Plan Review Details - Permit 19040484
Plan Review Stops For Permit 19040484
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-10-02 Cont ID  
Sent By pvalenti Date 2019-10-02 Time 14:13 Rev Time 0.00
Received By pvalenti Date 2019-10-02 Time 14:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-06-05 Cont ID  
Sent By pvalenti Date 2019-06-05 Time 07:51 Rev Time 0.00
Received By pvalenti Date 2019-06-05 Time 07:51 Sent To  
Notes
2019-06-05 08:16:55***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 > DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107.
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE,
 WOOD, MARBLE, ETC.).
 4. STATED VALUE OF WORK.
 5. DESCRIPTION OF EXISTING SITE CONDITIONS:
 (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ).
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
  
 FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  
 SUBMIT TWO COPIES OF THE TEST REPORTS FOR THE SOUND
 INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED
 FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-15 Cont ID  
Sent By pvalenti Date 2019-04-15 Time 10:55 Rev Time 0.00
Received By pvalenti Date 2019-04-15 Time 10:55 Sent To  
Notes
2019-04-15 11:04:03***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107. PROVIDE MORE INFORMATION:
  
 A. PROVIDE A COMPLETE LAYOUT OF THE UNIT; WE NEED TO
 SEE IF ANY OF THE WALLS IN THE BATHROOM ARE
 TENANT/CORRIDOR SEPERATION WALLS.
 B. WHAT MATERIAL WILL BE USED TO REPLACE SECTIONS OF
 WALL WHERE REQUIRED?
 C. WHAT MATERIAL WILL BE USED TO REPAIR FLOOR CONCRETE
 WHERE REQUIRED?
 D. WHAT TYPE OF FLOORING/UNDERLAYMENT WILL BE USED IF
 REQUIRED?

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-06-03 Cont ID  
Sent By jpearson Date 2019-06-03 Time 13:56 Rev Time 0.00
Received By jpearson Date 2019-06-03 Time 06:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-05-17 Cont ID  
Sent By pleduc Date 2019-05-17 Time   Rev Time 0.00
Received By pleduc Date 2019-05-17 Time 14:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-02 Cont ID  
Sent By pvalenti Date 2019-10-02 Time 14:14 Rev Time 0.00
Received By pvalenti Date 2019-09-26 Time 14:14 Sent To  
Notes
2019-09-27 14:14:37RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-05 Cont ID  
Sent By pvalenti Date 2019-06-05 Time 08:17 Rev Time 0.00
Received By pvalenti Date 2019-05-15 Time 15:07 Sent To  
Notes
2019-06-05 07:04:41TO PV DESK
  
2019-05-16 15:07:57B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-15 Cont ID  
Sent By pvalenti Date 2019-04-15 Time 11:04 Rev Time 0.00
Received By pvalenti Date 2019-04-10 Time 15:45 Sent To  
Notes
2019-04-11 15:45:31PLUMB <5K

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-05-31 Cont ID  
Sent By ccole Date 2019-05-31 Time 14:15 Rev Time 0.00
Received By ccole Date 2019-05-31 Time 14:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-10-02 Cont ID  
Sent By gjohnson Date 2019-10-02 Time 11:07 Rev Time 0.00
Received By gjohnson Date 2019-10-02 Time 10:35 Sent To  
Notes
2019-10-02 11:07:16PROVISO; PROVIDE 2 COPIES OF THE LETTER REFERENCED IN
 PREVIOUS COMMENTS SINGED AND SEALED BY DESIGNER OF
 RECORD, OWNER AND NOTARIZED SHALL STATE NEW DESIGN DOES
 NOT COMPLY WITH FHA OWNER MAY HAVE RETURN TO COMPLIANCE
 IF UNIT IS SOLD.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-05-22 Cont ID  
Sent By gjohnson Date 2019-05-22 Time 09:22 Rev Time 0.00
Received By gjohnson Date 2019-05-22 Time 07:08 Sent To  
Notes
2019-05-22 10:55:372ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
  
 PREVIOUS COMMENTS NOT COMPLIED:
  
 2) TOILETS ARE NOT ACCEPTABLE TO BE ADJACENT TO SHOWERS
 AS THE CLEAR FLOOR SPACE WOULD NOT COMPLY. FHA 7.44
  
 3) PROVIDE CLEAR FLOOR SPACE FOR ALL FIXTURES. ALL
 FIXTURES SHALL BE CENTERED IN THE CLEAR FLOOR SPACE.
 FHA 7.3, 7.53
 THIS BUILDING WAS DESIGNED AND BUILT IN COMPLIANCE WITH
 THE FHA ANY MODIFICATIONS SHALL REMAIN IN COMPLIANCE
 CHANGING THE TUB TO A SHOWER DOES NOT COMPLY BECAUSE IT
 DOES NOT ALLOW FOR A PARALLEL CLEAR FLOOR AT THE SHOWER
 THE DESIGN CAN BE APPROVED IF THE DESIGNER PROVIDES TWO
 COPY,S OF A SIGNED AND SEALED LETTER ON THERE LETTER
 HEAD IT SHOULD FOLLOW THE EXAMPLE BELOW.
  
 PROJECT ADDRESS: ______________________________________
 _____________________
 PERMIT NUMBER: ________________________
 THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE
 PROPOSED BATHROOM DESIGN DOES NOT MEET THE REQUIREMENTS
 OF THE FAIR HOUSING ACCESSIBILITY GUIDELINES. THE OWNER
 AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF
 SALE IF SO REQUESTED BY THE BUYER.
  
 SIGNATURE OF DESIGNER: ______________________________
 PRINTED NAME OF DESIGNER: ___________________________
  
 SIGNATURE OF OWNER: ________________________________
 PRINTED NAME OF OWNER: _____________________________
 NOTARY FOR OWNER?S SIGNATURE:
 STATE OF FLORIDA, COUNTY OF PALM BEACH
 THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME
 THIS _____ DAY OF ________, 20__ BY
 ___________________________ WHO IS PERSONALLY KNOWN TO
 ME OR WHO HAS PRODUCED: ___________________________ AS
 IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH.
 NOTARY SIGNATURE ___________________________________
 NOTARY PRINTED NAME ________________________________
  
  
  
  
  
  
 5) SUBMIT A SLAB REPAIR DETAIL FOR REVIEW SHOW HOW YOU
 INTEND ON OFFSETTING THE TUB DRAIN AND CONVERTING TO
 SHOWER. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS OF THE CONCRETE TO BE REPLACED, AND THE PSI
 OF THE CONCRETE. SHOW THE SIZE AND LENGTH OF THE
 DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE EXISTING
 SLAB, AND THE SPACING OF THE DOWELS ON CENTER.
  
  
 7) VALUE IS LOW. PROVIDE A BONA FIDE SIGN CONTRACT.
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING LAND VALUE.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-15 Cont ID  
Sent By thunt Date 2019-04-15 Time 07:34 Rev Time 0.00
Received By thunt Date 2019-04-15 Time 07:34 Sent To  
Notes
2019-04-15 07:35:25 
  
 PLUMBING 1ST REVIEW**DENIED** THIS BUILDING WAS
 CONSTRUCTED IN 2006 UNDER THE FAIR HOUSING ACT. THE
 FOLLOWING COMMENTS COME FROM THE FAIR HOUSING MANUAL
 AND THE FLORIDA BUILDING CODE
  
 1) DRAWINGS SHALL BE OF SUITABLE MATERIAL. NO PENCIL
 PERMITTED. FBC 107.2.1
  
 2) TOILETS ARE NOT ACCEPTABLE TO BE ADJACENT TO SHOWERS
 AS THE CLEAR FLOOR SPACE WOULD NOT COMPLY. FHA 7.44
  
 3) PROVIDE CLEAR FLOOR SPACE FOR ALL FIXTURES. ALL
 FIXTURES SHALL BE CENTERED IN THE CLEAR FLOOR SPACE.
 FHA 7.3, 7.53
  
 4) PROVIDE NEW CABINET DETAIL SHOWING MAX HEIGHT OF 34"
 WILL COMPLY WITH FHA 7.52
  
 5) SUBMIT A SLAB REPAIR DETAIL FOR REVIEW SHOW HOW YOU
 INTEND ON OFFSETTING THE TUB DRAIN AND CONVERTING TO
 SHOWER. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS OF THE CONCRETE TO BE REPLACED, AND THE PSI
 OF THE CONCRETE. SHOW THE SIZE AND LENGTH OF THE
 DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE EXISTING
 SLAB, AND THE SPACING OF THE DOWELS ON CENTER.
  
 6) PERSON DESIGNING PLANS SHALL SIGN AND TAKE
 RESPONSIBILITY. FBC 471, 481
  
 7) VALUE IS LOW. PROVIDE A BONA FIDE SIGN CONTRACT.
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDINGONLY LAND VALUE.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  