Plan Review Details - Permit 19040574
Plan Review Stops For Permit 19040574
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-05-06 Cont ID  
Sent By jwitmer Date 2019-05-06 Time 08:33 Rev Time 0.00
Received By jwitmer Date 2019-05-06 Time 07:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-05-07 Cont ID  
Sent By jpearson Date 2019-05-07 Time 10:53 Rev Time 0.00
Received By jpearson Date 2019-05-07 Time 10:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-04-19 Cont ID  
Sent By scaldero Date 2019-04-19 Time 14:15 Rev Time 0.00
Received By scaldero Date 2019-04-19 Time 14:05 Sent To  
Notes
2019-04-19 14:15:41PERMIT # 19040574
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 2) ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 3) EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE BARRIER-PROTECT
 ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 4) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 5) SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO
 THE FIRE ALARM AND SPRINKLER SYSTEM.
  
 6) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-05-07 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-11 Time 13:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-05-06 Cont ID  
Sent By jwitmer Date 2019-05-06 Time 08:33 Rev Time 0.00
Received By jwitmer Date 2019-05-06 Time 07:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-04-25 Cont ID  
Sent By ccole Date 2019-04-25 Time 16:02 Rev Time 0.00
Received By ccole Date 2019-04-25 Time 15:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-04-19 Cont ID  
Sent By gjohnson Date 2019-04-19 Time 15:10 Rev Time 0.00
Received By gjohnson Date 2019-04-19 Time 15:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-05-07 Cont ID  
Sent By jpearson Date 2019-05-07 Time 10:53 Rev Time 0.00
Received By jpearson Date 2019-05-07 Time 10:53 Sent To  
Notes
2019-05-06 08:35:20ARCHITECTURAL SHEETS SIGNATURE OK. J. W. 05/06/2019

Review Stop Z ZONING
Rev No 1 Status P Date 2019-05-02 Cont ID  
Sent By eschneid Date 2019-05-02 Time 14:46 Rev Time 0.50
Received By eschneid Date 2019-05-02 Time 14:46 Sent To  
Notes
***NONE***