| 2019-05-06 09:44:43 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19040725 |
| | ADD: 1771 PALM BEACH LAKES # W303 |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: |
| | E-MAIL: [email protected] / KARI NEVILLE |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. MAY 06/2019 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET 001-A000 UNDER THE HEADING (4) |
| | OCCUPANT LOAD & EGRESS |
| | TOTAL OCCUPANT LOAD: 42 PEOPLE |
| | 1A) LIST NUMBER OF EXITS REQUIRED AS (2), WRONG TABLE |
| | LIST TABLE 1021.2(2) SHOULD READ UNDER THE: |
| | 2017 FBC-B TABLE 1006.3.2(2). PLEASE UPDATE PLANS. |
| | |
| | 1B) THE SECOND ISSUE WITHIN THIS HEADING (4) OCCUPANT |
| | LOAD & EGRESS IS STATEMENT ( C ) NUMBER OF EXITS |
| | PROVIDED. THE 2017 FBC-B TABLE 1006.3.2(2) LIST THE |
| | NUMBER OF OCCUPANTS AS 49 OCCUPANTS AND THE MAXIMUM |
| | COMMON PATH OF TRAVEL IS 75 FEET EVEN IF SPRINKLERED. |
| | THIS TENANT SPACE IS OVER 100 FEET IN DEPTH REQUIRING 2 |
| | EXITS. |
| | |
| | 1C) PLEASE SHOW COMPLIANCE WITH SECTION 1016.2 EGRESS |
| | THROUGH INTERVENING SPACES OF THE 2017 FBC-B. |
| | 1016.2.5. EGRESS SHALL NOT PASS THROUGH KITCHENS, |
| | STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR |
| | PURPOSES. |
| | EXCEPTION: 2.MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| | STOCKROOMS IN GROUP M OCCUPANCIES WHERE ALL OF THE |
| | FOLLOWING ARE MET: |
| | 2.1.THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| | THAT FOUND IN THE MAIN RETAIL AREA. |
| | 2.2.NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| | THROUGH THE STOCKROOM. |
| | 2.3.THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| | EGRESS SIDE. |
| | 2.4.THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| | MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| | WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| | REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA |
| | TO THE EXIT WITHOUT OBSTRUCTIONS. |
| | |
| | 2) THE DEMOLITION PLAN 012_A100 SHOWS AN ELEMENT |
| | (CIRCLE) IN FRONT OF THE ACCESSIBLE RESTROOM BUT THERE |
| | IS NO NOTE IT HAS TO BE REMOVED. WHEN YOU LOOK AT THE |
| | SHEET 014_A101 NEW WORK PLAN, THIS SAME CIRCLE THAT IS |
| | JUST TO THE RIGHT OF THE RESTROOM DOOR (LABELED 6) |
| | THERE ARE 2 NOTES. (1) EXISTING WATER METER & (2) |
| | LANDLORD NOTE: ARCHITECT OF RECORD IS RESPONSIBLE FOR |
| | ALL CODE COMPLIANCE INCLUDING ACCESSIBILITY, VERIFY |
| | PROTRUDING OBJECT REQUIREMENT AND DOOR CLEARANCE TO THE |
| | RESTROOM MEETS CODE. |
| | PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY |
| | CODE SECTION 404.2.4 MANEUVERING CLEARANCES. |
| | MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL |
| | COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL |
| | EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED |
| | LATCH SIDE OR HINGE SIDE CLEARANCE. SEE TABLE |
| | 404.2.4.1, FIGURE 404.2.4.1(A). |
| | |
| | 3) SHEET 028_ A202 DETAIL (2) DOES NOT PROVIDE THE |
| | HEIGHT OF THE REAR TOILET GRAB BAR AND IN DETAIL (3) |
| | THE HEIGHT OF THE TOILET GRAB BAR FROM THE FLOOR TO THE |
| | CENTERLINE OF THE BAR IS DIMENSIONED AS 39 INCHES -41 |
| | INCHES. PLEASE SHOW COMPLIANCE WITH THE 2017 |
| | FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB |
| | BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE, NOT CENTERLINE. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |