Plan Review Details - Permit 19040803
Plan Review Stops For Permit 19040803
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-05 Cont ID  
Sent By pvalenti Date 2019-08-05 Time 15:56 Rev Time 0.00
Received By pvalenti Date 2019-08-05 Time 13:09 Sent To  
Notes
2019-08-05 16:09:20PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING REVIEW APPROVED WITH PROVISO:
  
 1. AN APPROVED ROOFING SUB-PERMIT IS REQUIRED ON-SITE
 PRIOR TO ROOF WORK.
 2. APPROVED BALCONY AND HANDRAIL CONNECTION DETAILS ARE
 REQUIRED ON-SITE PRIOR TO INSPECTION.
 3. A BLOWER DOOR TEST FOR AIR LEAKAGE, HAS TO BE
 COMPLETED BY AN APPROVED THIRD PARTY COMPANY AND IS
 REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF C.O. AS
 PER FBC EC R 402.4.1.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-20 Cont ID  
Sent By pvalenti Date 2019-05-20 Time 14:17 Rev Time 0.00
Received By pvalenti Date 2019-05-17 Time 13:45 Sent To  
Notes
2019-05-20 14:52:30***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1ST BUILDING PLAN REVIEW DENIED:
  
 1. FBC B 107.2.1 THE DETAILS FOR LINTEL #21 ON SHEETS
 4/7 & 5/7 ARE NOT CLEAR AS TO MEETING THE REQUIRED LOAD
 CAPACITY. PLEASE ADJUST AND CLARIFY.
  
 2. FBC B 109.3 THE VALUATION OF THIS APPLICATION
 APPEARS TO BE VERY LOW. PLEASE ADJUST AND CLARIFY.
  
 3. FBC B 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, DOOR, AND
 OVERHEAD GARAGE DOOR SUBMITTALS.
  
 NOTES:
 A. PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE.
 CALL (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT
 ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF.
  
 B. A ROOFING SUB-PERMIT IS REQUIRED PRIOR TO ROOF WORK.
  
 C. BALCONY AND STAIR HANDRAIL SUBMITTALS ARE REQUIRED
 TO BE APPROVED BY THE DESIGNER OF RECORD.
  
 D. A BLOWER DOOR TEST, FOR AIR LEAKAGE, HAS TO BE
 COMPLETED BY THIRD PARTY AND IS REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF C.O. AS PER FBC EC
 R402.4.1.2.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2019-10-22 Cont ID  
Sent By ppetty Date 2019-10-22 Time 11:28 Rev Time 0.00
Received By ppetty Date 2019-10-22 Time 11:28 Sent To  
Notes
2019-10-22 11:28:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS:PASS WITH PROVISO, SEE
 COMMENTS BELOW.
  
 1.
 2.
 3.
 4.
 5. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. PROVIDE CORRECTION. NEC
 225.30,225.32
 6.
 7.
 8.
 9.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2019-09-25 Cont ID  
Sent By ppetty Date 2019-09-25 Time 08:55 Rev Time 0.00
Received By ppetty Date 2019-09-25 Time 08:55 Sent To  
Notes
2019-09-25 08:52:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3
 2.
 3.
 4.
 5. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. PROVIDE CORRECTION. NEC
 225.30,225.32
 6.
 7.
 8.
 9. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-08-27 Cont ID  
Sent By ppetty Date 2019-08-27 Time 11:37 Rev Time 0.00
Received By ppetty Date 2019-08-27 Time 12:48 Sent To  
Notes
2019-08-27 11:37:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3
 2. PLEASE SHOW LOCATION OF NEW PANEL.
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2
 4.PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 5. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. PROVIDE CORRECTION. NEC
 225.30
 6.
 7.
 8. PROVIDE SPEC SHEET FOR TANKLESS WATER HEATER IS THIS
 GAS OR ELECTRIC? WPB FBC 107.2.1
 9. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-26 Cont ID  
Sent By ppetty Date 2019-07-26 Time 10:34 Rev Time 0.00
Received By ppetty Date 2019-07-26 Time 10:34 Sent To  
Notes
2019-07-26 10:33:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2.
 3.
 4.
 5. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. PROVIDE CORRECTION. NEC
 225.30
 6.
 7.
 8. PROVIDE SPEC SHEET FOR TANKLESS WATER HEATER IS THIS
 GAS OR ELECTRIC? WPB FBC 107.2.1
 9. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-13 Cont ID  
Sent By jpearson Date 2019-05-13 Time 15:38 Rev Time 0.00
Received By jpearson Date 2019-05-13 Time 10:41 Sent To  
Notes
2019-05-13 15:38:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS
 PERMITTED. PROVIDE CORRECTION. WPB FBC 107.2.1; NEC
 230.2; FBC RE E3601.2
 3. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
 4. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 5. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. PROVIDE CORRECTION. NEC
 225.30
 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 7. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING THE GARAGE DOOR OPENERS.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 8. PROVIDE SPEC SHEET FOR TANKLESS WATER HEATER IS THIS
 GAS OR ELECTRIC? WPB FBC 107.2.1
 9. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-07-18 Cont ID  
Sent By fmittner Date 2019-07-18 Time 11:11 Rev Time 0.00
Received By fmittner Date 2019-07-18 Time 11:11 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-05-02 Cont ID  
Sent By fmittner Date 2019-05-02 Time 09:52 Rev Time 0.00
Received By fmittner Date 2019-05-02 Time 09:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2019-10-22 Cont ID  
Sent By ppetty Date 2019-10-22 Time 11:29 Rev Time 0.00
Received By ppetty Date 2019-10-11 Time 13:59 Sent To  
Notes
2019-10-22 08:27:39ROUTED TO PPETTY'S DESK
2019-10-15 14:00:07RESUB ROUTED TO JESMITH'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-09-25 Cont ID  
Sent By ppetty Date 2019-09-25 Time 08:55 Rev Time 0.00
Received By ppetty Date 2019-09-23 Time 14:50 Sent To  
Notes
2019-09-24 14:50:34RESUB ROUTED TO PPETTY

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-08-27 Cont ID  
Sent By ppetty Date 2019-08-27 Time 12:49 Rev Time 0.00
Received By ppetty Date 2019-08-14 Time 14:18 Sent To  
Notes
2019-08-15 14:18:45RESUB ROUTED TO PPETTY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-05 Cont ID  
Sent By pvalenti Date 2019-08-05 Time 16:38 Rev Time 0.00
Received By pvalenti Date 2019-07-11 Time 15:34 Sent To  
Notes
2019-07-12 15:35:05R25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-17 Cont ID  
Sent By lmarchan Date 2019-06-17 Time 13:28 Rev Time 0.00
Received By lmarchan Date 2019-06-06 Time 13:52 Sent To  
Notes
2019-06-07 13:52:20R21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-20 Cont ID  
Sent By pvalenti Date 2019-05-20 Time 14:57 Rev Time 0.00
Received By pvalenti Date 2019-04-16 Time 13:52 Sent To  
Notes
2019-04-17 13:52:27R25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-10-28 Cont ID  
Sent By pvalenti Date 2019-10-28 Time 10:08 Rev Time 0.00
Received By pvalenti Date 2019-10-28 Time 10:07 Sent To  
Notes
2019-10-28 10:21:42IMPACT FEE REVIEW:
  
 APPROVED, THE CONTRACTOR PROVIDED THE COUNTY STAMPED
 PLAN AND RECEIPT # MU-2019-033384-0000.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-08-05 Cont ID  
Sent By pvalenti Date 2019-08-05 Time 14:39 Rev Time 0.00
Received By pvalenti Date 2019-08-05 Time 14:39 Sent To  
Notes
2019-08-05 14:40:38***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 IMPACT FEE REVIEW DENIED:
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233?5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-05-20 Cont ID  
Sent By pvalenti Date 2019-05-20 Time 14:53 Rev Time 0.00
Received By pvalenti Date 2019-05-20 Time 14:53 Sent To  
Notes
2019-05-20 14:54:39***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-07-27 Cont ID  
Sent By cmontell Date 2019-07-27 Time 07:16 Rev Time 0.00
Received By cmontell Date 2019-07-27 Time 07:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-15 Cont ID  
Sent By cmontell Date 2019-05-15 Time 14:17 Rev Time 0.00
Received By cmontell Date 2019-05-15 Time 14:16 Sent To  
Notes
2019-05-15 14:16:32MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED MECHANICAL PLAN PER AMENDMENTS TO THE FLORIDA
 BUILDING CODE, 6TH EDITION (2017) SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 CHRIS MONTELLO
 561-805-6733

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-10-22 Cont ID  
Sent By jesmith Date 2019-10-22 Time 08:24 Rev Time 0.00
Received By jesmith Date 2019-10-22 Time 07:43 Sent To  
Notes
2019-10-22 08:24:24PLUMBING COMMEMTS: APPROVED WITH PROVISO
 1. PER WPB FBC 107.2.1 AND AS ALLOWED BY WPB FBC
 107.3.4.1 DEFERRED SUBMITTALS, PROVIDE THE COMPLETE
 MANUFACTURER'S INSTALLATION MANUAL AND SPECIFICATIONS
 FOR THE TANKLESS WATER HEATER. HEATER'S EFFICIENCY MUST
 SHOW AS MIN .92EF TO MATCH THE R405 ENERGY FORM. THE KW
 AND AMPERAGE SHALL MATCH THE ELECTRICAL LOAD TABLE ON
 PLAN PAGE 7 OF 7. THE HEATER MUST BE ABLE TO PRODUCE
 HOT WATER 110F TO MULTIPLE FIXTURES AT THE SAME TIME.
 THIS SUBMITTAL SHALL BE SUBMITTED, APPROVED AND IN
 PLACE PRIOR TO FINAL INSPECTION. CONTRACTOR PROCEEDS AT
 HIS OWN RISK.
 2. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL. IT IS NOTED THAT A CODE COMPLIANT SANITARY
 RISER DIAGRAM HAS BEEN SUBMITTED. STRUCTURAL DESIGN AND
 FIXTURE LOCATIONS MAY WELL REQUIRE ADDITIONAL VENTRS
 AND PIPING CONFIGURATIONS. IT IS THE CONTRACTOR'S
 RESPONSIBILITY TO PROVIDE A CODE COMPLIANT
 INSTALLATION.
 3. PROVIDE WATER HAMMER ARRESTORS AT WATER SUPPLIES TO
 WASHING MACHINE, ICE LINE AND DISHWASHER. FBC RES
 P2903.5
 4. THE COMBINED DISCHARGE FROM A DISHWASHER AND A ONE-
 OR TWO-COMPARTMENT SINK, WITH OR WITHOUT A FOOD-WASTE
 DISPOSER, SHALL BE SERVED BY A TRAP OF NOT LESS THAN
 11/2 INCHES (38 MM) IN OUTSIDE DIAMETER. THE DISHWASHER
 DISCHARGE PIPE OR TUBING SHALL RISE TO THE UNDERSIDE OF
 THE COUNTER AND BE FASTENED OR OTHERWISE HELD IN THAT
 POSITION BEFORE CONNECTING TO THE HEAD OF THE FOOD
 WASTE DISPOSAL OR TO A TEE-WYE FITTING IN THE SINK
 TAILPIECE. FBC RES P2717.2
 5. SHUT OFF VALVES FOR THE UNDER COUNTER WASHING
 MACHINE AND ICE MAKER SHALL BE ACCESSIBLE. FBC RES
 P2903.9.4

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-01 Cont ID  
Sent By jesmith Date 2019-08-01 Time 10:53 Rev Time 0.00
Received By jesmith Date 2019-08-01 Time 08:46 Sent To  
Notes
2019-08-01 10:53:44PLUMBING COMMEMTS: APPROVED WITH PROVISO
 1. PER WPB FBC 107.2.1 AND AS ALLOWED BY WPB FBC
 107.3.4.1 DEFERRED SUBMITTALS, PROVIDE THE COMPLETE
 MANUFACTURER?S INSTALLATION MANUAL AND SPECIFICATIONS
 FOR THE TANKLESS WATER HEATER. HEATER'S EFFICIENCY MUST
 SHOW AS MIN .92EF TO MATCH THE R405 ENERGY FORM. THE KW
 AND AMPERAGE SHALL MATCH THE ELECTRICAL LOAD TABLE ON
 PLAN PAGE 7 OF 7. THE HEATER MUST BE ABLE TO PRODUCE
 HOT WATER 110F TO MULTIPLE FIXTURES AT THE SAME TIME.
 THIS SUBMITTAL SHALL BE SUBMITTED, APPROVED AND IN
 PLACE PRIOR TO FINAL INSPECTION. CONTRACTOR PROCEEDS AT
 HIS OWN RISK.
 2. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL. IT IS NOTED THAT A CODE COMPLIANT SANITARY
 RISER DIAGRAM HAS BEEN SUBMITTED. STRUCTURAL DESIGN AND
 FIXTURE LOCATIONS MAY WELL REQUIRE ADDITIONAL VENTRS
 AND PIPING CONFIGURATIONS. IT IS THE CONTRACTOR'S
 RESPONSIBILITY TO PROVIDE A CODE COMPLIANT
 INSTALLATION.
 3. PROVIDE WATER HAMMER ARRESTORS AT WATER SUPPLIES TO
 WASHING MACHINE, ICE LINE AND DISHWASHER. FBC RES
 P2903.5
 4. THE COMBINED DISCHARGE FROM A DISHWASHER AND A ONE-
 OR TWO-COMPARTMENT SINK, WITH OR WITHOUT A FOOD-WASTE
 DISPOSER, SHALL BE SERVED BY A TRAP OF NOT LESS THAN
 11/2 INCHES (38 MM) IN OUTSIDE DIAMETER. THE DISHWASHER
 DISCHARGE PIPE OR TUBING SHALL RISE TO THE UNDERSIDE OF
 THE COUNTER AND BE FASTENED OR OTHERWISE HELD IN THAT
 POSITION BEFORE CONNECTING TO THE HEAD OF THE FOOD
 WASTE DISPOSAL OR TO A TEE-WYE FITTING IN THE SINK
 TAILPIECE. FBC RES P2717.2
 5. SHUT OFF VALVES FOR THE UNDER COUNTER WASHING
 MACHINE AND ICE MAKER SHALL BE ACCESSIBLE. FBC RES
 P2903.9.4

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-02 Cont ID  
Sent By thunt Date 2019-05-02 Time 15:49 Rev Time 0.00
Received By thunt Date 2019-05-02 Time 14:51 Sent To  
Notes
2019-05-02 15:49:53PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE THE COMPLETE INSTALLATION MANUAL FOR THE
 TANKLESS WATER HEATER. HEATER'S EFFICIENCY MUST SHOW AS
 MIN .92EF TO MATCH THE R405 ENERGY FORM. PROVIDE HEAT
 RISE CHART AS ON SHT #7 THE KW RATING IS LISTED AS
 4.5KW. THE HEATER MUST BE ABLE TO PRODUCE HOT WATER
 110F TO MUILT FIXTURES AT THE SAME TIME. FBC 107.2.1
  
 2) MIN TRAP SIZE FOR A WASHING MACHINE IS 2". PLAN ON
 SHT.#7 CALLS OUT 1 1/2". FBC P 709.1
  
 3) DISHWASHER SHALL DISCHARGE BY MEANS OF AIR GAP AND
 NOT DIRECTLY CONNECT INTO THE STACK. FBC-P 802.1.6
  
 4) TANKLESS SHALL HAVE CLEAR ACCES TO ALLOW FOR
 OBSERVATIONS, MAINTENANCE, SERVICING, AND REPLACING.
 FBC-R P 2801.5
  
 5) PROVIDE SHOWER PAN DETAIL. SHOW PRE-PITCH, FINISHED
 CURB HEIGHT AND SHOWER PAN MATERIAL BEING USED FBC
 107.2.1
  
 6) PROVIDE LOCATION ON PLAN WHERE THE SHUT OFF VALVES
 FOR THE UNDER COUNTER WASHING MACHINE AND ICE MAKER ARE
 LOCATED. VALVES SHALL HAVE READY ACCESSIBLE. FBC-R
 P2903.9.4
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-08-05 Cont ID  
Sent By pvalenti Date 2019-08-05 Time 14:31 Rev Time 0.00
Received By pvalenti Date 2019-08-05 Time 14:31 Sent To  
Notes
2019-08-05 14:35:53PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING REVIEW APPROVED WITH PROVISO:
  
 PLEASE PROVIDE ROOFING SUB-PERMIT PRIOR TO ROOF
 INSTALLATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-05-20 Cont ID  
Sent By pvalenti Date 2019-05-20 Time 14:55 Rev Time 0.00
Received By pvalenti Date 2019-05-20 Time 14:55 Sent To  
Notes
2019-05-20 14:57:11***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1ST REVIEW DENIED:
  
 A ROOFING SUB PERMIT IS REQUIRED.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-18 Cont ID  
Sent By fmittner Date 2019-07-18 Time 11:12 Rev Time 0.00
Received By fmittner Date 2019-07-18 Time 11:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-05-02 Cont ID  
Sent By fmittner Date 2019-05-02 Time 09:52 Rev Time 0.00
Received By fmittner Date 2019-05-02 Time 09:52 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved