| 2019-04-11 10:46:35 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | APPLICANTION CHECKLIST |
| | ALL STRUCTURES INSTALLED FOR LESS THAN 180 DAYS, |
| | GREATER THAN 120 SQ. FT. WITH 10 OR MORE OCCUPANTS |
| | * APPLICATION NEEDS TO BE SUBMITTED AT LEAST TWO WEEKS |
| | PRIOR TO EVENT |
| | 1. PERMIT APPLICATION |
| | A. PROVIDE EVENT FUNCTION |
| | B. ADDRESS OF EVENT |
| | C. WORK DESCRIPTION ? I.E. NUMBER AND SIZE OF TENTS |
| | D. OWNER AND CONTRACTOR INFO. |
| | E. VALUE ? ATTACH COPY OF CONTRACT WITH OWNER |
| | F. SPECIFY DATES OF INSTALLATION AND REMOVAL |
| | 2. SITE PLAN |
| | A. SHOW TO SCALE THE SIZE AND LOCATION OF NEW |
| | CONSTRUCTION AND EXISTING |
| | STRUCTURES ON THE SITE? |
| | B. SHOW DISTANCE TO LOT LINES AND OTHER STRUCTURES PER |
| | FBC CHPT. 6, SEC. 602 |
| | C. PROVIDE SQUARE FOOTAGE |
| | D. PROVIDE ESTIMATED OCCUPANCY CONTENT OF EACH TENT |
| | E. PROVIDE ACCESSIBLE ROUTE FROM PARKING TO TENT |
| | ENTRANCE |
| | F. IDENTIFY MEANS OF EGRESS PER CHPT. 10 |
| | G. PROVIDE ACCESSIBLE ROUTE FROM TENT TO ACCESSIBLE |
| | RESTROOMS |
| | H. ACCESSIBLE RESTROOMS SHALL BE LOCATED WITHIN 500 |
| | FEET OF TENT |
| | 2. FOUNDATION/TIE DOWN |
| | A. PROVIDE DETAIL OF TIE DOWN FOR UPLIFT |
| | B. PROVIDE DETAIL OF ANCHORS FOR TENT LEG LATERAL |
| | MOVEMENT |
| | 3. CONFORMANCE PER SECTION 3103.1.1 |
| | TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE |
| | STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, |
| | ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY |
| | REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC |
| | HEALTH, SAFETY AND GENERAL WELFARE. |
| | A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? FOR |
| | STRUCTURES WITH SPANS OF 30 FEET OR GREATER. |
| | B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER |
| | NFPA 701 FOR EACH TENT |
| | C. MEANS OF EGRESS 1) OPEN SIDES ? NO LIFE SAFETY PLAN |
| | REQUIRED. |
| | 2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN |
| | A) STATE OCCUPANT LOAD. |
| | B) IDENTIFY MEANS OF EGRESS. |
| | C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO |
| | EXIT. |
| | D) PROVIDE FLOOR LAYOUT OF EVENT. |
| | D. ACCESSIBILITY 1) IDENTIFY ACCESSIBLE ROUTE ON SITE |
| | PLAN |
| | E. LIGHT 1) OPEN SIDES ? N/A |
| | 2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE |
| | F. VENTILATION 1) OPEN SIDES ? N/A |
| | 2) CLOSED SIDES ? PER SEC. 1203 |
| | G. SANITARY 1) IDENTIFY EXISTING PERMANENT FACILITIES |
| | ON SITE PLAN |
| | 2) PROVIDE PORTABLE FACILITIES PER TABLE 2902. |
| | _______________________________________________________ |
| | _________________ |
| | |
| | |
| | *ADDITIONAL REQUIREMENTS |
| | FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN |
| | OF 30 FEET OR GREATER IN ANY DIRECTION: |
| | |
| | A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE |
| | BASEPLATE/TIEDOWN DETAILS. |
| | B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE. |
| | |
| | THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY |
| | A DESIGN PROFESSIONAL. |
| | |
| | OPTION TO ABOVE REQUIREMENT ? |
| | YOU MAY PLACE A STATEMENT ON YOUR PLAN THAT THE TENT |
| | WILL BE REMOVED IF WINDS ARE EXPECTED TO EXCEED 30 MPH |
| | |
| | _______________________________________________________ |
| | _________________ |
| | |
| | |