Plan Review Details - Permit 19040513
Plan Review Stops For Permit 19040513
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-07-19 Cont ID  
Sent By shill Date 2019-07-19 Time 06:39 Rev Time 0.00
Received By shill Date 2019-07-19 Time 06:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-06-26 Cont ID  
Sent By jgomez Date 2019-06-26 Time 17:03 Rev Time 0.00
Received By jgomez Date 2019-06-26 Time 13:39 Sent To  
Notes
2019-06-26 13:41:07TENANT BUILD-OUT, SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 1) OK
  
 2)OK
  
 3A) OK
  
 3B)OK
  
 3C)OK
  
 3D)OK
  
 4) OK
  
 5) OK
  
 6)OK
  
 ORIGINAL COMMENT.
 7) SHEET 015-A-501 SHOWS ELEVATIONS 3 & 5 RESTROOMS 107
 & 108 WITH THE BOTTOM OF THE CABINET FURN529 AT 4 FEET
 6 INCHES FROM THE FLOOR. THESE CABINETS ARE AMOUNTED
 ABOVE THE REACH RANGES.
 2017 FBC-ACCESSIBILITY CODE, 308 REACH RANGES
 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 RESPONSE:
 REACH RAGE WAS REVISED TO 4'-0". THIS REACH DIMENSION
 DOESN'T COMPLY. THERE IS AN OBSTRUCTION TO REACH THE
 CABINET. SEE SEC. 308.2.2 FBC-ACCESSIBILITY AND REVISE
 AS REQUIRED.
  
 8A) OK.
  
 8B)OK.
  
 8C) OK.
  
 8D) OK.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-07 Cont ID  
Sent By jwitmer Date 2019-05-07 Time 13:11 Rev Time 0.00
Received By jwitmer Date 2019-05-06 Time 14:40 Sent To  
Notes
2019-05-07 13:11:422017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19040513
 ADD: 1831 PALM BEACH LAKES BLVD. SUITE:
 CONT: CLARO DEVELOPMENT
 TEL: 305-890-6192
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 07/ 2019
 ACTION: DENIED
  
 1) ALL OF THE ARCHITECTURAL SHEETS BY SCOTT P. WRASMAN
 ARE NOT SIGNED AND SEALED ELECTRONICALLY. ARCHITECTS:
 FLORIDA ADMINISTRATIVE CODE 61G1-16.005. PROCEDURES FOR
 DIGITALLY SIGNING AND SEALING AND FOR ELECTRONICALLY
 TRANSMITTING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 2) THE STRUCTURAL SHEET BY NICHOLAS ANTHONY CAPOZZI P E
 ARE NOT SIGNED AND SEALED ELECTRONICALLY.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 3A) SHEET 001-T-001 THE COVER SHEET UNDER THE CODE
 SUMMARY LIST THE CONSTRUCTION TYPE AS TYPE VB. PLEASE
 NOTE THE SHELL BUILDING PERMIT FOR THIS BUILDING IS A
 CONSTRUCTION TYPE II-B (PERMIT 18101337). PLEASE UPDATE
 THE PLANS.
  
 3B) SHEET 001-T-001 THE COVER SHEET UNDER THE CODE
 SUMMARY FIRE RESISTANCE/ BUILDING STRUCTURE LIST THE
 CONSTRUCTION TYPE AS TYPE VB. PLEASE NOTE THE SHELL
 BUILDING PERMIT FOR THIS BUILDING IS A CONSTRUCTION
 TYPE II-B (PERMIT 18101337). PLEASE UPDATE THE PLANS.
  
 3C) SHEET 001-T-001 THE COVER SHEET UNDER THE CODE
 SUMMARY THE PLANS INDICATE SPRINKLERED N/A. PLEASE
 UPDATE PLANS, THE SHELL PERMIT (18101337) LIST FIRE
 SPRINKLERS AS PART OF THE PROJECT. TO DATE THERE IS AN
 ISSUED UNDERGROUND 6 INCH FIRE LINE (19030580) BEING
 INTRODUCED INTO THE PROJECT. UPDATE PLANS.
  
 3D) SHEET 001-T-001 THE COVER SHEET UNDER THE HEADING
 PROJECT SUMMARY LIST THIS STRUCTURE AS VB CONSTRUCTION
 TYPE WITH THE STRUCTURE CONSISTING OF A FRAMED ROOF
 WITH PLYWOOD DECK, TJI WOOD JOIST AND PARALAM BEAMS.
 THE PERIMETER WALLS ARE LOAD BEARING STRUCTURAL GAUGE
 STEEL STUDS.
 PLEASE UPDATE PLANS, UNDER THE SHELL PERMIT THE ROOF
 FRAMING SYSTEM, IS BAR JOIST WITH METAL B DECK. THE
 EXTERIOR BEARING WALLS ARE STRUCTURAL STEEL POST AND
 STEEL BEAM CONSTRUCTION WITH STRUCTURAL GAUGE STEEL
 INFILL WALLS, SEE SHELL PERMIT 18101337.
  
 4) THE SHEET 004-G-003 LIFE SAFETY AND ACCESSIBILITY
 SHEET INDICATE THAT THIS BUILDING IS TO CONFORM TO THE
 ANSI 1117.1 2009. PLEASE NOTE THE SUBMITTED PLANS WILL
 NEED TO CONFORM TO THE REQUIREMENTS OF THE 2017
 FBC-ACCESSIBILITY CODE. THIS CODE IS ADOPTED AS PART OF
 THE FLORIDA BUILDING CODE BY LAW, S.553.73(1)(A),
 FLORIDA STATUTES. THE ADMINISTRATIVE REQUIREMENTS OF
 THE FLORIDA BUILDING CODE, BUILDING, CHAPTER 1.
  
 5) SHEET 015-A-501 SHOWS ELEVATIONS 3, 4 & 5 WITH NO
 DIMENSIONS (ELEVATION) TO THE GRAB BARS FOR THE WATER
 CLOSET. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4
 POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
  
 6) SHEET 015-A-501 SHOWS ELEVATIONS 3 & 5 RESTROOMS 107
 & 108 WITH THE BOTTOM OF THE MIRROR BOTTOM OF MIRROR AT
 3 FEET 4 INCHES. PLEASE REVIEW 603.3 MIRRORS. 2017
 FBC-ACCESSIBILITY CODE. MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 7) SHEET 015-A-501 SHOWS ELEVATIONS 3 & 5 RESTROOMS 107
 & 108 WITH THE BOTTOM OF THE CABINET FURN529 AT 4 FEET
 6 INCHES FROM THE FLOOR. THESE CABINETS ARE AMOUNTED
 ABOVE THE REACH RANGES.
 2017 FBC-ACCESSIBILITY CODE, 308 REACH RANGES
 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 8A) SHEET M-100 ROOF TOP EQUIPMENT SHOWS WITH NOTE 3 A
 NEW ROOFTOP CONDENSER HP-1 TO BE MOUNTED ON ROOF RACKS
 SEE M-200. M-200 THE CONDENSING UNIT STAND. THE DETAIL
 INDICATES THE USE OF A FLORIDA APPROVAL FL # 24546.1
 SUBMIT THE APPROVAL PLEASE.
 PLEASE SHOW COMPLIANCE WITH 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (G) PRE-ENGINEERED A/C STANDS.
  
 8B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8C) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 8D) WITHIN THE ROOF TOP CONDENSING STAND DETAIL THERE
 IS A STATEMENT THE CONTRACTOR TO VERIFY THE THICKNESS
 OF THE ROOF ASSEMBLY 18 INCHES CLEARANCE REQUIRED FROM
 THE BOTTOM OF THE SUPPORT RACK HORIZONTAL STRUCTURAL
 MEMBER TO THE TOP OF THE ROOF ASSEMBLY. PLEASE NOTE THE
 VERTICAL CLEAR MEASUREMENT DEPENDS ON THE WIDTH OF THE
 MECHANICAL UNIT (IN INCHES) PLEASE REVIEW THE 2017
 FBC-B TABLE 1510.10, CLEARANCE BELOW RAISED ROOF
 MOUNTED MECHANICAL UNITS.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-07 Cont ID  
Sent By jleahy Date 2019-06-07 Time 14:01 Rev Time 0.00
Received By jleahy Date 2019-06-07 Time 14:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-05-23 Cont ID  
Sent By jleahy Date 2019-05-23 Time 08:46 Rev Time 0.00
Received By jleahy Date 2019-05-23 Time 08:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-07-15 Cont ID  
Sent By bwoods Date 2019-07-15 Time   Rev Time 0.00
Received By bwoods Date 2019-07-15 Time   Sent To  
Notes
2019-07-15 09:38:00PERMIT #19040513
 REVIEW COMMENTS - FIRE DEPARTMENT
 PASSED 7/15/19
  
  
 BRITTANY R WOODS
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4754
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-17 Cont ID  
Sent By pleduc Date 2019-06-10 Time 10:43 Rev Time 0.00
Received By pleduc Date 2019-06-10 Time 10:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-05-22 Cont ID  
Sent By pleduc Date 2019-05-22 Time   Rev Time 0.00
Received By pleduc Date 2019-05-22 Time 13:35 Sent To  
Notes
2019-05-22 14:15:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET T 001 - UNDER CODE SUMMARY THE IS AN
 INDICATION OF N/A NEXT TO THE SPRINKLERED.
  
 THERE IS A FIRE SPRINKLER PLAN SHEET ATTACHED.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET T 001 - UNDER CODE SUMMARY THERE IS AN
 INDICATION OF NFPA 72, 2010.
  
 THE CURRENT EDITION YEAR IS 2013.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND CORRECT.
  
  
  
 3) SHEET T 001 - UNDER PROJECT SUMMARY THERE IS
 INDICATION STATING LIFE SAFETY SYTEMS OF FIRE
 EXTINGUISHER AND SMOKE DETECTORS.
  
 THERE ARE NO INDICATIONS OF A FIRE SPRINKLER SYSTEM NOR
 FIRE SPRINKLER ALARM.
  
 PLEASE REVIEW AND CORRECT
  
  
  
 4) ELECTRICAL SHEETS - THERE ARE INDICATIONS OF FIRE
 ALARM DEVICES/EQUIPMENT BY NO INDICATION THAT ALL FIRE
 ALARM DEVICES/EQUIPMENT SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS BY CERTIFIED FIRE
 ALARM CONTRACTOR.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-19 Cont ID  
Sent By shill Date 2019-07-19 Time 06:40 Rev Time 0.00
Received By shill Date 2019-07-10 Time 08:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-26 Cont ID  
Sent By jgomez Date 2019-06-26 Time 17:05 Rev Time 0.00
Received By jgomez Date 2019-06-03 Time 09:23 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-25 Cont ID  
Sent By cmontell Date 2019-05-25 Time 08:42 Rev Time 0.00
Received By cmontell Date 2019-05-25 Time 08:42 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-05-07 Cont ID  
Sent By jwitmer Date 2019-05-07 Time 13:12 Rev Time 0.00
Received By jwitmer Date 2019-05-06 Time 14:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-17 Cont ID  
Sent By cmontell Date 2019-06-17 Time 14:38 Rev Time 0.00
Received By cmontell Date 2019-06-17 Time 14:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-05-25 Cont ID  
Sent By cmontell Date 2019-05-25 Time 08:42 Rev Time 0.00
Received By cmontell Date 2019-05-25 Time 08:42 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-18 Cont ID  
Sent By gjohnson Date 2019-06-18 Time 09:44 Rev Time 0.00
Received By gjohnson Date 2019-06-17 Time 10:47 Sent To  
Notes
2019-06-17 10:48:14LOGGED IN FOR GEORGE JOHNSON.

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By tklarge Date 2019-05-16 Time 10:33 Rev Time 0.00
Received By tklarge Date 2019-05-15 Time 10:36 Sent To  
Notes
2019-05-16 08:36:571) THE CLEAR FLOOR SPACE FOR THE HANDICAP ACCESSIBLE
 FIXTURES IN THE TOILET ROOMS IS CONFUSING. CLEARLY SHOW
 THE CLEAR FLOOR SPACES FOR THE WATER CLOSET AND THE
 LAVATORY ON THE PLANS. SHOW THE LENGTH AND WIDTH
 DIMENSIONS OF EACH CLEAR FLOOR SPACE ON THE PLANS.
 COMPLY WITH 2017 FBC-ACCESS. SECS.305, 306, 604.3.1 &
 606.2.
 2) A CLEAR FLOOR SPACE SHALL BE PROVIDED AT THE BREAK
 ROOM SINK.SHOW THIS ON THE PLAN ALONG WITH THE
 DIMENSIONS. 2017 FBC-ACCESS. SEC.606.2.
 3) THE DOORS IN TOILET ROOMS # 107 & # 108 APPEAR TO
 SWING INTO THE CLEAR FLOOR SPACE FOR THE LAVATORIES.
 COMPLY WITH 2017 FBC-ACCESS. SEC. 603.2.3. (SEE
 EXCEPTIONS).
 4) SHT. A-501 - ELEVATION #9 - SHOW THE LEADING EDGES
 OF THE DRINKING FOUNTAINS FROM THE FINISH FLOOR ON THE
 PLAN. PROTRUSION LIMITS SHALL COMPLY WITH 2017
 FBC-ACCESS. SEC.307.
 5) SHT. A-501 - ELEV. #9 - THE DRINKING FOUNTAINS SHALL
 BE PROVIDED WITH KNEE AND TOE CLEARANCES IN ACCCORDANCE
 WITH 2017 FBC- ACCESS. SEC. 306.
 6) SHT. A-501 - ELEVS. #4 & #5 - SHOW THE HEIGHT OF THE
 WATER CLOSET FROM THE FINISH FLOOR TO THE TOP OF THE
 SEAT ON THE PLAN. COMPLY WITH 2017 FBC-ACCESS.
 SEC.604.4.
 7) SHT. A-501 - ELEVS. #4 & #5 - SHOW THE HEIGHT OF THE
 GRAB BARS FROM THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE. 2017 FBC- SEC. 609.4.
 8) SHT. A-501 - ELEVS. #4 & #5 - THE LOCATION OF THE
 REAR AND SIDE GRAB BARS FOR THE WATER CLOSET SHALL
 COMPLY WITH 2017 FBC-ACCESS. SEC.604.5.1 & 604.5.2.
 SHOW THESE DIMENSIONS ON THE PLANS.
 9) SHT. A-501 - ELEVS. #4 & #5 - SHOW THE HEIGHT OF THE
 LAVATORY FROM THE FINISH FLOOR TO THE TOP OF THE
 LAVATORY RIM. COMPLY WITH 2017 FBC-ACCESS. SEC.606.3.
 10) SHT. A-501 - ELEVS.#4 & #5 - SHOW THE KNEE AND TOE
 CLEARANCES FOR THE LAVATORIES ON THE PLANS. COMPLY WITH
 2017 FBC-ACCESS. SEC.606.2.
 11) SHT. A-501 - ELEVS. #4 & #5 - SHOW THE HEIGHT OF
 THE TOILET PAPER DISPENSERS ABOVE THE FINISH FLOOR.
 COMPLY WITH 2017 FBC-ACCESS. SEC.604.7.
 12) SHT. A-501 - ELEVS. #3 & #5 - THE MAXIMUM HEIGHT OF
 THE CABINET IN THE TOILET ROOMS SHALL COMPLY WITH 2017
 FBC- ACCESS. SEC.308.2, 308.3.
 13) TEMPERD WATER IS REQUIRED AT THE LAVATORIES IN THE
 TOILET ROOMS PER 2017 FBC-PLUMBING SEC. 416.5.
 14) AN INLINE BACKFLOW PREVENTION DEVICE IS REQUIRED ON
 THE WATER SUPPLY TO THE COFFEEMAKER AND ALSO TO THE
 REFRIGERATOR. 2017 FBC-PLUMBING SEC. 608.3, 608.16.10.
 15) SHT. P-100 - THE FLOOR DRAINS ON THE SANITARY RISER
 ARE NOT PROPERLY VENTED. 2017 FBC-PLUMBING SEV.901.2.
 16) SHT. P-100 - THE INSTALLATION OF BACK TO BACK WATER
 CLOSETS SHALL COMPLY WITH 2017 FBC-PLUMBING SEC.706.3
 (EXCEPTION).
 17) THE HOT WATER PIPING AND RECIRCULATION WATER LINE
 SHALL BE INSULATED IN ITS ENTIRETY PER 2017 FBC-ENERGY
 SEC. C404.4. THE INSULATION THICKNESS SHALL BE IN
 ACCORDANCE WITH THE 2017 FBC-ENERGY TABLE C403.2.10.
 18) SUBMIT DETAILS AS TO THE DRAINAGE AND DISCHARGE OF
 RAINWATER FROM THE RROOF OF THIS STRUCTURE. WPB AMEND.
 TO FBC SEC. 1107.2.1, 2017 FBC-PLUMBING SEC.1101.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-07-19 Cont ID  
Sent By shill Date 2019-07-19 Time 06:39 Rev Time 0.00
Received By shill Date 2019-07-19 Time 06:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-06-17 Cont ID  
Sent By shill Date 2019-06-17 Time 16:05 Rev Time 0.00
Received By shill Date 2019-06-17 Time 16:05 Sent To  
Notes
2019-06-17 16:06:42DIGITAL SIGNATURES OK
 PLEASE NOTIFY IF ALL TRADES PASS THIS REVIEW CYCLE.
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-05-24 Cont ID  
Sent By shill Date 2019-05-24 Time 11:51 Rev Time 0.00
Received By shill Date 2019-05-24 Time 11:51 Sent To  
Notes
2019-05-24 11:52:26A, MEP SIGNATURES & TITLE BLOCK OK ON ENERGY CALCS &
 PLANS
 NEW PAGES SUBMITTED NEXT REVIEW CYCLE REQUIRE
 VERIFICATION
  
  
  
2019-05-16 10:35:15SIGNATURE ON PLUMBING DRAWINGS OK.TKL.
2019-04-19 07:54:314/19/19 HARD COPIES LOCATED IN LIBRARY.

Review Stop Z ZONING
Rev No 3 Status P Date 2019-07-16 Cont ID  
Sent By eschneid Date 2019-07-16 Time 14:14 Rev Time 0.25
Received By eschneid Date 2019-07-16 Time 14:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-06-25 Cont ID  
Sent By eschneid Date 2019-06-25 Time 15:06 Rev Time 0.50
Received By eschneid Date 2019-06-25 Time 11:40 Sent To  
Notes
2019-06-25 15:07:27FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) REPEAT COMMENT: PROVIDE STAMPED PLANS OR A LETTER
 FROM THE PALM BEACH OUTLETS MANAGEMENT APPROVING YOUR
 PLANS. --- THE RESPONSE STATES THAT THE COVER SHEET IS
 STAMPED AND THAT THERE IS AN E-MAIL PROVIDED. NEITHER
 ONE OF THESE OCCURRED. PLEASE UPLOAD THE CITED
 DOCUMENTS.
  
 2) PLEASE NOTE THAT THE PALM BEACH OUTLETS DESIGN
 GUIDELINES LIMIT PERMANENT WINDOW SIGNAGE TO NO MORE
 THAN 10% OF THE WINDOW AREA. THE CODE SECTION CITED IN
 THE PERMIT RESPONSE IS FOR A DIFFERENT DISTRICT WITHIN
 THE CITY. STAFF ACKNOWLEDGES THE NOTE THAT SIGNAGE WILL
 REQUIRE A SEPARATE PERMIT AND THE FINAL CALCULATIONS
 WILL OCCUR AT THAT TIME.
  
 3) THE NORTHERN FACADE DIFFERS FROM THE ORIGINAL
 APPROVED SITE PLAN SO A MINOR PLANNED DEVELOPMENT
 AMENDMENT SHOWING AS BUILT CONDITIONS NEEDS TO BE
 SUBMITTED TO THE PLANNING DIVISION PRIOR TO THE FINAL
 INSPECTION.
  
 4) SUBJECT TO THE PROVISOS IN 2 AND 3, THE PLANS MEET
 ZONING REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-05-07 Cont ID  
Sent By eschneid Date 2019-05-07 Time 10:27 Rev Time 0.75
Received By eschneid Date 2019-05-07 Time 09:14 Sent To  
Notes
2019-05-07 10:27:42FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) PROVIDE STAMPED PLANS OR A LETTER FROM THE PALM
 BEACH OUTLETS MANAGEMENT APPROVING YOUR PLANS.
  
 2) PLEASE DESCRIBE WHAT THE WINDOW FILM SHOWN ON THE
 BUILDING ELEVATIONS IS, TO INCLUDE OPACITY. VERIFY THAT
 THE LOWER PORTIONS OF THE NORTH FACADE PROVIDE
 UNOBSTRUCTED VIEW INTO THE BUILDING.
  
 3) THE SIGNAGE VISIBLE FROM THE EXTERIOR OF THE
 BUILDING REQUIRES SEPARATE PERMITS WITH PLANS. THIS
 INCLUDES THE WINDOW SIGNAGE AT THE WESTERN WINDOW/DOORS
 (TDB-V.0044, TDB-V-0038, TDB-C.0008, TDB-V.0045 AND
 POSTER SIGN BEHIND GLASS). PLEASE NOTE THAT THIS
 SIGNAGE MAY NOT TAKE UP MORE THEN 10% OF THE WINDOW
 AREA. WHILE NO DIMENSIONS WERE PROVIDED, IT APPEARS
 THAT MORE THAN 10% OF THE GLAZED AREA IS SIGNAGE.
  
 4) PROVIDE A SIGHT LINE DRAWING TO VERIFY THAT THE EF-1
 AND HP-1 ARE SCREENED FROM VIEW IN ACCORDANCE WITH THE
 PALM BEACH OUTLETS DESIGN GUIDELINES.
  
 5) THE NORTHERN FACADE DIFFERS FROM THE ORIGINAL
 APPROVED SITE PLAN SO A MINOR PLANNED DEVELOPMENT
 AMENDMENT SHOWING AS BUILT CONDITIONS NEEDS TO BE
 SUBMITTED TO THE PLANNING DIVISION PRIOR TO THE FINAL
 INSPECTION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  