Plan Review Details - Permit 19040476
Plan Review Stops For Permit 19040476
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-03 Cont ID  
Sent By shill Date 2019-07-03 Time 08:38 Rev Time 0.00
Received By shill Date 2019-07-03 Time 08:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-05-01 Cont ID  
Sent By shill Date 2019-05-01 Time 18:05 Rev Time 0.00
Received By shill Date 2019-05-01 Time 18:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-07-16 Cont ID  
Sent By jleahy Date 2019-07-16 Time 16:55 Rev Time 0.00
Received By jleahy Date 2019-07-16 Time 16:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-02 Cont ID  
Sent By jleahy Date 2019-07-02 Time 14:44 Rev Time 0.00
Received By jleahy Date 2019-07-02 Time 14:41 Sent To  
Notes
2019-07-02 14:56:47FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1 RECEPTACLE NEEDS TO BE INSTALLED AT FRONT OF
 BUILDING
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE
 FRONT AND BACK OF EACH DWELLING UNIT HAVING DIRECT
 ACCESS TO GRADE LEVEL. BALCONIES, DECKS, AND PORCHES
 THAT ARE ACCESSIBLE FROM INSIDE OF THE DWELLING UNIT
 SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE
 BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE
 LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE
 THE BALCONY, DECK,
 OR PORCH SURFACE.
  
 KITCHEN COUNTER LOOKS TO BE MISSING OUTLETS FOR SPACING
 E3901.4 COUNTERTOP RECEPTACLES.
 IN KITCHENS PANTRIES, BREAKFAST ROOMS, DINING ROOMS AND
 SIMILAR AREAS OF DWELLING UNITS, RECEPTACLE OUTLETS FOR
 COUNTERTOP SPACES SHALL BE INSTALLED IN ACCORDANCE WITH
 SECTIONS E3901.4.1 THROUGH E3901.4.5
  
 OUTLETS INSTALLED SHALL MEET E3902 OF FBC FOR GFCI AND
 AFCI PROTECTION.
  
 R315.1CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN
 ATTACHED GARAGE, OR OTHER FEATURE, FIXTURE, OR ELEMENT
 THAT EMITS CARBON MONOXIDE AS BYPRODUCT OF COMBUSTION
 SHALL HAVE AN OPERATIONAL CARBON MONOXIDE ALARM
 INSTALLED WITHIN
 10 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-25 Cont ID  
Sent By jpearson Date 2019-04-25 Time 15:49 Rev Time 0.00
Received By jpearson Date 2019-04-25 Time 12:50 Sent To  
Notes
2019-04-25 15:49:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN,
 DETAILING ALL WORK PROPOSED. THERE WERE TWO SHEETS
 SUBMITTED NAMED A-1, WITH DIFFERENT INFORMATION ON
 EACH. THE ONE THAT IS SEPARATE FROM THE OTHERS, AND WAS
 NOT SIGNED, APPEARS TO BE AN ATTEMPT AT AN ELECTRICAL
 PLAN. PROVIDE CORRECTIOIN. WPB FBC 107.2.1, 107.3.5; FS
 471, 481
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 3. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-03 Cont ID  
Sent By shill Date 2019-07-03 Time 08:38 Rev Time 0.00
Received By shill Date 2019-06-18 Time 09:47 Sent To  
Notes
2019-06-20 09:47:18R21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-03 Cont ID  
Sent By hmoser Date 2019-05-03 Time 09:10 Rev Time 0.00
Received By hmoser Date 2019-04-10 Time 16:33 Sent To  
Notes
2019-04-11 16:33:14R21

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2019-05-03 Cont ID  
Sent By hmoser Date 2019-05-03 Time 09:10 Rev Time 0.00
Received By hmoser Date 2019-05-03 Time 08:51 Sent To I
Notes
2019-05-03 09:10:14NOTE ON PLAN PAGE A-1 MECHANICAL WORK UNDER SEPARATE
 PLAN AND PERMIT.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2019-05-01 Cont ID  
Sent By shill Date 2019-05-01 Time 18:03 Rev Time 0.00
Received By shill Date 2019-05-01 Time 18:03 Sent To  
Notes
2019-05-01 18:05:02NOT A SUBSTANTIAL IMPROVEMENT
 CUMULATIVE 5 YEAR $45,000 < 50% $119,055 PAPA
 IMPROVEMENT VALUE
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-24 Cont ID  
Sent By thunt Date 2019-06-24 Time 12:36 Rev Time 0.00
Received By thunt Date 2019-06-24 Time 12:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-04-18 Cont ID  
Sent By thunt Date 2019-04-18 Time 13:15 Rev Time 0.00
Received By thunt Date 2019-04-18 Time 13:15 Sent To  
Notes
2019-04-18 13:16:39PROVISO: PAN FOR WATER HEATER WITH DRAIN LINE GOING TO
 THE OUTSIDE SHALL BE REQUIRED AS CURRENT GARAGE BEING
 TURNED INTO LIVING SPACE NOW DAMAGE WILL BE CAUSED IT
 WATER HEATER SHALL LEAK.