| 2019-05-17 14:09:48 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH |
| | EDITION |
| | FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1. SEE PLAN PAGE A4.02. STAIR DETAIL REFERENCES DETAILS |
| | D,E&F 4.03. PLAN PAGE 4.03 IS MISSING. REVIEW OF STAIRS |
| | IS NOT COMPLETE. |
| | |
| | 2. SEE STAIR DETAIL ON PAGE A4.02, OPENING BETWEEN |
| | GUARD AND STAIR SHALL NOT EXCEED 4 INCHES PER R312.1.3. |
| | |
| | 3. STATE GOVERNING CODES ON COVER PAGE. |
| | |
| | 4. ROOFING PERMIT REQUIRED. |
| | |
| | 5. PROVIDE DESIGN PRESSURES OF ALL WINDOW AND EXTERIOR |
| | DOOR OPENINGS. PLACE ON WINDOW AND DOOR SCHEDULE OR |
| | PLACE ON PLAN NEXT TO EACH OPENING. |
| | FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN |
| | PRESSURES PURSUANT TO FBC-R301.2. |
| | |
| | 6. REF. PLAN PAGE A4.00. EXTERIOR WALL INSULATION IS |
| | SHOWN AS R-19 FOR 2ND FLOOR WOOD FRAMED WALLS. THE |
| | ENERGY SUBMITTAL DOES NOT HAVE ENERGY DATA FOR WOOD |
| | FRAMED WALLS. PLEASE CLARIFY |
| | |
| | 7. REF. PLAN PAGE A4.00. R VALUE MISSING FROM PLAN FOR |
| | CMU EXT. WALL INSULATION. ENERGY SUBMITTAL SHOWS R4.1. |
| | PLEASE CLARIFY. |
| | |
| | 8. THERE IS A CONFLICT BETWEEN PLAN PAGE D1.01 - |
| | PARTITIONS AND BEARING WALLS TO REMAIN AND PLAN PAGE |
| | A1.02 (B) NEW EXTERIOR WALLS. PLEASE CLARIFY. |
| | |
| | 9. THERE IS A CONFLICT BETWEEN PLAN PAGE D1.02 - |
| | PARTITIONS AND BEARING WALLS TO REMAIN AND PLAN PAGE |
| | A1.03 (A) NEW EXTERIOR WALLS. PLEASE CLARIFY. |
| | |
| | 10. PROVIDE PRODUCT APPROVALS FOR ALL WINDOWS AND |
| | EXTERIOR DOORS. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR |
| | SUBMITTALS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| 2019-04-25 15:04:11 | PLAN REVIEWER, PLEASE EVALUATE THE APPROPRIATENESS OF |
| | REVOKING 17061319. ALSO LOOK AT ALL RECORDS TO |
| | DETERMINE ESTABLISHED UNITS ON PROPERTY AND APPLICABLE |
| | CODES, EXISTING & FBC OR RESIDENTIAL?. SAK |