Plan Review Details - Permit 19040819
Plan Review Stops For Permit 19040819
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-11-13 Cont ID  
Sent By rmcdouga Date 2019-11-13 Time 08:56 Rev Time 0.00
Received By rmcdouga Date 2019-11-13 Time 08:56 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-13 Cont ID  
Sent By jduprey Date 2019-05-13 Time 10:16 Rev Time 0.00
Received By jduprey Date 2019-05-13 Time 10:13 Sent To  
Notes
2019-05-13 10:21:30BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE ANCHOR DETAIL MUST BE SIGNED AND SEAL IN
 ORIGINAL BY THE ENGINEER, COPIES WERE PROVIDED. PLANS
 THAT HAVE BEEN PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE, DATE AND
 SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-11-06 Cont ID  
Sent By fgiaquin Date 2019-11-06 Time 06:11 Rev Time 0.00
Received By fgiaquin Date 2019-11-06 Time 05:52 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-08 Cont ID  
Sent By fgiaquin Date 2019-05-08 Time 16:48 Rev Time 0.00
Received By fgiaquin Date 2019-05-08 Time 16:26 Sent To  
Notes
2019-05-08 16:48:31ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. SHOW SIZE OF TAPPED FEEDER CONDUCTORS FBC 107.2.1
  
 3. SHOW SIZE OF GENERATOR FEEDER. FBC 107.2.1
  
 4. ONE-LINE DIAGRAM SHOWS 3 MAINS AND 3 EXISTING PANELS
 THEN ANOTHER ONE-LINE DIAGRAMS SHOWS 1 MAIN AND PANEL
 BEING REMOVED. WHICH IS IT? FBC 107.2.1
  
 5. PLANS SHOW 60KW GENERATOR BUT PERMIT SAYS 22KW
 GENERATOR? PLEASE CLARIFY. FBC 107.2.1
  
 6. TRANSFER SWITCH SHOWN IN CUT SHEETS IS RATED AT
 100AMPS. MINIMUM 400AMP RATED TRANSFER SWITCH REQUIRED.
 NEC 110.3B
  
 7. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF GENERATOR
 AND TRANSFER SWITCH. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-11-13 Cont ID  
Sent By tklarge Date 2019-11-13 Time 06:45 Rev Time 0.00
Received By tklarge Date 2019-11-13 Time 06:16 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-24 Cont ID  
Sent By thunt Date 2019-04-24 Time 08:11 Rev Time 0.00
Received By thunt Date 2019-04-24 Time 07:51 Sent To  
Notes
2019-04-24 08:12:44GAS 1ST REVIEW**DENIED**
  
 1) PLANS/ SUBMITTAL DOCUMENTS THAT BEAR THE NAME, TITLE
 BLOCK AND OR LICENSE NUMBER OF A DESIGN PROFESSIONAL
 SHALL BE WET SIGNED AND SEAL. FAC 61G15-23.001. FL ST
 471,481. ALL OTHER PLANS/ SUBMITTAL DOCS SHALL BE
 SIGNED AND DATE MY PERSON TAKING RESPONSIBILITY.
  
 2) WHAT PIPING SIZE AND MATERIAL IS ABOVEGROUND? SHOW
 THE TYPE OF ALL PIPE MATERIAL BEING INSTALLED, ALL PIPE
 SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 3)SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION.
 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
  
 4)AT SOME POINT YOU SYSTEM CHANGES TO .5 LB. PLEASE
 SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES USED
 TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 5)I THIS A NEW OR EXISTING GAS METER/ SYSTEM? PLEASE
 CLARIFY. IF EXISTING THE BTU LOAD OF THE EXISTING GAS
 SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE
 SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED.
 IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 6) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD.
  
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-11-13 Cont ID  
Sent By rmcdouga Date 2019-11-13 Time 08:56 Rev Time 0.00
Received By rmcdouga Date 2019-10-30 Time 14:04 Sent To  
Notes
2019-10-31 14:04:50RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-13 Cont ID  
Sent By jduprey Date 2019-05-13 Time 10:21 Rev Time 0.00
Received By jduprey Date 2019-04-16 Time 11:38 Sent To  
Notes
2019-05-08 17:58:16TO MISC 2
  
2019-04-17 11:38:45ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-11-01 Cont ID  
Sent By rfalcone Date 2019-11-01 Time 09:52 Rev Time 0.00
Received By rfalcone Date 2019-11-01 Time 09:52 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-04-23 Cont ID  
Sent By mcruz Date 2019-04-23 Time 15:28 Rev Time 0.00
Received By mcruz Date 2019-04-23 Time 15:16 Sent To  
Notes
2019-04-23 15:28:54ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PURSUANT TO SEC. 94-220(D)(7) - MECHANICAL SYSTEMS,
 BACKFLOW PREVENTERS, TELEVISION ANTENNAS, SATELLITE
 DISHES AND SIMILAR DEVICES SHALL BE SCREENED FROM VIEW
 ON ALL SIDES TO THE FULL HEIGHT OF THE STRUCTURE BY
 LANDSCAPING OR BUILT ELEMENTS DESIGNED AS AN INTEGRAL
 PART OF THE BUILDING ARCHITECTURE.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER
 THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO
 SCHEDULE AN APPOINTMENT.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  