Plan Review Details - Permit 19040764
Plan Review Stops For Permit 19040764
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-06 Cont ID  
Sent By jwitmer Date 2019-05-06 Time 10:51 Rev Time 0.00
Received By jwitmer Date 2019-05-06 Time 10:06 Sent To  
Notes
2019-05-06 10:51:322017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19040764
 ADD: 2915 S DIXIE HWY.
 CONT: SUPERIOR CONCRETE
 TEL: 561-329-3575
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MAY 06/ 2019
 ACTION: DENIED
  
 1) THE SUBMITTED PLAN ARE MISSING INFORMATION TO BE
 ABLE TO DO A COMPLETE AND THOROUGH PLAN REVIEW:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS:
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
  
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE SECTION 503).
  
 4. THE BUILDING FIRE SPRINKLERED? AREA INCREASES TAKEN?
  
 2) WITHOUT THE LISTED ABOVE PLAN REVIEW CRITERIA A
 REVIEW FOR LIFE SAFETY CANNOT OCCUR. FROM SHEET LS1
 HERE ARE EXAMPLES OF UNKNOWNS?
 2A) THE PLAN LIST THE ICE CREAM SHOP PRODUCTION AREA AS
 HAVING 5951 SQ. FEET. WITH AN OCCUPANT LOAD OF 15.
 5951/15= 396.73 OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD
 FACTOR FOUND IN THE 2017 FBC-B TABLE 1004.1.2. SHOULD
 BE INDUSTRIAL 100 GROSS OR AN OCCUPANT LOAD OF 60
 OCCUPANTS.
  
 2B) IN THE BUSINESS OCCUPANCY 2089 SQ. FEET THE PLAN
 INDICATES 7 OCCUPANTS. 2089/100= 21 OCCUPANTS. BUSINESS
 USE 100 GROSS.
  
 2C) IN THE BLAST FREEZER THE FOOTAGE OF 2089 SQ. FEET
 INDICATES 2 PERSONS. AGAIN IN TABLE 1004.1.2. FOR A
 WAREHOUSE USE YOU SHOULD USE 500 SQ. FT. AS AN OCCUPANT
 LOAD FACTOR OR 2089/ 500= 5 OCCUPANTS.
  
 2D) THESE COMMENTS ARE COMMON FOR ALL OF THE LIFE
 SAFETY SHEETS. THE OCCUPANT LOADS ARE GOING TO
 INCREASE, WITHOUT THE KNOWLEDGE OF FIRE SPRINKLERS OR
 NOT THE MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE
 CANNOT BE DETERMINED. SEE 2017 FBC-B TABLE 1006.2.1.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-08 Cont ID  
Sent By jpearson Date 2019-05-08 Time 07:46 Rev Time 0.00
Received By jpearson Date 2019-05-07 Time 14:27 Sent To  
Notes
2019-05-08 07:46:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
 2. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE
 OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS IS
 FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-05-14 Cont ID  
Sent By pleduc Date 2019-05-14 Time   Rev Time 0.00
Received By pleduc Date 2019-05-14 Time 13:28 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-14 Cont ID  
Sent By cpuell Date 2019-05-14 Time 15:08 Rev Time 0.00
Received By cpuell Date 2019-04-15 Time 10:26 Sent To  
Notes
2019-04-17 10:26:47B04

Review Stop Z ZONING
Rev No 1 Status N Date 2019-05-01 Cont ID  
Sent By llouie Date 2019-05-01 Time   Rev Time 0.00
Received By llouie Date 2019-04-30 Time 15:15 Sent To  
Notes
2019-05-01 15:30:31REVIEW OF THE FIRE SAFETY PLAN DOES NOT REQUIRE ZONING
 REVIEW. NO STRUCTURAL EXPANSION OR EXTERIOR SITE
 IMPROVEMENTS PROPOSED UNDER THIS PERMIT.