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-01 Cont ID  
Sent By thunt Date 2019-05-01 Time 08:36 Rev Time 0.00
Received By thunt Date 2019-05-01 Time 08:35 Sent To  
Notes
2019-05-01 08:40:08PLUMBING 1ST REVIEW**DENIED**
  
 1) A SEPERATE IRRIGATION PERMIT SHALL BE REQUIRED FOR
 THE RELOCATION OF THE MAIN IRRIGATION LINE AND
 CONNECTION TO THE EXISTING BACKFLOW DEVICE AS CALLED
 OUT ON SHT. IP.0, IP-1, IP-2 FOR THE INSTALLATION OF
 THE NEW WALL. FBC 105.1
  
 2) WILL THE BACKFLOW DEVICES BE RELOCATED? FBC 107.2.1.
 PLEASE PROVIDE LOCATION ON PLAN.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-07-11 Cont ID  
Sent By dbattles Date 2019-07-11 Time 08:23 Rev Time 0.00
Received By dbattles Date 2019-07-11 Time 08:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-07-03 Cont ID  
Sent By shill Date 2019-07-03 Time 14:14 Rev Time 0.00
Received By shill Date 2019-07-03 Time 14:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By jpearson Date 2019-05-14 Time 14:23 Rev Time 0.00
Received By jpearson Date 2019-04-24 Time 11:40 Sent To  
Notes
2019-05-14 14:24:14ALL SIGNATURES GOOD FOR THIS REVIEW. WILL NEED TO CHECK
 ANY SHEETS SUBMITTED NEXT REVIEW CYCLE. WPB FBC 107.1
2019-05-01 08:35:35ALL PAGES OK
2019-04-24 11:40:23BUILDING - OK

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2019-06-26 Time   Rev Time 0.00
Received By pgreilic Date 2019-06-26 Time 09:05 Sent To  
Notes
2019-06-26 09:06:471.) A MINOR PLANNED DEVELOPMENT AMENDMENT WILL BE
 REQUIRED PRIOR TO ISSUANCE OF FINAL CERTIFICATE OF
 OCCUPANCY
 2.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By pgreilic Date 2019-05-01 Time   Rev Time 0.00
Received By pgreilic Date 2019-05-01 Time 10:16 Sent To  
Notes
2019-05-01 10:17:291.) INCLUDE APPROVED SITE PLAN IN PERMIT SET PER MINOR
 PD AMENDMENT
  
 2.) SEPARATE LANDSCAPE PERMIT REQUIRED, LANDSCAPE PAGES
 TO BE REMOVED FROM BUILDING PERMIT
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]