Plan Review Details - Permit 19040645
Plan Review Stops For Permit 19040645
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-30 Cont ID  
Sent By dbattles Date 2019-04-29 Time 07:57 Rev Time 0.00
Received By dbattles Date 2019-04-26 Time 16:08 Sent To  
Notes
2019-04-30 08:31:08ALL COMMENTS ADDRESSED.
2019-04-29 07:57:30****CORRECTIONS****
 W.P.B. PERMIT: 19040645
 REVIEWED: APRIL 26, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 3103.2 FBC[B] CONSTRUCTION DOCUMENTS. A PERMIT
 APPLICATION AND CONSTRUCTION DOCUMENTS SHALL BE
 SUBMITTED FOR EACH INSTALLATION OF A TEMPORARY
 STRUCTURE. THE CONSTRUCTION DOCUMENTS SHALL INCLUDE A
 SITE PLAN INDICATING THE LOCATION OF THE TEMPORARY
 STRUCTURE AND INFORMATION DELINEATING THE MEANS OF
 EGRESS AND THE OCCUPANT LOAD.
 A) HOW LONG ARE THESE TO BE IN PLACE?
 B) PROVIDE MEANS OF EGRESS/LIFE SAFETY PLAN
 C) 61-41.009 DESIGN PLAN AND SYSTEMS APPROVAL. PROVIDE
 APPROVED PLAN FOR MANUFACTURED STRUCTURE FROM
 HTTPS://WWW.FLORIDABUILDING.ORG/MB/MB_PLAN_SRCH.ASPX
 D) WILL THERE BE PLUMBING HOOKED UP TO THE UNIT?
 61-41.016 DEPARTMENT INSIGNIA.
 (1) EACH MANUFACTURED BUILDING, RE-CERTIFIED BUILDING,
 AND COMPONENTS APPROVED BY THE AGENCY SHALL BE AFFIXED
 WITH THE APPROPRIATE INSIGNIA PRIOR TO LEAVING THE
 MANUFACTURING PLANT.
 NOTES:
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-03 Cont ID  
Sent By jpearson Date 2019-05-03 Time 12:54 Rev Time 0.00
Received By jpearson Date 2019-05-03 Time 12:02 Sent To  
Notes
2019-05-03 12:54:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE ELECTRICAL PLANS SUBMITTED FOR TEMPORARY SERVICE
 UNDER PERMIT 19031013 ONLY SHOW 277/480 VOLT
 DISTRIBUTION. THIS TRAILER CALLS FOR A 120/240 VOLT
 SINGLE PHASE SERVICE. WHERE IS THIS BEING FED FROM?
 WHAT IS THE LOAD REQUIRED FOR THE TRAILER? WHAT SIZE
 CONDUCTORS WILL FEED THE TRAILER? WHAT IS THE GROUNDING
 FOR THE TRAILER? PROVIDE RISER DIAGRAM AND LOAD
 CALCULATION WITH CORRECTIONS. NEC 215.5, 220, 250; WPB
 FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-04-16 Cont ID  
Sent By scaldero Date 2019-04-16 Time 10:15 Rev Time 0.00
Received By scaldero Date 2019-04-16 Time 10:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-09 Cont ID  
Sent By cpuell Date 2019-05-09 Time 15:12 Rev Time 0.00
Received By cpuell Date 2019-04-12 Time 13:18 Sent To  
Notes
2019-04-15 13:18:58B13

Review Stop Z ZONING
Rev No 1 Status P Date 2019-05-09 Cont ID  
Sent By aaponte Date 2019-05-09 Time 13:19 Rev Time 0.00
Received By aaponte Date 2019-05-09 Time 13:19 Sent To  
Notes
***NONE***