Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-22 Cont ID  
Sent By shill Date 2019-05-22 Time 11:13 Rev Time 0.00
Received By shill Date 2019-05-22 Time 11:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-22 Cont ID  
Sent By jduprey Date 2019-04-22 Time 11:47 Rev Time 0.00
Received By jduprey Date 2019-04-22 Time 11:46 Sent To E
Notes
2019-04-22 11:52:55BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE PLANS AND STRUCTURAL ROOF CERTIFICATION WERE
 SUBMITTED WITH A COPY ENGINEER'S SIGNATURE. THE
 ENGINEER APPEARS TO HAVE A DIGITAL SIGNATURE, IF SO THE
 DOCUMENTS CAN BE SEND VIA EMAIL TO [email protected] WITH
 THE DIGITAL SIGNATURE OR YOU CAN RE-SUBMITT THE
 DOCUMENTS ON PAPER AND ORIGINAL ENGINEER SIGNATURE. FBC
 107
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE ORIGINAL
 SIGNATURE, DATE AND SEAL OF THE ENGINEER PER FL ADMIN.
 CODE RULE 61G15-23.001.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-20 Cont ID  
Sent By jleahy Date 2019-05-20 Time 15:44 Rev Time 0.00
Received By jleahy Date 2019-05-20 Time 15:44 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By fgiaquin Date 2019-04-30 Time 06:48 Rev Time 0.00
Received By fgiaquin Date 2019-04-30 Time 06:23 Sent To I
Notes
2019-04-30 06:26:06ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. MUST BE WET SIGNATURE ON ENGINEER'S SEAL. PLEASE SEE
 REQUIREMENTS FOR SIGNATURES AND SEALS BELOW:
  
  
 PRINTED COPIES OF DIGITALLY SIGNED PLANS ARE NOT
 CONSIDERED TO BE SIGNED AND SEALED PER FLORIDA
 STATUTES. PLEASE SEE REQUIREMENTS BELOW FOR SIGNATURE
 AND SEALS.
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-22 Cont ID  
Sent By shill Date 2019-05-22 Time 11:13 Rev Time 0.00
Received By shill Date 2019-05-15 Time 14:45 Sent To  
Notes
2019-05-16 14:46:03RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-30 Cont ID  
Sent By fgiaquin Date 2019-04-30 Time 06:49 Rev Time 0.00
Received By fgiaquin Date 2019-04-12 Time 13:16 Sent To  
Notes
2019-04-15 13:16:57ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-05-17 Cont ID  
Sent By hmtribou Date 2019-05-17 Time 14:18 Rev Time 0.00
Received By hmtribou Date 2019-05-17 Time 14:18 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-04-19 Cont ID  
Sent By hmtribou Date 2019-04-19 Time 12:59 Rev Time 0.00
Received By hmtribou Date 2019-04-19 Time 12:59 Sent To B
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved