Plan Review Details - Permit 19040488
Plan Review Stops For Permit 19040488
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-05-07 Cont ID  
Sent By pvalenti Date 2020-05-07 Time 14:44 Rev Time 0.00
Received By pvalenti Date 2020-05-07 Time 14:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-10-20 Cont ID  
Sent By pvalenti Date 2019-10-20 Time 13:14 Rev Time 0.00
Received By pvalenti Date 2019-10-20 Time 13:14 Sent To  
Notes
2019-10-20 13:43:35***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 1. OK
 2. OK
 3. OK
 4. FAIL: THE 60" WINDOW SIZES SHOWN ON THE SCHEDULE
 PAGE A-1 FOR THE KITCHEN (TYPE "A" SINGLE HUNG) WINDOW
 AND ALSO PAGE A-2 FRONT ENTRY AREA (TYPE "A" SINGLE
 HUNG IN CONFLICT WITH TYPE "E" FIXED WINDOW SHOWN ON
 THE SCHEDULE) ARE TOO LARGE PER PRODUCT APPROVAL.
 ALSO, WHICH SINGLE HUNG WINDOWS ARE TO BE INSTALLED ON
 THIS PROJECT (SH 800 OR SH 7700A)?
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. A. FAILED: MISSING A CONNECTION DETAIL FOR ROOF
 TRUSS TO STEEL BEAM CONNECTIONS.
 13. B. OK
 13. C. OK
 13. D. ON PAGE A-5 THERE ARE (2) TRUSS ANCHORING
 SCHEDULES THAT HAVE CONFLICTING CONNECTION DETAILS.
 PLEASE HAVE ONLY (1) SCHEDULE WIYH ALL NECCESSARY
 INFORMATION.
 13. E. OK
 14. OK
 15. OK
 16. OK
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-17 Cont ID  
Sent By jgomez Date 2019-05-17 Time 14:32 Rev Time 0.00
Received By jgomez Date 2019-05-17 Time 08:04 Sent To  
Notes
2019-05-17 14:32:56NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 SEC. R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 2-PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED BY
 SEC. 1106 FBC-EXISTING BUILDING. AND SEC. R101.4.2 AND
 R101.5 FBC-ENERGY CONSERVATION.
  
 3- PROVIDE SURVEY (2 COPIES) SHOWING ALL THE
 INFORMATION REQUIRED BY SEC. 107.2.5 CITY AMENDMENTS.
  
 4- WINDOWS ON BEDROOMS #1 AND #2 DON'T COMPLY WITH THE
 EGRESS REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL.
 REVISE AS REQUIRED.
 NOTE: ARCHITECT TO SPECIFY TYPE OF WINDOW ON THE WINDOW
 SCHEDULE. . COORDINATE WITH PRODUCT APPROVAL. BASED ON
 SINGLE HUNG WINDOW PRODUCT APPROVAL SUBMITTED, WINDOW
 TYPE "A" DOESN'T COMPLY WITH EGRESS. REVISE AS
 REQUIRED.
 ALSO, SIZE OF WINDOWS SHOWN ON THE WINDOW SCHEDULE ARE
 INCORRECT. FOR EXAMPLE, ACCORDING TO EXTERIOR
 ELEVATIONS, WINDOW "F" ARE TWO WINDOWS MULLED TOGETHER
 NOT JUST ONE WINDOW SIZE 72"X60". REVISE AS REQUIRED.
 PLEASE COORDINATE WINDOW SCHEDULE WITH ALL WINDOWS
 SHOWN ON PLANS AND ELEVATIONS TO AVOID
 CONFLICTS/DELAYS.
  
 5- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR NEW ENTRY DOOR AND SIDE WINDOW AS SHOWN ON PLANS.
 SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC.
 R101301.1 FBC-RESIDENTIAL.
  
 6- THERE IS A NEW ROOF FOR THE ENTIRE HOUSE:
 A)ARCHITECT TO SPECIFY ALL THE DEAD AND LIVE LOADS,
 INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 FBC-RESIDENTIAL (NOTE: TAKE INTO CONSIDERATION
 FOOTNOTES "B" AND "G" OF TABLE R301.5 TO AVOID
 CONFLICTS/DELAYS).
  
 B) ARCHITECT TO SPECIFY ATTIC ACCESS SIZE AND LOCATION.
 SEC. R307.1 FBC-RESIDENTIAL.
  
 7- REVISE THE ROOF EDGE ZONE DISTANCE SPECIFIED ON THE
 DESIGN WIND PRESSURES ON SHEET CVR.
 THE MINIMUM DISTANCE FOR EDGE AND CORNER AREAS IS 4
 FEET NOT 3 FEET AS REQUIRED BY NOTE "A" ON FIGURE
 R301.2(7) FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 8- CLARIFY/REVISE FLOOD ZONE INFORMATION SHOWN ON SHEET
 SP-1.
 PER SEC. 18-284 CITY ORDINANCE NO. 4729-17 NEW FLOOD
 INSURANCE RATE MAPS WERE ADOPTED ON OCTOBER 5, 2017.
 THERE ARE NO MORE FLOOD ZONES "B". ALSO, NOTES SHOWN
 UNDER THE FLOOD ZONE INFORMATION DON'T CORRESPOND TO
 THE CITY OF WEST PALM BEACH. REVISE AS REQUIRED.
 NOTE: THIS PROPERTY IS NOT LOCATED IN A FLOOD HAZARD
 AREA.
  
 9- SHEET SP-2: AREAS SHOWN ON THE AREA CALCULATIONS AND
 PROPOSED SITE PLAN DON'T MATCH. REVISE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 10- REVISE THE FOOTING MINIMUM DEPTH SHOWN ON THE WALL
 SECTION ON SHEET A-1. NEED 12" MIN. DEPTH. SEC.
 R403.1.4 FBC-RESIDENTIAL. ALSO, VERTICAL REINFORCEMENT
 NOTE ON SAME WALL IS REFERENCING THE SFBC. THIS CODE NO
 LONGER EXISTS. REVISE AS REQUIRED.
  
 11- WOOD INFILL DETAIL 4/A-3: CLARIFY CONNECTOR
 SPECIFIED TO FASTEN THE WOOD STUDS. WHAT IS "SIMPSON
 UPC". SEC. R301.1 FBC-RESIDENTIAL.
  
 12- SHEET A-4:
 A)FOOTING F3 SHOWN ON THE FOOTING SCHEDULE DOESN'T
 MATCH FOOTING SHOWN ON THE FOUNDATION PLAN. REVISE AS
 REQUIRED TO MATCH. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) SPECIFICATIONS SHOWN ON THE FOUNDATION PLAN AND
 DETAILS PROVIDED ARE NOT CLEAR. THEY NEED TO BE
 COORDINATED. DETAIL 2/A-4 IS FOR FOOTINGS OR FOR TIE
 BEAMS?. IF THIS DETAIL IS FOR FOOTING, THEN CLARIFY HOW
 IS THE PROPOSED 3" CONCRETE SLAB GOING TO HAVE 2 #5
 TIES THE WAY IS SHOWN ON THIS DETAIL. NOTE: CONSIDER
 THE REQUIRED REINFORCEMENT CLEARANCE. THE SEC. 107.2.1
 CITY AMENDMENTS.
  
 C)CLARIFY GENERAL CONSTRUCTION NOTE SHOWN AT THE BOTTOM
 OF SHEET. THERE IS NOT POOL IN THIS PROJECT. SEC.
 107.2.1 CITY AMENDMENTS.
  
 D) CLARIFY THICKNESS OF VAPOR BARRIER. FOUNDATION PLAN
 NOTES AND TYPICAL CONCRETE COL. TO FOOTING DETAIL ON
 SAME SHEET DON'T MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 13-SHEET A-5:
 A)ROOF FRAMING PLAN SHOWS A NEW 4"X12" STEEL I BEAM BY
 THE NEW KITCHEN AREA. THERE ARE NO DETAILS AND
 SPECIFICATIONS ON THE FOUNDATION PLAN FOR COLUMNS AND
 FOOTING TO SUPPORT THIS BEAM. PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS. ALSO, SPECIFY CONNECTIONS AT THE
 ENDS OF THIS BEAM. ALSO, PROVIDE DETAILS AND
 SPECIFICATION FOR FASTENING OF ROOF TRUSSES TO THIS
 BEAM. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) PROVIDE DETAILS AND SPECIFICATIONS FOR CONNECTIONS
 AT THE END OF ALL WOOD BEAMS SHOWN ON THE ROOF FRAMING
 PLAN. SEC. R301.1 FBC-RESIDENTIAL.
  
 C)SIZE OF PRECAST LINTEL SHOWN ON THE LINTEL SCHEDULE
 DON'T SEEM TO BE CORRECT. IT LOOKS LIKE SIZE OF
 OPENINGS ARE WIDER THAN SIZE OF LINTELS SPECIFIED.
 REVISE AS REQUIRED. AND, PROVIDE DETAIL AND
 SPECIFICATIONS SHOWN HOW ARE THE LINTELS SUPPORTED ON
 THE COLUMNS. SPECIFY HOW MUCH BEARING SUPPORT IS
 REQUIRED ON EACH END. SEC. R301.1 FBC-RESIDENTIAL.
  
 D) ROOF TRUSS CONNECTORS SPECIFIED ARE NOT CLEAR.
 CONNECTORS SPECIFIED ON THE TRUSS ANCHORAGE WOOD TO CMU
 SCHEDULE AND CONNECTORS SPECIFIED ON THE TRUSS ANCHOR
 SCHEDULE ON SAME SHEET DON'T MATCH. REVISE AS REQUIRED
 TO MATCH. ALSO, SIMPSON HETA 12 CONNECTORS DON'T
 PROVIDE AN UPLIFT VALUE OF 1810# AS SPECIFIED ON THE
 TRUSS ANCHORAGE WOOD TO CMU SCHEDULE. SEE SIMPSON
 CATALOG AND REVISE AS REQUIRED. SEC. R301.1
 FBC-RESIDENTIAL.
  
 E) THERE ARE NOTES NEXT TO THE ROOF FRAMING PLAN THAT
 DON'T APPLY TO THIS HOUSE. SEE REVISE AS REQUIRED TO
 AVOID CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS.
  
 F) THERE MANY DIFFERENT SPECIFICATIONS ON THE SAME
 SHEET FOR THE NAIL TYPE AN SPACING OF THE ROOF
 SHEATHING. REVISE AS REQUIRED TO MATCH. NOTE: SEC.
 R803.2.3.1 FBC-RESIDENTIAL REQUIRES 8D RING SHANK NAILS
 MIN. THERE IS A NOTE UNDER THE PLYWOOD SHEATHING
 NAILING SCHEDULE STATING THAT "RING SHANK NOT REQ'D
 WHEN MEAN ROOF HT<25'. THIS IS INCORRECT. REVISE AS
 REQUIRED ALSO.
  
 14-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 15- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 16- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $129,486. THE
 PERMIT FEE BALANCE IS $2854.42.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-10-07 Cont ID  
Sent By ppetty Date 2019-10-07 Time 14:54 Rev Time 0.00
Received By ppetty Date 2019-10-07 Time 14:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-03 Cont ID  
Sent By jpearson Date 2019-05-03 Time 09:16 Rev Time 0.00
Received By jpearson Date 2019-05-02 Time 09:23 Sent To  
Notes
2019-05-03 09:16:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. THERE
 ARE NOTES IN 2 LOCATIONS THAT CONFLICT WITH CODE, NOTE
 13 IN ELECTRICAL NOTES AND THE FIRST NOTE SHOWN UNDER
 "FOR NEW ELECTRIC ONLY". ALL BRANCH CIRCUITS THAT
 SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 3. PANEL SCHEDULE STATES THAT PANEL A IS EXISTING, BUT
 THE RISER DIAGRAM STATES THAT IT IS A NEW PANEL.
 CORRECT DISCREPANCY. WPB FBC 107.2.1
 4. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN
 EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 5. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 7. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS
 SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
 8. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 9. TWO NOTES STATE THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. ONE OF THE NOTES
 CITES THE 2008 NEC WHICH IS NOT THE CURRENT CODE.
 PROVIDE CORRECTION. ELECTRICAL NOTE 14 AND SECOND NOTE
 UNDER "FOR NEW ELECTRIC ONLY". NEC 406.12; FBC RE
 E4002.14; FBC PREFACE
 10. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. LOAD CALULATION PROVIDED DOES NOT INCLUDE THE
 SQUARE FOOTAGE DEMAND AS PER THE FBC RESIDENTIAL
 METHOD. NEC 220; FBC RE E3602.2
 11. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 12. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE E3901
 13. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION FOR BATH 1. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-07 Cont ID  
Sent By pvalenti Date 2020-05-07 Time 14:58 Rev Time 0.00
Received By pvalenti Date 2020-04-30 Time 14:34 Sent To  
Notes
2020-05-04 14:35:1005/04/2020 SENT TO PETER VALENTI. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-10-20 Cont ID  
Sent By pvalenti Date 2019-10-20 Time 13:43 Rev Time 0.00
Received By pvalenti Date 2019-10-03 Time 12:08 Sent To  
Notes
2019-10-04 12:08:50R25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-17 Cont ID  
Sent By jgomez Date 2019-05-17 Time 14:46 Rev Time 0.00
Received By jgomez Date 2019-04-10 Time 14:20 Sent To I
Notes
2019-04-11 14:20:50R26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2020-05-27 Cont ID  
Sent By pvalenti Date 2020-05-27 Time 14:53 Rev Time 0.00
Received By pvalenti Date 2020-05-27 Time 14:53 Sent To  
Notes
2020-05-27 14:56:13PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 IMPACT FEE REVIEW APPROVED:
  
 THE IMPACT FEES HAVE BEEN REVIEWED BY THE COUNTY;
 RECEIPT # MU-2020-016581-0000 (PLANS ARE STAMPED BY
 COUNTY)

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2020-05-07 Cont ID  
Sent By pvalenti Date 2020-05-07 Time 14:53 Rev Time 0.00
Received By pvalenti Date 2020-05-07 Time 14:52 Sent To  
Notes
2020-05-07 14:57:44PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-05-17 Cont ID  
Sent By jgomez Date 2019-05-17 Time 14:45 Rev Time 0.00
Received By jgomez Date 2019-05-17 Time 14:44 Sent To  
Notes
2019-05-17 14:45:34IMPACT FEES - PAPER SUBMITTALS
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-10-18 Cont ID  
Sent By cmontell Date 2019-10-18 Time 13:48 Rev Time 0.00
Received By cmontell Date 2019-10-18 Time 13:42 Sent To  
Notes
2019-10-18 13:48:18MECHANICAL PLAN REVIEW PASS WITH PROVISOS
  
 1 - NO RETURNS ON PLANS PLEASE HAVE INSTALLED FOR ROUGH
 INSPECTION
  
  
 CHRIS MONTELLO
 805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By cmontell Date 2019-05-14 Time 15:03 Rev Time 0.00
Received By cmontell Date 2019-05-14 Time 14:53 Sent To  
Notes
2019-05-14 15:02:55MECHANICAL PLAN REVIEW FAIL
  
 1- NEED EQUIPMENT SIZING PER 2017 - FLORIDA BUILDING
 CODE - ENERGY CONSERVATION SEC R403.7.1 EQUIPMENT
 SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS THAT AFFECT EQUIPMENT
 SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT INCLUDE
 LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS. NEW OR REPLACEMENT HEATING AND COOLING
 EQUIPMENT SHALL HAVE AN EFFICIENCY RATING EQUAL TO OR
 GREATER THAN THE MINIMUM REQUIRED BY FEDERAL LAW FOR
 THE GEOGRAPHIC LOCATION WHERE THE EQUIPMENT IS
 INSTALLED.
  
 2 NEED ENERGY PERFORMANCE LEVEL PER 2017 - FLORIDA
 BUILDING CODE - ENERGY CONSERVATION SEC R401.3 ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD (MANDATORY) THE
 BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW (SECTION 553.9085, FLORIDA STATUTES)
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX RD.
  
 CHRIS MONTELLO
 805-6733
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-04-18 Cont ID  
Sent By thunt Date 2019-04-18 Time 15:41 Rev Time 0.00
Received By thunt Date 2019-04-18 Time 15:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2019-05-17 Cont ID  
Sent By jgomez Date 2019-05-17 Time 14:45 Rev Time 0.00
Received By jgomez Date 2019-05-17 Time 14:45 Sent To  
Notes
2019-05-17 14:46:18SHINGLES NOA 16-0811.11.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-10-15 Cont ID  
Sent By rfalcone Date 2019-10-15 Time 08:37 Rev Time 0.00
Received By rfalcone Date 2019-10-15 Time 08:37 Sent To I
Notes
2019-10-15 08:42:3610/15/2019 PASSED.
  
 THE PROPOSED RENOVATION EXCEEDS THE 50% VALUATION OF
 EXISTING STRUCTURE. PLEASE SUBMIT A SEPERATE
 LANDSCAPING PERMIT PRIOR TO ISSUANCE OF CERTIFICATE OF
 OCCUPANY.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT HTTPS://WPB.ORG/DEPARTME
 NTS/DEVELOPMENT-SERVICES/OVERVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: (561) 822-1442
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-04-25 Cont ID  
Sent By mcurz Date 2019-04-25 Time 16:58 Rev Time 0.00
Received By mcruz Date 2019-04-25 Time 16:39 Sent To PC
Notes
2019-04-25 16:58:40ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PROPOSED RENOVATION EXCEEDS THE 50% VALUATION OF
 EXISTING STRUCTURE. SUBMIT A SEPARATE LANDSCAPING
 PERMIT.
 2) INDICATE THE OVERHANG DIMENSION. STRUCTURAL
 OVERHANGS, INCLUDING BUT NOT LIMITED TO BALCONIES,
 CORNICES, GUTTERS, EAVES, AND ROOF OVERHANG PROJECTIONS
 SHALL NOT EXTEND FARTHER THAN THREE FEET INTO ANY
 SETBACK.
 3) CORNER SETBACK DIMENSION REQUIREMENT IS 12.5', YOU
 INDICATE 12' ON PLAN.
  
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER
 THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO
 SCHEDULE AN APPOINTMENT.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]