Plan Review Details - Permit 19040705
Plan Review Stops For Permit 19040705
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-23 Cont ID  
Sent By dbattles Date 2019-04-23 Time 16:14 Rev Time 0.00
Received By dbattles Date 2019-04-23 Time 16:14 Sent To  
Notes
2019-04-23 16:15:39SEPARATE PERMIT NEEDED FOR DETACHED STORAGE AND
 DUMPSTER ENCLOSURE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-04-30 Cont ID  
Sent By jpearson Date 2019-04-30 Time 14:44 Rev Time 0.00
Received By jpearson Date 2019-04-30 Time 10:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-04-29 Cont ID  
Sent By pleduc Date 2019-04-29 Time   Rev Time 0.00
Received By pleduc Date 2019-04-29 Time 15:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-12 Cont ID  
Sent By cmontell Date 2019-08-12 Time 14:18 Rev Time 0.00
Received By cmontell Date 2019-08-12 Time 14:18 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-06-26 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-18 Time 09:52 Sent To  
Notes
2019-06-20 09:52:26RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-09 Cont ID  
Sent By cpuell Date 2019-05-09 Time 15:12 Rev Time 0.00
Received By cpuell Date 2019-04-15 Time 15:32 Sent To  
Notes
2019-04-16 15:32:57B31

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-08-12 Cont ID  
Sent By cmontell Date 2019-08-12 Time 14:17 Rev Time 0.00
Received By cmontell Date 2019-08-12 Time 14:17 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-26 Cont ID  
Sent By ccole Date 2019-06-26 Time 14:45 Rev Time 0.00
Received By ccole Date 2019-06-26 Time 13:08 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-22 Cont ID  
Sent By ccole Date 2019-04-22 Time 10:28 Rev Time 0.00
Received By ccole Date 2019-04-22 Time 10:01 Sent To  
Notes
2019-04-22 10:37:451ST REVIEW FBC-2017 MECHANICAL
 MASTER PERMIT #18100338
 REVISION #19040705
 4/22/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE EXHAUST OUTLET FOR VEF-1 MUST BE MINIMUM 3 FT.
 AWAY FROM THE PROPERTY LINE- SECTION 501.3.1 (3) FBC M.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SPLIT SYSTEMS- SECTION C403.2.1 FBC EC.
  
 3) POVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW AIR
 HANDLERS- SECTION 307.2.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-08-09 Cont ID  
Sent By cmontell Date 2019-08-12 Time 14:18 Rev Time 0.00
Received By tklarge Date 2019-08-08 Time 09:08 Sent To  
Notes
2019-08-08 11:58:341) PLEASE PROVIDE A RESPONSE NARRATIVE THAT CLEARLY
 DESCRIBES THE CHANGES BEING MADE TO THE PLUMBING SYSTEM
 AND THAT RESPONDS TO THE PREVIOUS PLAN REVIEW COMMENTS
 DATED 6/20/19 AND ALSO TO THESE COMMENTS.. WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) INSERT THE REVISED PLUMBING PLANS INTO THE MASTER
 SET OF PLANS.WPB AMEND. TO FBC SEC. 107.1.
 3) IT IS OBVIOUS THE DEVELOPED LENGTH DISTANCE FROM THE
 SOURCE OF HOT WATER TO THE FIXTURES THAT REQUIRES HOT
 WATER EXCEEDS 50 FEET. THEREFORE A HOT WATER
 RECIRCULATING SYSTEM WILL BE REQUIRED PER 2017
 FBC-PLUMBING SEC.607.2. 3RD REQUEST.
 4) THE HOT WATER SYSTEM SHALL BE INSULATED IN
 ACCORDANCE WITH 2017 FBC-PLUMBING SEC.607.5 AND THE
 2017 FBC-ENERGY SEC. C404.4 AND TABLE C403.2.10.
 5) A RECIRCULATING PUMP IS REQUIRED ON THE
 RECIRCULATION SYSTEM AND MUST BE INSTALLED IN
 ACCORDANCE WITH 2017 FBC-ENERGY SEC.C404.6.1.
 6) A MOP SINK IS REQUIRED FOR THIS OCCUPANCY PER 2017
 FBC-PLUMBING TABLE. 403.1. 3RD REQUEST.
 7) SUBMIT A COMPLETE KITCHEN EQUIPMENT SCHEDULE. THERE
 ARE SYMBOLS USED FOR KITCHEN EQUIPMET ON SHT. P1.1.
 THAT ARE NOT ON THE SCHEDULE ON SHT. P0.1. CLARIFY.
 8) SHT.P1.2 HAS A NOTE THAT STATES THE MOP SINK WILL BE
 INSTALLED UNDER A SEPARATE PERMIT. WHY IS THIS BEING
 DONE? THE MOP SINK SHALL BE INSTALLED UNDER THIS PERMIT
 NUMBER AND SHALL CONNECT TO THE GREASE INTERCEPTOR.
 2017 FBC-PLUMBING SEC.1003..3.1.
 9) THIS SUBMITTAL IS CONFUSING. THE REVISED PLUMBING
 PLANS HAVE AN ADDRESS ON THEM AS 518 S. DIXIE HWY.AND
 THE OTHER PLANS NOTE THE ADDRESS AS 327 HIBISCUS.
 CLARIFY. IN ADDITION, REVISED SHEET S-102R SHOWS
 INDIVIDUAL TENANT SPACES BUT THESE SPACES ARE NOT SHOWN
 ON ANY OTHER PLAN. CLARIFY.
 10) SHT.P1.2 - SHOWS TWO TANKLESS WAATER HEATERS BUT
 THE DETAIL ON SHT. P0.1 ONLY SHOWS ONE. IF THESE ARE
 PIPED IN SERIES, BOTH WATER HEATERS SHALL BE SHOWN ON
 THE DETAIL. WPB AMEND. TO FBC-SEC.107.2.1.
 11) 3RD REQUEST.HALLWAY FLOOR DRAINS ARE NOT INSTALLED
 AS THIS REVISION SHOWS AND ARE ALREADY INSTALLED.
 PLEASE CLARIFY. FBC 107.2.1
 12) SHT. P1.1 - THE HAND SINK (B7) AND FIXTURE B2
 DUMPING INTO FLOOR SINKS IN THE COFFEE BAR AREA SHALL
 DISCHARGE TO THE GREASE WASTE SYSTEM. FBC 1003.3.1.
 13) SHT.P1.1 - IDENTIFY EQUIPMENT # D1A, D4, D5, D6, D7
 D16A, #K32 THESE FIXTURES MAY HAVE TO DISCHARGE THROUGH
 THE GREASE WASTE SYSTEM.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-06-20 Cont ID  
Sent By thunt Date 2019-06-20 Time 13:56 Rev Time 0.00
Received By thunt Date 2019-06-20 Time 13:56 Sent To  
Notes
2019-06-20 14:01:52PLUMBING 2ND REVIEW**DENIED**
  
 1) ANSWERED**PROVIDE A NARRATIVE AS TO WHAT IS CHANGING
 ON THIS REVISION. FBC 107.2.1
  
 2) 2ND REQUEST RETURN LINE REQUIRED IF TOTAL PIPE
 LENGHT IS OVER 50' PLUMBING WATER ISOMETRIC IS MISSING
 THE HOT WATER RETURN PIPING CALL OUT IN SHT. P.01 WATER
 HEATER DETAIL AND REQUIRED WHEN THE OVERALL DEVELOPED
 LENGHT FROM THE WATER HEATER IS OVER 50'. TO ANY
 FIXTURE FBC 107.3.5, FBC-P 607.2
  
 3) 2ND REQUEST. THERE IS NO MOP SINK ON THE PERMIT
 NUMBERS YOUPROVIDED. YOU MUST INCLUDE THE MOP SINK ON
 THIS PLAN AND SHOW IT DISCHARGE INTO THE GREASE
 INTERCEPTOR. NOTE THIS WILL MAY CHAGE THE SIZING
 REQUIREMENTS OF THE GREASE INTERCEPTOR .YOU HAVE NOTES
 ON 2 DIFFERENT PAGES REGARDING THE MOP SINK. CURRENTLY
 NO MOP SINK EXIST AND NO OTHER SEPARATE PERMIT CAN BE
 LOCATED. THE MOP SINK IS A REQUIREMENT PER FBC-P 403.1.
 INCLUDE MOP SINK ON YOUR PLANS OR PROVIDE PERMIT NUMBER
 THAT MOP SINK IS LOCATED ON. FBC 107.3.5
  
 4) 2ND REQUEST.HALLWAY FLOOR DRAINS ARE NOT INSTALLED
 AS THIS REVISION SHOWS AND ARE ALREADY INSTALLED.
 PLEASE CLARIFY. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-24 Cont ID  
Sent By gjohnson Date 2019-04-24 Time 07:48 Rev Time 0.00
Received By thunt Date 2019-04-23 Time 16:47 Sent To  
Notes
2019-04-24 07:49:41PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE A NARRATIVE AS TO WHAT IS CHANGING ON THIS
 REVISION. FBC 107.2.1
  
 2) PLUMBING WATER ISOMETRIC IS MISSING THE HOT WATER
 RETURN PIPING CALL OUT IN SHT. P.01 WATER HEATER DETAIL
 AND REQUIRED WHEN THE OVERALL DEVELOPED LENGHT FROM THE
 WATER HEATER IS OVER 50'. TO ANY FIXTURE FBC 107.3.5,
 FBC-P 607.2
  
 3) YOU HAVE NOTES ON 2 DIFFERENT PAGES REGARDING THE
 MOP SINK. CURRENTLY NO MOP SINK EXIST AND NO OTHER
 SEPARATE PERMIT CAN BE LOCATED. THE MOP SINK IS A
 REQUIREMENT PER FBC-P 403.1. INCLUDE MOP SINK ON YOUR
 PLANS OR PROVIDE PERMIT NUMBER THAT MOP SINK IS LOCATED
 ON. FBC 107.3.5
  
 4) HALLWAY FLOOR DRAINS ARE NOT INSTALLED AS THIS
 REVISION SHOWS. PLEASE CLARIFY. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-05-09 Cont ID  
Sent By aaponte Date 2019-05-09 Time 11:56 Rev Time 0.00
Received By aaponte Date 2019-05-09 Time 11:56 Sent To  
Notes
2019-05-09 13:12:17MASTER PERMTI 16070183 SHALL BE REVISED TO INCLUDE THE
 ADDITIONAL SQUARE FOOTAGE ADDED WITH THE HALLWAY
 ENCLOSURE.
 RAMP FROM HALWAY TO STREET SHALL BE REMOVED.
 SPACE (FROM PREVIOUS CORRIDOR) UP TO THE STREET SHALL
 BE ENCLOSED WITH GATE.
 NO STORAGE ALLOWED FACING THE STREET.