Plan Review Details - Permit 19040464
| Plan Review Stops For Permit 19040464 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
P |
Date |
2019-08-07 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-08-07 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-08-07 |
Time |
08:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
F |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-06-24 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-06-24 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2019-06-24 08:57:58 | SEE BUILDING COMMENT. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-05-28 |
Time |
07:41 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-05-28 |
Time |
07:41 |
Sent To |
|
|
| Notes |
| 2019-05-28 07:41:54 | 319 FBC[R] ADDRESSES ARE NEEDED FOR THIS PROJECT. THE | | | PERMIT CANNOT BE ISSUED UNTIL AND ADDRESS HAS BEEN | | | ASSIGNED TO THE BUILDING. | | | - PLEASE CALL MICHAEL ORIO BY PHONE AT 561-494-1080, OR | | | BY E-MAIL [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-08-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-08-16 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-08-16 |
Time |
13:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-06-24 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-06-24 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2019-06-24 08:56:46 | BUILDING REVIEW COMMENTS | | | W.P.B. PERMIT: 19040464 | | | 2 ND REVIEW: JUNE 24, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[B] = FBC BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | | | | 5)319 FBC[R] ADDRESSES ARE NEEDED FOR THIS PROJECT. THE | | | PERMIT CANNOT BE ISSUED UNTIL AND ADDRESS HAS BEEN | | | ASSIGNED TO THE BUILDING. | | | - PLEASE CALL MICHAEL ORIO BY PHONE AT 561-494-1080, OR | | | BY E-MAIL [email protected] | | | REPONSE SAYS ADDRESS IS ON SITE PLAN. | | | - I DON'T SEE THE BUILDING ADDRESS ON SD-4. | | | WHAT IS THE ADDRESS ASSIGNED BY MICHAEL ORIO FOR THIS | | | SPECIFIC BUILDINGH? THE PERMIT ADDRESS IN OUR SYSTEM | | | NEEDS TO MATCH THE ASSIGNED BUILDING ADDRESS BEFORE THE | | | PERMIT IS ISSUED. | | | | | | 6) REQUIREMENT 2 - ACCESSIBLE AND USABLE PUBLIC AND | | | COMMON USE AREAS | | | - SHOW ACCESSIBLE PATH TO TRASH COLLECTION AREA. | | | - RESPONSE SAYS SEE LS-0.4.1. THIS IS NOT A SITE PLAN | | | AND THE PATH CAN'T BE SEEN TO THE TRASH AREA IN THE | | | PARKING LOT. PLEASE SHOW ACCESSIBLE PATH ON PLAN THAT | | | WILL SHOW THE PATH AND HOW IT RELATES TO THE SITE. | | | | | | 9) 1011.12 FBC[B] | | | - ROOF HATCH OK SINCE NO MECHANICAL ACCESS. | | | 1011.12.2 FBC[B] SHEET A-2.4.6 SHOWS 30 X 36 INCH BILCO | | | HATCH. PLEASE DIMENSION THE ROOF HATCH TO SHOW IT IS 16 | | | SQ. FT MINIMUM. MINIMUM WIDTH SHOULD ALLOW FOR | | | EQUIPMENT REPLACEMENT. | | | NEW COMMENT: | | | 1011.12.1, IN BUILDINGS WITHOUT AN OCCUPIED ROOF ACCESS | | | TO THE ROOF FROM THE TOP STORY SHALL BE PERMITTED TO BE | | | BY AN ALTERNATING TREAD DEVICE, A SHIPS LADDER OR A | | | PERMANENT LADDER. | | | - HOW IS THE ROOF HATCH ACCESSED? | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-05-28 |
Time |
07:44 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-05-28 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2019-05-28 07:45:16 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 19040464 | | | REVIEWED: MAY 28, 2019 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[B] = FBC BUILDING | | | FBC[EXISTING] = FBC EXISTING BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | FBC[R] = FBC RESIDENTIAL | | | | | | 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH | | | ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES | | | TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH | | | THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND | | | THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR | | | GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS | | | ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO. | | | 4504-14, AND CITY OF WEST PALM BEACH CODE OF | | | ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION | | | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS | | | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. PER CITY OF | | | WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART IN | | | PUBLIC PLACES, SECTION 78-122, RENOVATION AND NEW | | | CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO THE | | | ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE | | | PROJECTS. SEC. 78-129. - PUBLIC ART ASSESSMENT FOR | | | PRIVATE DEVELOPMENT. (A) APPLICABILITY. THE PROVISIONS | | | OF THIS ARTICLE AND THE PUBLIC ART ASSESSMENT SECTION | | | SHALL APPLY TO ALL PRIVATE DEVELOPMENT PROJECTS, | | | INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR | | | IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL | | | CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN | | | $750,000.00. ALL BUILDINGS WITHIN NEW PLANNED | | | DEVELOPMENTS SHALL BE ASSESSED CUMULATIVELY TOWARDS | | | THIS ART IN PUBLIC PLACES REQUIREMENT, EVEN IF THE | | | BUILDINGS ARE PERMITTED SEPARATELY OR DEVELOPED IN | | | PHASES. THE PROVISIONS OF THIS SECTION APPLY TO NEW | | | DEVELOPMENT OR NEW CONSTRUCTION WITHIN EXISTING PLANNED | | | DEVELOPMENTS. | | | - THIS PROJECT MEETS THE CRITERIA TO PROVIDE AIPP. | | | PLEASE CONTACT: MS. SYBILLE WELTER ART IN PUBLIC PLACES | | | COORDINATOR 822-1515 E-MAIL: [email protected] | | | | | | 2) 109.3 FBC[AMENDED] PROVIDE COST ESTIMATING METHOD | | | AND CALCULATIONS THAT WERE USED FOR PERMIT VALUATION. | | | - THE VALUE APPEARS TO BE BASED AT AROUND 100 DOLLARS | | | PER SQUARE FOOT. CURRENT CONSTRUCTION COSTS FOR ANY | | | TYPE OF NEW CONSTRUCTION WOULD EXCEED THAT AMOUNT. | | | PLEASE EVALUATE CONSTRUCTION COSTS. THE COSTS WOULD | | | EXCLUDE LAND AND ITEMS THAT WILL BE PERMITTED SEPARATLY | | | (FIRE ALARM AND FIRE SPRINKLERS) | | | | | | 3) 107.5.3 FBC[AMENDED] CODE EDITIONS. | | | - SHEET LS-0.4.0 JUST BELOW FAIR HOUSING EDITION. | | | PLEASE REMOVE REFERENCES TO FT. LAUDERDALE. | | | | | | 4) F.S. 553.79(5) THRESHOLD BUILDING. | | | THIS PROJECT MEETS THE DEFINITION OF A THRESHOLD | | | BUILDING. THE FOLLOWING IS REQUIRED PRIOR TO | | | COMMENCEMENT. | | | A) COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT | | | OF UNDERSTANDING; IF PDF OF AGREEMENT IS NEEDED PLEASE | | | CONTACT THE BUILDING PLAN REVIEWER AND THEY WILL | | | PROVIDE VIA E-MAIL. [email protected] | | | B) PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL | | | PROPOSED INSPECTORS. PLEASE INCLUDE AS MANY ADDITIONAL | | | INSPECTORS AS POSSIBLE BECAUSE THESE ARE THE ONLY | | | PEOPLE THAT THE CHIEF BUILDING INSPECTOR WILL ALLOW TO | | | BE ON-SITE. | | | C) ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT | | | REQUIRED BY FS553.79(7)(D). ?ALL PLANS FOR THE BUILDING | | | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE | | | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECTS OR ENGINEERS | | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE | | | FIRE SAFETY STANDARDS AS DETERMINED BY THE LOCAL | | | AUTHORITY IN ACCORDANCE WITH THIS CHAPTER 553 AND | | | CHAPTER 633.? | | | D) OK-FOUND SHEET S-1.1 THRESHOLD INSPECTION PLAN | | | REQUIRED, FS553.79(5)A). | | | - THERE IS A SIMILAR STATEMENT LIKE ITEM C IN THE | | | COMMENT ABOVE, BUT IT NEEDS TO BE THE STATEMENT IN | | | QUOTES FROM ITEM C ABOVE. | | | | | | 5)319 FBC[R] ADDRESSES ARE NEEDED FOR THIS PROJECT. THE | | | PERMIT CANNOT BE ISSUED UNTIL AND ADDRESS HAS BEEN | | | ASSIGNED TO THE BUILDING. | | | - PLEASE CALL MICHAEL ORIO BY PHONE AT 561-494-1080, OR | | | BY E-MAIL [email protected] | | | | | | 6) REQUIREMENT 2 - ACCESSIBLE AND USABLE PUBLIC AND | | | COMMON USE AREAS | | | - SHOW ACCESSIBLE PATH TO TRASH COLLECTION AREA. | | | | | | 7) REQUIREMENT 3 - USABLE DOORS. THE DOORS IN COMMON | | | SPACES AND THE SIDE ENTERING INTO DWELLING UNITS NEED | | | TO HAVE USABLE HARDWARE THAT CAN BE USED WITHOUT TIGHT | | | GRASPING OR TWISTING. | | | - TYPICALLY THE HARDWARE WOULD BE A LEVER TYPE. THIS | | | TYPE OF HARDWARE WOULD NOT BE REQUIRED ONCE INSIDE THE | | | UNIT. YOU MAY WANT TO CLARIFY HARDWARE ON THE DOOR | | | SCHEDULE. | | | | | | 8) REQUIREMENT 5 - LIGHT SWITCHES, OUTLETS, THERMOSTATS | | | AND OTHE CONTROLS IN ACCESSIBLE LOCATIONS. (SIDE | | | REACHES OVER OBSTRUCTIONS) | | | - PLEASE VERIFY THAT A NOTE OR REFERENCE TO THE | | | REQUIRED HEIGHTS CAN BE FOUND IN ELECTRICAL PAGES WHERE | | | THE CONTRACTOR WILL SEE THEM. | | | | | | 9) 1011.12 FBC[B] STAIRWAY TO ROOF. IN BUILDINGS FOUR | | | OR MORE STORIES ABOVE GRADE PLANE, ONE STAIRWAY SHALL | | | EXTEND TO THE ROOF SURFACE UNLESS THE ROOF HAS A SLOPE | | | STEEPER THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL | | | (33-PERCENT SLOPE). | | | - PROVIDE STAIRWAY TO ROOF, OR PROVIDE CODE SECTION | | | THAT EXEMPTS 1011.12 FOR BUILDINGS OVER 4 STORIES. | | | | | | 10) 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING | | | CAPACITY AND FOUNDATION RECOMMENDATIONS. | | | - PLEASE UPLOAD GEOTECHNICAL REPORT INTO SUPPORTING | | | DOCUMENTS IN PROJECTDOX | | | | | | 11) 107.3.5 FBC[AMENDED] | | | - STRUCTURAL S-2.4.1 NOTE 1 SHOULD NOT REFERENCE NAVD | | | SINCE IT CONFLICTS WITH CIVIL PLANS. JUST A REFERENCE | | | TO SEE CIVIL PLANS WOULD SUFFICE. | | | | | | 12) 1803.6 FBC[B] REPORTING. WHERE GEOTECHNICAL | | | INVESTIGATIONS ARE REQUIRED, A WRITTEN REPORT OF THE | | | INVESTIGATIONS SHALL BE SUBMITTED TO THE BUILDING | | | OFFICIAL BY THE PERMIT APPLICANT AT THE TIME OF PERMIT | | | APPLICATION. THIS GEOTECHNICAL REPORT SHALL INCLUDE, | | | BUT NEED NOT BE LIMITED TO, THE FOLLOWING INFORMATION: | | | - (SEE 1803.6 FOR REQUIREMENTS) | | | | | | 13) 3002.4 FBC[B] ELEVATOR CAR TO ACCOMMODATE AMBULANCE | | | STRETCHER. ANY BUILDING THAT IS MORE THAN THREE STORIES | | | HIGH OR IN WHICH THE VERTICAL DISTANCE BETWEEN THE | | | BOTTOM TERMINAL LANDING AND THE TOP TERMINAL LANDING | | | EXCEEDS 25 FEET (7620 MM), MUST BE CONSTRUCTED TO | | | CONTAIN AT LEAST ONE PASSENGER ELEVATOR THAT IS | | | OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE DEPARTMENT | | | EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL | | | BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE AN | | | AMBULANCE STRETCHER 24 INCHES BY 76 INCHES (610 MM BY | | | 1950 MM) WITH NOT LESS THAN 5-INCH (127 MM) RADIUS | | | CORNERS, IN THE HORIZONTAL, OPEN POSITION AND SHALL BE | | | IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY | | | MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL BE | | | NOT LESS THAN 3 INCHES (76 MM) IN HEIGHT AND SHALL BE | | | PLACED INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME. | | | - SHOW HOW STRECHER WILL FIT IN ONE OF THE ELEVATORS. A | | | SGRAPHIC REPRESENTAION OF 24X74 INCH RECTANGLE WITH | | | MAXIMUM 5 INCH RADIUS CORNERS FROM ENTRY TO FINAL | | | POSITION ON PLAN VIEW WILL SUFFICE. | | | | | | 14) 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE | | | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE | | | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT | | | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE | | | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A | | | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL | | | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE | | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION | | | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | - PLEASE PROVIDE A LIST OF DEFERRED SUBMITTALS SO THAT | | | I WILL NOT ASK FOR ITEMS THAT WILL BE SUPPLIED AT A | | | LATER DATE, OR INDICATE WHICH PAGE A LIST CAN BE FOUND. | | | | | | 15) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS | | | FOR WINDOWS, WINDOW MULL (IF APPLICABLE), DOORS, | | | TRANSOMS, SLIDERS OR INDICATE THAT YOU WOULD LIKE THEM | | | DEFERED. | | | | | | 16) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT | | | APPROVAL(P.A.) FOR ROOFING, OR INDICATE THAT YOU WOULD | | | LIKE THEM DEFERED. INCLUDE P.A. FOR RIDGE VENTS IN | | | ROOFING SUBMITTAL | | | | | | 17) 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS | | | TO THE BUILDING INSPECTOR PRIOR TO INSTALLATION. | | | - THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN | | | SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE | | | DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE | | | REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION. | | | | | | 18) 107.2.1.2 FBC[AMENDED] PROVIDE STAIRCASE AND GUARD | | | RAIL ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED. | | | | | | 19) 1014 FBC [B] GUARDS AND HANDRAILS. 1607.8 FBC [B] | | | LOADS ON HANDRAILS AND GUARDRAILS. PROVIDE HANDRAIL AND | | | GUARDRAIL ENGINEERING, OR INDICATE THAT YOU WOULD LIKE | | | IT DEFERRED. | | | | | | 20) 107.3.4. FBC[AMENDED] A CONSTRUCTION GUARDRAIL | | | DETAIL, PREPARED BY A DESIGN PROFESSIONAL LICENSED | | | UNDER FS471 OR FS481, IS REQUIRED TO BE SUBMITTED, | | | REVIEWED AND ISSUED BY THE CITY OF WEST PALM BEACH, OR | | | INDICATE THAT IT WILL BE DEFERRED. *SUBJECT TO THE | | | INSPECTORS DISCRETION, THIS MAY BE ACCEPTED IN THE | | | FIELD AT TIME OF INSPECTION. | | | | | | 21) 1207.2 FBC[B] PLEASE ADVISE ,VIA EMAIL, WHAT | | | FLOORING AND UNDERLAYMENT ARE PROPOSED? IF THE | | | UNDERLAYMENT PRODUCT PROPOSED IS NOT ONE FOR WHICH WE | | | HAVE TEST REPORTS ON FILE, THE FOLLOWING REPORTS WILL | | | BE REQUIRED: | | | 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND | | | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND | | | SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF | | | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E90. | | | 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING | | | ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR | | | BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR | | | NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN | | | ACCORDANCE WITH ASTM E492. | | | 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | 22) 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND | | | FLOOR COVERING MATERIALS SHALL COMPLY WITH SECTIONS | | | 804.2 THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND | | | COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL, | | | LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING | | | MATERIALS THAT ARE NOT COMPRISED OF FIBERS. | | | | | | 103.1.1.2 FBC[CE] CODE COMPLIANCE CERTIFICATION. THE | | | BUILDINGS OWNER, THE OWNERS ARCHITECT, OR OTHER | | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | | RENOVATION. | | | -PLEASE HAVE APPROPRIATE PARTIES SIGN THE ENERGY | | | CALCULATIONS. | | | | | | NOTES: | | | | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-08-23 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-08-23 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-08-23 |
Time |
09:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-07-15 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-07-15 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-07-15 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2019-07-15 12:59:09 | IN PROGRESS. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | 2. CORRECTED. | | | 3. CORRECTED. | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. CORRECTED. | | | 7. CORRECTED. | | | 8. MANY OF THE UNIT PLANS DO NOT SHOW THE LOCAL SMOKE | | | ALARMS. PROVIDE CORRECTION. WPB FBC 107.2.1 (THE SMOKE | | | ALARMS ARE NOW SHOWN, HOWEVER, THEY ARE SHOWN ON | | | DIFFERENT CIRCUITS. THERE SHOULD BE ONE CIRCUIT WITH | | | INTERCONNECTION BETWEEN THE ALARMS. PROVIDE | | | CORRECTION.) | | | 9. CORRECTED. | | | 10. CORRECTED. | | | 11. CORRECTED. | | | | | | NEW COMMENTS: | | | | | | 12. SEVERAL SHEETS FROM THE FIRST SUBMISSION THAT STATE | | | THEY ARE 95% DOCUMENTS HAVE NOT BEEN REPLACED WITH THIS | | | SUBMISSION. PROVIDE A FULL SET FOR REVIEW. WPB FBC | | | 107.2.1 | | | 13. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC | | | 210.8(D) | | | 14. AS THIS IS NOT A 100% SUBMITTAL, FURTHER COMMENTS | | | NOT ADDRESSED IN THIS REVIEW MAY BE POSSIBLE UPON NEXT | | | REVIEW. WPB FBC 107.2.1 | | | | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-05-17 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-05-17 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-05-17 |
Time |
07:33 |
Sent To |
|
|
| Notes |
| 2019-05-17 13:32:46 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND | | | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN | | | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE | | | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN | | | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC | | | 105.1, 107.2.1 | | | 2. SHEET E-3.4.0 AND E-5.4.0 SHOW A SERVICE FOR PANEL | | | S. SITE LIGHTING AND SERVICE SHOULD BE A SEPARATE | | | SUBMITTAL. IF THIS IS ATTACHED TO THE BUILDING, THEN | | | THE SERVICE SHOULD BE TIED TO THE GROUNDING ELECTRODE | | | SYSTEM OF THAT BUILDING. IT SHOULD ALSO BE LABELED AS | | | AN ADDITIONAL SERVICE, OR AN ADDITIONAL MAIN. MAINS | | | NEED TO BE GROUPED. ADDITIONAL SERVICES NEED TO BE | | | LABELED PROPERLY. PROVIDE CLARIFICATIONS AND | | | CORRECTIONS AS NEEDED. WPB FBC 107.2.1; NEC 215.5, | | | 230.2, 230.72, 250.50 | | | 3. LABEL MAINS AND SERVICES PROPERLY. PLAN SHOWS MS-1 | | | AS MAIN 1 OF 2, BUT IT DOESN'T APPEAR TO HAVE ONE MAIN | | | SWITCH. IT APPEARS THAT THIS SWITCHBOARD WOULD INCLUDE | | | 3 MAINS. PROVIDE CLARIFICATIONS AND CORRECTIONS AS | | | NEEDED. WPB FBC 107.2.1; NEC 215.5, 230.2 | | | 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | 5. PROVIDE COMPLIANCE WITH NEC 240.87. | | | 6. NOTE FOR AIC CALCULATION NOTED AS A DEFERRED | | | SUBMITTAL. PROVIDE WHEN AVAILABLE. NEC 110.9, 110.10 | | | 7. PANEL H SHOWS A LOAD OF 222.64 AMPS. THE PANEL | | | SCHEDULE STATES THAT THIS IS A 200 AMP PANEL, WHICH | | | WOULD BE OVERLOADED. PANEL MDP SHOWS A 200 AMP BREAKER | | | FEEDING THIS PANEL. PROVIDE CORRECTION. NEC 408.30, | | | 408.36 | | | 8. MANY OF THE UNIT PLANS DO NOT SHOW THE LOCAL SMOKE | | | ALARMS. PROVIDE CORRECTION. WPB FBC 107.2.1 | | | 9. SHEET E-4.5.0 IS ILLEGIBLE. PROVIDE CORRECTION. WPB | | | FBC 107.2.1 | | | 10. PROVIDE NOTE FOR LABELING OF UNIT PANELS. THE | | | CURRENT PLAN SHOWS THE PANELS NAMED AFTER THE TYPE OF | | | UNIT. THE IDENTIFICATION SHALL INCLUDE AN APPROVED | | | DEGREE OF DETAIL THAT ALLOWS EACH CIRCUIT TO BE | | | DISTINGUISHED FROM ALL OTHERS. NEC 408.4 | | | 11. MAIN ELECTRICAL ROOM AND ELECTRICAL ROOM ON 3RD | | | FLOOR CONTAIN LARGE EQUIPMENT THAT WOULD REQUIRE AND | | | ENTRY/EXIT AT EACH END OF THE WORK SPACE. IT APPEARS | | | THAT NEITHER OF THE EXCEPTIONS TO THIS REQUIREMENT HAVE | | | BEEN MET. PROVIDE CLARIFICATION AND CORRECTIONS AS | | | NEEDED. NEC 110.26(C)(2) | | | | | | AS THIS IS NOT A 100% SUBMITTAL, FURTHER COMMENTS NOT | | | ADDRESSED IN THIS REVIEW MAY BE POSSIBLE UPON NEXT | | | REVIEW. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2019-08-21 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2019-08-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2019-08-21 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-08-21 09:51:30 | REVIEWED UNDER FORMAL ENGINEERING SUBMITTAL E19010020. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-07-19 |
Time |
06:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-07-19 |
Time |
06:34 |
Sent To |
|
|
| Notes |
| 2019-07-19 06:34:20 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | | APPLICATION IF REQUIRED | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | | | MAIN PHONE: (561) 822-1200 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2019-04-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-04-30 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-04-30 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2019-04-30 10:03:53 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | | APPLICATION IF REQUIRED | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | | | MAIN PHONE: (561) 822-1200 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2019-07-30 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-07-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-07-30 |
Time |
15:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-06-13 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-06-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-06-13 |
Time |
15:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-04-29 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-04-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-04-29 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2019-04-29 11:55:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET A 0.4 - THERE IS NO INDCATION OF INFORMATION | | | UNDER SECTION, FIRE ALARM. THERE ARE, HOWEVER, | | | INDICATIONS OF FIRE ALARM ON OTHER PLAN SHEETS. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | 2) SHEET C 6.00 - THEREARE INDICATION OF FIRE MAINS AND | | | UNDERGROUNG FIRE LINES. | | | | | | ALL UNDERGROUND FIRE LINE AND FIRE MAINS SHALL BE | | | INSTALLED AND INSPECTED PER NFPA 24. | | | | | | PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS | | | PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT, | | | | | | | | | | | | 2A) SHEET C 6.00 - WATER SUPPLY SHALL BE INSTALLED AND | | | MAINTAINED PRIOR TO ANY WORK ON A STRUCTURE. | | | | | | PER NFPA 241, SAFEGUARDING CONSTRUCTION, ALTERATION, | | | AND DEMOLITION OPERATIONS | | | | | | 8.7.2 WATER SUPPLY. | | | 8.7.2.1* AWATER SUPPLY FOR FIRE PROTECTION, EITHER | | | TEMPORARY OR | | | PERMANENT, SHALL BE MADE AVAILABLE AS SOON AS | | | COMBUSTIBLE | | | MATERIAL ACCUMULATES. | | | 8.7.2.2 THERE SHALL BE NO DELAY IN THE INSTALLATION OF | | | FIRE PROTECTION | | | EQUIPMENT. (SEE A.8.2.5.) | | | 8.7.2.3* WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE | | | TO | | | BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND IN | | | SERVICE | | | PRIOR TO COMMENCING CONSTRUCTION WORK ON ANY STRUCTURE. | | | | | | PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS | | | PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT, | | | | | | | | | | | | 3) SHEET FP 2.1.2 - THERE APPEAR TO BE AN INDICATION OF | | | ONE STANDPIPE CABINET WITHIN THE EXIT CORRIDOR. | | | . | | | PER NFPA 1 | | | | | | 13.2.2.2 NEW BUILDINGS SHALL BE EQUIPPED WITH A CLASS I | | | STANDPIPE | | | SYSTEM INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF | | | SECTION 13.2 | | | WHERE ANY OF THE FOLLOWING CONDITIONS EXIST: | | | (1) MORE THAN THREE STORIES ABOVE GRADE WHERE THE | | | BUILDING IS | | | PROTECTED BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM | | | | | | PER NFPA 14 | | | | | | 7.3.2* CLASS I SYSTEMS. CLASS I SYSTEMS SHALL BE | | | PROVIDED WITH | | | 21?2 IN. (65 MM) HOSE CONNECTIONS IN THE FOLLOWING | | | LOCATIONS: | | | (1) AT THE MAIN FLOOR LANDING IN EXIT STAIRWAYS | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | 3A) SHEET FP 2.1.2 - THERE ARE INDICATIONS OF | | | STANDPIPE. | | | | | | PER NFPA 241: | | | | | | 7.6 STANDPIPES. IN ALL NEW BUILDINGS IN WHICH | | | STANDPIPES ARE | | | REQUIRED OR WHERE STANDPIPES EXIST IN BUILDINGS BEING | | | ALTERED | | | OR DEMOLISHED, SUCH STANDPIPES SHALL BE MAINTAINED IN | | | CONFORMITY | | | WITH THE PROGRESS OF BUILDING CONSTRUCTION IN SUCH A | | | MANNER | | | THAT THEY ARE ALWAYS READY FOR USE. | | | | | | 8.7.4.2 STANDPIPE INSTALLATIONS IN BUILDINGS UNDER | | | CONSTRUCTION. | | | WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION, IN | | | BUILDINGS UNDER CONSTRUCTION, A STANDPIPE SYSTEM, | | | EITHER TEMPORARY | | | OR PERMANENT IN NATURE, SHALL BE INSTALLED IN | | | ACCORDANCE | | | WITH 8.7.4.2.1 THROUGH 8.7.4.2.10. | | | 8.7.4.2.1 THE STANDPIPES SHALL BE PROVIDED WITH | | | CONSPICUOUSLY | | | MARKED AND READILY ACCESSIBLE FIRE DEPARTMENT | | | CONNECTIONS | | | ON THE OUTSIDE OF THE BUILDING AT THE STREET LEVEL AND | | | SHALL | | | HAVE AT LEAST ONE STANDARD HOSE OUTLET AT EACH FLOOR. | | | 8.7.4.2.2 THE PIPE SIZES, HOSE VALVES, HOSE, WATER | | | SUPPLY, AND | | | OTHER DETAILS FOR NEW CONSTRUCTION SHALL BE IN | | | ACCORDANCE WITH | | | THIS STANDARD. | | | 8.7.4.2.3 THE STANDPIPES SHALL BE SECURELY SUPPORTED | | | AND RESTRAINED | | | AT EACH ALTERNATE FLOOR. | | | 8.7.4.2.4* AT LEAST ONE APPROVED HOSE VALVE FOR | | | ATTACHING FIRE | | | DEPARTMENT HOSE SHALL BE PROVIDED AT EACH INTERMEDIATE | | | LANDING | | | OR FLOOR LEVEL IN THE EXIT STAIRWAY, AS DETERMINED BY | | | THE | | | AUTHORITY HAVING JURISDICTION. | | | 8.7.4.2.5 VALVES SHALL BE KEPT CLOSED AT ALL TIMES AND | | | GUARDED | | | AGAINST MECHANICAL INJURY. | | | 8.7.4.2.6 HOSE VALVES SHALL HAVE NH STANDARD EXTERNAL | | | THREADS FOR THE VALVE SIZE SPECIFIED IN ACCORDANCE WITH | | | NFPA 1963, STANDARD FOR FIRE HOSE CONNECTIONS, UNLESS | | | MODIFIED | | | BY 8.7.4.2.7. | | | 8.7.4.2.7 WHERE LOCAL FIRE DEPARTMENT CONNECTIONS DO | | | NOT CONFORM | | | TO NFPA 1963, STANDARD FOR FIRE HOSE CONNECTIONS, THE | | | AUTHORITY | | | HAVING JURISDICTION SHALL DESIGNATE THE CONNECTION TO | | | BE USED. | | | 8.7.4.2.8* THE STANDPIPES SHALL BE EXTENDED UP WITH | | | EACH | | | FLOOR AND SHALL BE SECURELY CAPPED AT THE TOP. | | | 8.7.4.2.9 TOP HOSE OUTLETS SHALL BE NOT MORE THAN ONE | | | FLOOR | | | BELOW THE HIGHEST FORMS, STAGING, AND SIMILAR | | | COMBUSTIBLES AT | | | ALL TIMES. | | | 8.7.4.2.10 TEMPORARY STANDPIPES SHALL REMAIN IN SERVICE | | | UNTIL | | | THE PERMANENT STANDPIPE INSTALLATION IS COMPLETE. | | | | | | STANDPIPES ARE REQUIRED TO BE INSTALLED WHEN | | | CONSTRUCTION STARTS AT THE 3RD LEVEL. | | | | | | | | | PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS | | | PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT, | | | | | | | | | 3B) THERE APPEARS TO ONLY ON FIRE DEPARTMENT CONNECTION | | | ON EACH FLOOR. | | | | | | PER NFPA 14 | | | | | | 7.3.2.2* WHERE THE MOST REMOTE PORTION OF A | | | NONSPRINKLERED | | | FLOOR OR STORY IS LOCATED IN EXCESS OF 150 FT (45.7 M) | | | OF TRAVEL | | | DISTANCE FROM A HOSE CONNECTION IN OR ADJACENT TO A | | | REQUIRED | | | EXIT OR THE MOST REMOTE PORTION OF A SPRINKLERED FLOOR | | | OR STORY | | | IS LOCATED IN EXCESS OF 200 FT (61 M) OF TRAVEL | | | DISTANCE FROM A | | | HOSE CONNECTION IN OR ADJACENT TO A REQUIRED EXIT, | | | ADDITIONAL | | | HOSE CONNECTIONS SHALL BE PROVIDED, IN APPROVED | | | LOCATIONS, | | | WHERE REQUIRED BY THE LOCAL FIRE DEPARTMENT OR THE AHJ. | | | | | | PLEASE REVIEW AND CORRECT AS THE DISTANCE APPEARS TO BE | | | EXCEEDED OR JUSTIFY WITH SPECIFIC DIMENSIONS. | | | | | | | | | 4) SHEET LS 4.0 - UNDER THE PROJECT NARRATIVE THERE ARE | | | INDICATIONS OF "ENCLOSED PARKING GARAGE AND "HIGHEST | | | OCCUPIED FLOOR LEVEL ABOVE FIRE DEPARTMENT ACCESS | | | 317'-6", AS WELL AS, OTHER HIGH RISE REFERENCES. | | | | | | PLEASE REVIEW AND CLARIFY/CORRECT. | | | | | | | | | | | | | | | 5) SHEET LS 0.4.1(A 0.4 ACTUAL) - WITHIN THE INDEX | | | SHEET LS 0.4.1 IS INDICATED FOR THE LIFE SAFETY OF | | | FLOOR 1 - 5. THERE ARE NO INDICATIONS OF LIFE SAFETY ON | | | THAT SHEET. SHEET LS 0.4.1 IS INDICATED AS SHEET A 0.4 | | | IN THE LOWER RIGHT TILTE BLOOCK. | | | | | | PLEASE REVIEW AND COORECT AND PROVIDE THE APPLICABLE | | | LIFE SAFETY SHEETS. | | | | | | | | | | | | | | | 5) SHEET E 2.4.0 - THERE INDICATIONS OF FIRE ALARM | | | DEVICES AND EQUIPMENT. | | | | | | ALL FIRE ALARM EQUIPMENT AND DEVICES SHALL BE INSTALLED | | | UNDER SEPARATE PERMIT AND SHOP DRAWINGS. | | | | | | PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS | | | PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT, | | | | | | | | | | | | 5) SHEET E 2.4.1 - THERE IS AN INDICATION OF A FACP | | | WITHIN A FOYER AREA; HOWEVER, THERE IN NO INDICATION OF | | | A SMOKE DETECTOR OVER IT. | | | | | | PER NFPA 72 | | | | | | 10.4.4* IN AREAS THAT ARE NOT CONTINUOUSLY OCCUPIED, | | | AUTOMATIC | | | SMOKE DETECTION SHALL BE PROVIDED AT THE LOCATION OF | | | EACH FIRE ALARM CONTROL UNIT(S), NOTIFICATION APPLIANCE | | | CIRCUIT | | | POWER EXTENDERS, AND SUPERVISING STATION TRANSMITTING | | | EQUIPMENT | | | TO PROVIDE NOTIFICATION OF FIRE AT THAT LOCATION. | | | EXCEPTION: WHERE AMBIENT CONDITIONS PROHIBIT | | | INSTALLATION OF AUTOMATIC | | | SMOKE DETECTION, AUTOMATIC HEAT DETECTION SHALL BE | | | PERMITTED. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | | | | 6) SHEET A 7.4.1 - A 42" GUARD RAIL IS INDICATED AT THE | | | EXTERIOR OF THE STAIRWELLS. DETAILS OF THIS PROPOSED | | | RAILING IS LIMITED. | | | | | | PER NFPA 101, CH 7 MEANS OF EGRESS. | | | | | | 7.2.2.6.2* VISUAL PROTECTION. OUTSIDE STAIRS SHALL BE | | | ARRANGED TO | | | AVOID ANY IMPEDIMENTS TO THEIR USE BY PERSONS HAVING A | | | FEAR OF HIGH | | | PLACES. OUTSIDE STAIRS MORE THAN 36 FT (11 M) ABOVE THE | | | FINISHED | | | GROUND LEVEL, OTHER THAN PREVIOUSLY APPROVED EXISTING | | | STAIRS, SHALL BE | | | PROVIDED WITH AN OPAQUE VISUAL OBSTRUCTION NOT LESS | | | THAN 48. IN. | | | (1220 MM) IN HEIGHT. | | | | | | PLEASE REVIEW AND CORRECT/PROVIDE DETAILS OF | | | COMPLIANCE. | | | | | | | | | | | | 7)WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION | | | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. | | | | | | | | | | | | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-08-26 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-08-26 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-07-29 |
Time |
10:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-07-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-07-19 |
Time |
06:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-06-10 |
Time |
08:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-05-28 |
Time |
07:44 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-04-10 |
Time |
16:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2019-08-06 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-08-06 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-06-19 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2019-08-06 07:52:00 | RECEIPT - MU-2019-0731-329 - $294,071.99 PAID | | 2019-06-19 16:34:03 | 6/19/19 SENT TO IMPACT FOR REVIEW PER APPLICANT. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-05-28 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-05-28 |
Time |
07:42 |
Sent To |
|
|
| Notes |
| 2019-05-28 07:42:58 | 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC | | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2019-08-20 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-08-15 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-08-15 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2019-08-15 15:10:01 | MECHANICAL REVIEW | | | | | | APPROVED PER CHRIS COLE (REMOTELY) |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-07-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-07-11 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-07-10 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2019-07-11 09:25:14 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #19040464 | | | 7/10/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS: THE | | | SUBMITTED TRACE HEAT LOAD CALCULATIONS ARE NOT IN | | | COMPLIANCE WITH SECTIONS C407.5.2.2 & C407.5.2.2 FBC EC | | | BECAUSE ZONES HAVE NOT BEEN DEFINED. C407.5.2.3 | | | MULTIFAMILY RESIDENTIAL BUILDINGS. | | | RESIDENTIAL SPACES SHALL BE MODELED USING ONE THERMAL | | | BLOCK PER SPACE EXCEPT THAT THOSE FACING THE SAME | | | ORIENTATIONS ARE PERMITTED TO BE COMBINED INTO ONE | | | THERMAL BLOCK. CORNER UNITS AND UNITS WITH ROOF OR | | | FLOOR LOADS SHALL ONLY BE COMBINED WITH UNITS SHARING | | | THESE FEATURES. | | | | | | 2) COMMENT #3 FROM THE 1ST REVIEW PARTIALLY EXISTS: | | | PROVIDE THE SEQUENCE OF OPERATION FOR THE EXHAUST FAN | | | IN THE STORAGE AND DOMESTIC PUMP ROOMS. A) THE REQUIRED | | | CLEARANCE DISTANCE MEASUREMENTS FROM THE EXHAUST OUTLET | | | TO OPERABLE OPENINGS AND GRADE NOT PROVIDED. | | | | | | 3) COMMENT #4 FROM THE 1ST REVIEW STILL EXISTS: M5.1.1: | | | PLEASE CORRECT THE FBC MINIMUM VENTILATION CALCULATIONS | | | AND REMOVE OR CORRECT THE NOTES SPECIFYING RATES BASED | | | ON THE TABLES IN THE FBC R, THE FBC R CODE IS | | | APPLICABLE ONLY FOR SINGLE FAMILY HOMES, DUPLEXES, AND | | | TOWNHOUSES. REFER TO SECTION 403.3.2.1 FBC M COPIED | | | BELOW, AND INDICATE COMPLIANCE: | | | 403.3.2.1 OUTDOOR AIR FOR DWELLING UNITS. | | | AN OUTDOOR AIR VENTILATION SYSTEM CONSISTING OF A | | | MECHANICAL EXHAUST SYSTEM, SUPPLY SYSTEM OR COMBINATION | | | THEREOF SHALL BE INSTALLED FOR EACH DWELLING UNIT. | | | LOCAL EXHAUST OR SUPPLY SYSTEMS, INCLUDING OUTDOOR AIR | | | DUCTS CONNECTED TO THE RETURN SIDE OF AN AIR HANDLER, | | | ARE PERMITTED TO SERVE AS SUCH A SYSTEM. THE OUTDOOR | | | AIR VENTILATION SYSTEM SHALL BE DESIGNED TO PROVIDE THE | | | REQUIRED RATE OF OUTDOOR AIR CONTINUOUSLY DURING THE | | | PERIOD THAT THE BUILDING IS OCCUPIED. THE MINIMUM | | | CONTINUOUS OUTDOOR AIRFLOW RATE SHALL BE DETERMINED IN | | | ACCORDANCE WITH EQUATION 4-9. | | | (EQUATION 4-9) | | | WHERE: | | | QOA = OUTDOOR AIRFLOW RATE, CFM | | | AFLOOR = FLOOR AREA, FT2 | | | NBR = NUMBER OF BEDROOMS; NOT TO BE LESS THAN ONE | | | EXCEPTION: THE OUTDOOR AIR VENTILATION SYSTEM IS NOT | | | REQUIRED TO OPERATE CONTINUOUSLY WHERE THE SYSTEM HAS | | | CONTROLS THAT ENABLE OPERATION | | | FOR NOT LESS THAN 1 HOUR OF EACH 4-HOUR PERIOD. THE | | | AVERAGE OUTDOOR AIR FLOW RATE OVER THE 4-HOUR PERIOD | | | SHALL BE NOT LESS THAN THAT PRESCRIBED BY EQUATION 4-9. | | | | | | 4) COMMENT #9 FROM THE 1ST REVIEW STILL EXISTS. PLEASE | | | NOTE THAT ALL BEDROOM RETURN TRANSFERS FROM THE MASTER | | | BEDROOM SUITES ARE UNDERSIZED WITH THE EXCEPTION OF | | | UNIT C2 WHICH HAS (2) 16X6 TRANSFERS. M4.4.1, 4.4.2, | | | 4.4.3, 4.4.5, & 4.4.6: THE RETURN TRANSFER GRILLS AT | | | THE MASTER BEDROOM SUITES ARE UNDERSIZED PER SECTION | | | 601.6(2) AND 601.6(3) FBC M. THE RETURNS MUST BE SIZED | | | LARGE ENOUGH TO RETURN ALL AIR FROM THE SUITE AT 50 SQ. | | | INCHES PER 100 CFMS OF SUPPLY AIR. | | | | | | 5) COMMENT #10 FROM THE 1ST REVIEW STILL EXISTS: | | | M7.4.2- AC CLOSET DETAIL: INDICATE THE TYPE AND SIZE OF | | | CONDENSATE PIPING FOR THE AIR HANDLER- SECTIONS 307.2.1 | | | AND 602.2.1 FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-05-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-05-08 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-05-08 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2019-05-08 13:11:46 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19040464 | | | 5/8/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENERGYGAUGE COMPLIANCE SUBMITTAL MUST BE | | | CERTIFIED ON PAGE 4 WITH ELECTRONIC SEALS AND | | | SIGNATURES BY THE DESIGN PROFESSIONALS OF RECORD- | | | SECTION C103.1.1 FBC EC. | | | | | | 2) THE SUBMITTED TRACE HEAT LOAD CALCULATIONS ARE NOT | | | IN COMPLIANCE WITH SECTIONS C407.5.2.2 & C407.5.2.2 FBC | | | EC BECAUSE ZONES HAVE NOT BEEN DEFINED. PLEASE REVIEW | | | THE CODE SECTIONS PRINTED BELOW. | | | | | | C407.5.2.2 HVAC ZONES NOT DESIGNED. WHERE HVAC ZONES | | | HAVE NOT YET BEEN DESIGNED, THERMAL BLOCKS SHALL BE | | | DEFINED BASED ON SIMILAR INTERNAL LOAD DENSITIES, | | | OCCUPANCY, LIGHTING, THERMAL AND TEMPERATURE SCHEDULES, | | | AND IN COMBINATION WITH THE FOLLOWING GUIDELINES: | | | 1.SEPARATE THERMAL BLOCKS SHALL BE ASSUMED FOR INTERIOR | | | AND PERIMETER SPACES. INTERIOR SPACES SHALL BE THOSE | | | LOCATED MORE THAN 15 FEET (4572 MM) FROM AN EXTERIOR | | | WALL. PERIMETER SPACES SHALL BE THOSE LOCATED CLOSER | | | THAN 15 FEET (4572 MM) FROM AN EXTERIOR WALL. | | | 2.SEPARATE THERMAL BLOCKS SHALL BE ASSUMED FOR SPACES | | | ADJACENT TO GLAZED EXTERIOR WALLS: A SEPARATE ZONE | | | SHALL BE PROVIDED FOR EACH ORIENTATION, EXCEPT | | | ORIENTATIONS THAT DIFFER BY NOT MORE THAN 45 DEGREES | | | (0.79 RAD) SHALL BE PERMITTED TO BE CONSIDERED TO BE | | | THE SAME ORIENTATION. EACH ZONE SHALL INCLUDE FLOOR | | | AREA THAT IS 15 FEET (4572 MM) OR LESS FROM A GLAZED | | | PERIMETER WALL, EXCEPT THAT FLOOR AREA WITHIN 15 FEET | | | (4572 MM) OF GLAZED PERIMETER WALLS HAVING MORE THAN | | | ONE ORIENTATION SHALL BE DIVIDED PROPORTIONATELY | | | BETWEEN ZONES. | | | 3.SEPARATE THERMAL BLOCKS SHALL BE ASSUMED FOR SPACES | | | HAVING FLOORS THAT ARE IN CONTACT WITH THE GROUND OR | | | EXPOSED TO AMBIENT CONDITIONS FROM ZONES THAT DO NOT | | | SHARE THESE FEATURES. | | | 4.SEPARATE THERMAL BLOCKS SHALL BE ASSUMED FOR SPACES | | | HAVING EXTERIOR CEILING OR ROOF ASSEMBLIES FROM ZONES | | | THAT DO NOT SHARE THESE FEATURES. | | | | | | C407.5.2.3MULTIFAMILY RESIDENTIAL BUILDINGS. | | | RESIDENTIAL SPACES SHALL BE MODELED USING ONE THERMAL | | | BLOCK PER SPACE EXCEPT THAT THOSE FACING THE SAME | | | ORIENTATIONS ARE PERMITTED TO BE COMBINED INTO ONE | | | THERMAL BLOCK. CORNER UNITS AND UNITS WITH ROOF OR | | | FLOOR LOADS SHALL ONLY BE COMBINED WITH UNITS SHARING | | | THESE FEATURES. | | | | | | 3) SHEET M2.1.1: PROVIDE EXHAUST VENTILATION | | | CALCULATIONS FOR THE STORAGE AND DOMESTIC PUMP ROOM AND | | | INDICATE THE SEQUENCE OF OPERATION FOR THE FANS- SEE | | | TABLE 403.3.1.1 AND 501.4 FBC M. A) SHOW THE REQUIRED | | | CLEARANCE DISTANCES FOR THE EXHAUST OUTLETS TO OPERABLE | | | AND MECHANICAL AIR INTAKES, AND FROM GRADE- SECTION | | | 501.3.1 FBC M. | | | | | | 4) M5.1.1: PLEASE CORRECT THE FBC MINIMUM VENTILATION | | | CALCULATIONS AND REMOVE OR CORRECT THE NOTES SPECIFYING | | | RATES BASED ON THE TABLES IN THE FBC R, THE FBC R CODE | | | IS APPLICABLE ONLY FOR SINGLE FAMILY HOMES, DUPLEXES, | | | AND TOWNHOUSES. REFER TO SECTION 403.3.2.1 FBC M COPIED | | | BELOW, AND INDICATE COMPLIANCE: | | | | | | 403.3.2.1 OUTDOOR AIR FOR DWELLING UNITS. | | | | | | AN OUTDOOR AIR VENTILATION SYSTEM CONSISTING OF A | | | MECHANICAL EXHAUST SYSTEM, SUPPLY SYSTEM OR COMBINATION | | | THEREOF SHALL BE INSTALLED FOR EACH DWELLING UNIT. | | | LOCAL EXHAUST OR SUPPLY SYSTEMS, INCLUDING OUTDOOR AIR | | | DUCTS CONNECTED TO THE RETURN SIDE OF AN AIR HANDLER, | | | ARE PERMITTED TO SERVE AS SUCH A SYSTEM. THE OUTDOOR | | | AIR VENTILATION SYSTEM SHALL BE DESIGNED TO PROVIDE THE | | | REQUIRED RATE OF OUTDOOR AIR CONTINUOUSLY DURING THE | | | PERIOD THAT THE BUILDING IS OCCUPIED. THE MINIMUM | | | CONTINUOUS OUTDOOR AIRFLOW RATE SHALL BE DETERMINED IN | | | ACCORDANCE WITH EQUATION 4-9. | | | | | | (EQUATION 4-9) | | | WHERE: | | | | | | QOA = OUTDOOR AIRFLOW RATE, CFM | | | | | | AFLOOR = FLOOR AREA, FT2 | | | | | | NBR = NUMBER OF BEDROOMS; NOT TO BE LESS THAN ONE | | | | | | EXCEPTION: THE OUTDOOR AIR VENTILATION SYSTEM IS NOT | | | REQUIRED TO OPERATE CONTINUOUSLY WHERE THE SYSTEM HAS | | | CONTROLS THAT ENABLE OPERATION | | | FOR NOT LESS THAN 1 HOUR OF EACH 4-HOUR PERIOD. THE | | | AVERAGE OUTDOOR AIR FLOW RATE OVER THE 4-HOUR PERIOD | | | SHALL BE NOT LESS THAN THAT PRESCRIBED BY EQUATION 4-9. | | | | | | 5) SHEETS M2.4.1, M2.4.2, M2.4.3, M2.4.4, M2.4.5 & | | | M7.4.2: THE PLANS DO NOT INDICATE HOW AIR IN THE | | | CORRIDORS IS BEING RETURNED TO RTU-OA. PLEASE NOTE THAT | | | CORRIDORS SHALL NOT SERVE AS RETURN DUCTS- SECTION | | | 601.2 FBC M | | | | | | 6) SHEETS M4.4.1, M4.4.2, M4.4.3, M4.4.4, M4.4.5, & | | | M4.4.6: LOCAL EXHAUST SYSTEMS ARE REQUIRED FOR THE | | | KITCHENS AT A RATE OF 100 CFMS INTERMITTENT OR 25 CFMS | | | CONTINUOUS. INDICATE HOW COMPLIANCE WILL BE MET. | | | | | | 7) A4.4.10, M4.4.1, M4.4.2, M4.4.3, M4.4.4, M4.4.5, & | | | M4.4.6: THE CITY OF WPB BUILDING DEPARTMENT REQUIRES | | | EITHER THE DESIGN PROFESSIONAL OF RECORD OR THE | | | INTUMESCENT PAINT MANUFACTURER TO CERTIFY THE | | | APPLICATION OF THE PAINT ON THE INTERIOR SIDES OF THE | | | AC CLOSET DOORS- SECTION 107.2.1 WPB. FINAL MECHANICAL | | | APPROVAL IS CONTINGENT ON RECEIPT OF A SIGNED AND | | | SEALED LETTER OR REPORT BY THE DESIGN PROFESSIONAL OF | | | RECORD, OR A MANUFACTURER'S CERTIFICATION LETTER WITH | | | AN APPROVAL STAMP BY THE DESIGN PROFESSIONAL. PLEASE | | | PLACE NOTES ON THE PLANS ACCORDINGLY. | | | | | | 8) M4.4.1, M4.4.2, M4.4.3, M4.4.4, M4.4.5, & M4.4.6: | | | SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CLOTHES | | | DRYERS- SECTION 504.1 FBC M. PLEASE NOTE THAT DRYER | | | EXHAUST DUCTS SHALL NOT RUN THROUGH ABOVE CEILING | | | PLENUM SPACES- SECTION 504.4 FBC M. | | | | | | 9) M4.4.6: THE RETURN GRILL AT THE MASTER BEDROOM IS | | | UNDERSIZED PER SECTION 601.6(2) AND 601.6(3) FBC M. THE | | | RETURN MUST BE SIZED LARGE ENOUGH TO RETURN ALL AIR | | | FROM THE SUITE AT 50 SQ. INCHES PER 100 CFMS OF SUPPLY | | | AIR. | | | | | | 10) M7.4.2- AC CLOSET DETAIL: INDICATE THEY TYPE AND | | | SIZE OF CONDENSATE PIPING FOR THE AIR HANDLER- SECTIONS | | | 307.2.1 AND 602.2.1 FBC M. | | | | | | 11) M2.4.6 & M7.4.2: PROVIDE COMPLETE WIND LOAD | | | ENGIMNEERING FOR ATTACHEMNT OF THE RTU AND CURB, AND | | | EXTERIOR DUXCTWORK PO THE ROOF STRUCTURE- SECTION | | | 301.15 FBC M. | | | | | | 12) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S | | | ARE REQUIRED FOR THE ROOFTOP CONDENSER STANDS AND | | | EXHAUST AND O/A INLET LOUVERS. THESE MAY BE SUBMITTED | | | NOW WITH THE ENGINEER OF RECORD'S SHOP DRAWING STAMP OF | | | APPROVAL, OR MAY BE DEFERRED SUBMITTALS- SEE SECTION | | | 107.3.4.1 WPB. PLEASE NOTE THAT THE O/A LOUVERS SHALL | | | BE AMCA 550 RATED PER SECTION 401.5 FBC M. | | | | | | 13) CLARIFY IF THERE WILL BE AN ELEVATOR MACHINERY OR | | | CONTROL ROOM AND SHOW THE LOCATION IF APPLICABLE- | | | SECTION 3005.1. PLEASE NOTE THAT ELEVATOR MACHINE OR | | | CONTROLS ROOMS REQUIRE INDEPENDENT VENTILATION SYSTEMS- | | | SECTION 3005.2. FBC B. | | | | | | 14) CLARIFY IF THE HOISTWAY WILL BE VENTED AND PROVIDE | | | DETAILS- LOCATION OF VENT, TYPE AND SIZE OF VENT AND | | | DAMPER ETC. PLEASE NOTE THAT PLUMBING AND MECHANICAL | | | SYSTEMS SHALL NOT BE LOCATED IN THE HOISTWAY ENCLOSURE- | | | SECTION 3002.9 FBC B. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-08-26 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-08-26 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-08-23 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-07-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-07-09 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-06-28 |
Time |
17:34 |
Sent To |
|
|
| Notes |
| 2019-07-09 17:08:29 | 2ND REVIEW: 19040464 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH | | | | | | 3) SHT. A-10.4.1, A-10.4.2 AND A-10.4.3 THE LEGEND | | | REFERENCED IN THE RESPONSE LETTER DOES NOT SHOW THE | | | REQUIRED 56" X48" CLEAR FLOOR SPACE FOR THE TOILET | | | PLEASE ADD TO LEGEND PER FHA DESIGN MANUAL REQUIREMENT | | | #7 | | | | | | 8) PLEASE PROVIDE MANUFACTURE SPECIFICATION FOR SUB | | | METER IT SHALL SHOW THAT METER IS RATED FOR AIR PLENUM | | | NON COMBUSTIBLE MATERIAL. | | | | | | NEW COMMENTS; | | | | | | 1. SEPARATE PERMIT REQUIRED FOR ALL BACK FLOWS PLACE | | | NOTE ON PLAN.PER WPB UTILITIES DEPARTMENT | | | | | | 2. PROVIDE OVER FLOW ROOF DRAIN SIZING CALCULATIONS. | | | PER FBC PL 1106.2 | | | | | | 3. SHT. P-6.1.1 THE SAMPLING POINT SHALL NOT HAVE A | | | WELL BELOW PIPING THAT CAN HOLD EFFLUENT A 4" TWO WAY | | | CLEAN OUT IS ALL THAT IS REQUIRED. PER WPB UTIL. DEPT. | | | | | | 4. SHT. P-5.1.1 SHOWS A ZURN Z1170 SHT. P-6.1.1 SHOWS A | | | SCHIER GB 250 AND A STRIEM CB-275 PLEASE PROVIDE A | | | PLUMBING SITE PLAN THE CIVILS DO NOT SHOW INTERCEPTORS. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | 5. PROVIDE SIZING CALCULATIONS FOR ALL INTERCEPTORS. | | | PER FBC PL 1003.2 | | | | | | A COMPLETE REVIEW CAN NOT BE COMPLETED DUE TO PLAN NOT | | | COMPLETE MARKED AS 75% COMPLETE PROVIDE 100% COMPLETE | | | PLANS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-05-21 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-05-07 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-05-06 |
Time |
07:58 |
Sent To |
|
|
| Notes |
| 2019-05-07 16:46:33 | | | | 1ST REVIEW: 19040464 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THIS PROJECT SHALL COMPLY WITH FBC ACC 233.3.1 AND | | | | | | 233.3.1.1 RESIDENTIAL DWELLING UNITS WITH MOBILITY | | | FEATURES. IN FACILITIES WITH RESIDENTIAL DWELLING | | | UNITS, AT LEAST 5 PERCENT, BUT NO FEWER THAN ONE UNIT, | | | OF THE TOTAL NUMBER OF RESIDENTIAL DWELLING UNITS SHALL | | | PROVIDE MOBILITY FEATURES COMPLYING WITH 809.2 THROUGH | | | 809.4 AND SHALL BE ON AN ACCESSIBLE ROUTE AS REQUIRED | | | BY 206. | | | | | | 233.3.1.2 RESIDENTIAL DWELLING UNITS WITH COMMUNICATION | | | FEATURES. IN FACILITIES WITH RESIDENTIAL DWELLING | | | UNITS, AT LEAST 2 PERCENT, BUT NO FEWER THAN ONE UNIT, | | | OF THE TOTAL NUMBER OF RESIDENTIAL DWELLING UNITS SHALL | | | PROVIDE COMMUNICATION FEATURES COMPLYING WITH 809.5. | | | PLEASE CLEARLY INDICATE WHICH UNITS COMPLY. PER WPB | | | AMEND TO FBC 107.2 | | | | | | 2. THE LAVATORY'S IN THE B BATHROOMS SHALL BE MAX 34" | | | OFF FINISH FLOOR. PER FHA DESIGN MANUAL REQ.. #7 | | | | | | 3. SHT. A-10.4.1, A-10.4.2 AND A-10.4.3 SHOW DIMENSIONS | | | ON THE CLEAR FLOOR SPACE FOR THE TOILET, LAVATORY, | | | SHOWER AND KITCHEN PER FHA DESIGN MANUAL REQ. #7 | | | | | | 4.SHT. P-2.0.0 IN THE MIDDLE OF THE PAGE THERE IS A | | | NOTE UNDER SEPARATE PERMIT WHAT IS THIS NOTE FOR PLEASE | | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 5. SHT. P-2.4.1 IT APPEARS THAT THE SANITARY PIPING IS | | | SHOWN AS A DASHED LINE PLEASE CLARIFY THE PLUMBING | | | LEGEND SHOWS THE VENT AS A DASHED LINE PLEASE LABEL ALL | | | PIPING. PER WPB AMEND TO FBC 107.2.1 | | | | | | 6. SHT. P-2.4.6 OVER FLOW DRAIN ARE REQUIRED ON ROOFS | | | THE CAN COLLECT WATER IF THE MAIN DRAIN FAILS PLEASE | | | SHOW OVERFLOW DRAIN LOCATIONS. PER FBC PL 1108.1 | | | | | | 7. PLEASE PROVIDE A PAN DRAIN RISER. PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | 8. PROVIDE MANUFACTURE SPECIFICATIONS FOR SUB METER. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2019-08-26 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-08-26 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-08-26 |
Time |
13:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2019-08-26 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-08-26 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-08-26 |
Time |
13:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2019-07-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-07-09 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-07-09 |
Time |
17:50 |
Sent To |
|
|
| Notes |
| 2019-07-09 17:51:52 | 2ND REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: NOT COMPLIED | | | | | | 1. RAIN SENSOR REQUIRED PLEASE SHOW ON PLAN. PER FS | | | 373.62 | | | | | | PLANS MARKED AS 75% COMPLETE PROVIDE 100% COMPLETE | | | PLANS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-05-06 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-05-06 |
Time |
17:41 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-05-06 |
Time |
17:41 |
Sent To |
|
|
| Notes |
| 2019-05-06 17:45:38 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. RAIN SENSOR REQUIRED PLEASE SHOW ON PLAN. PER FS | | | 373.62 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2019-06-24 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-06-24 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-06-24 |
Time |
08:58 |
Sent To |
|
|
| Notes |
| 2019-06-24 09:14:50 | ROOFING SUBMITTAL DUE WITH SUB PERMIT. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-05-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-05-28 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-05-28 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2019-05-28 07:44:29 | 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVAL(P.A.) | | | FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM | | | DEFERED. INCLUDE P.A. FOR RIDGE VENTS IN ROOFING | | | SUBMITTAL. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2019-08-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-08-16 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-08-16 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2019-08-16 13:11:08 | IF ANY ADDITIONAL SHEETS ARE PROVIDED THEY WILL NEED TO | | | BE DIGITALLY SIGNED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2019-06-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-06-17 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-06-17 |
Time |
17:43 |
Sent To |
|
|
| Notes |
| 2019-06-17 17:49:48 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SOME CIVIL PAGES HAVE A DIGITAL SIGNATURE THAT WAS | | | SELF CERTIFIED (EXAMPLE: C1.01); DOES NOT COMPLY WITH | | | FAC61G15-23.004. OTHERS WERE SIGNED WITH A SIGNATURE | | | ISSUED BY IDENTRUST (EXAMPLE:C6.00) AND ARE OK. | | | | | | 2. OTHER PAGES OK; PLEASE ADVISE IF ALL TRADES PASS | | | THIS REVIEW CYCLE. | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-04-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-04-30 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-04-30 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2019-04-30 10:20:02 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | PLANS ARE NOTED AS 95%. 100% DOCUMENTS ARE REQUIRED FOR | | | PERMIT ISSUANCE. | | | | | | 1. THE ENERGY CALCS ARE NOT DIGITALLY SIGNED AND | | | SEALED, FS471, 481. | | | | | | 2. SURVEY, ARCHITECTURAL PAGES OK (SIGNATURES, TITLE | | | BLOCK). | | | | | | 3. CIVIL PAGES LACK THE STATEMENT REQUIRED BY | | | FAC61G15-23.004 (REQUIRED FOR DIGITALLY SIGNED | | | DOCUMENTS). PLEASE ADDRESS, BUT ONLY RESUBMIT PAGES | | | WHICH CHANGE DUE TO CODE RELATED COMMENTS. | | | | | | 4. PLEASE SUBMIT LANDSCAPE PAGES WITH A SEPARATE | | | LANDSCAPE PERMIT APPLICATION. | | | | | | 5. STRUCTURAL PAGES PREPARED BY EDUARDO GONZALEZ ARE | | | 95%. 100% PERMIT DOCUMENTS ARE REQUIRED FOR PERMIT | | | ISSUANCE. | | | | | | THE DIGITAL SIGNATURE (OR PLAN) LACKS THE STATEMENT | | | REQUIRED BY FAC61G15-23.004, PLEASE INCLUDE ON ALL | | | PAGES. | | | | | | 6. THE FMEP PAGES LACK THE STATEMENT REQUIRED BY | | | FAC61G15-23.004, ALSO LACK A COMPLETE TITLE BLOCK (CA | | | AND NAME PROVIDED, NO ADDRESS), LACKS A SEAL. EITHER | | | THE SIGNATURE IS TO STATE "SIGNED AND SEALED" OR THE | | | IMAGE OF A SEAL IS TO BE ON EACH PAGE. | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
P |
Date |
2019-08-27 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-08-27 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-08-27 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2019-08-27 10:40:01 | PROVISO: | | | PROVIDE CONSTRUCTION PROJECT DETAILS FOR GABRIEL EVENS. | | | NO SPECIFIC PROJECTS ARE LISTED, | | | THIS WILL BE REQUESTED VIA E-MAIL. | | | DELIVER 3 ORIGINALS TO OFFICE. | | | | | | DYLAN BATTLES | | | [email protected] | | | 561-822-6718 |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2019-08-16 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-08-16 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-08-16 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2019-08-16 13:18:23 | OK-THRESHOLD PLAN S-1.1 | | | | | | 8/13/2019 -REQUESTED THRESHOLD AGREEMENT-SENT CURRENT | | | VERSION TO MARK LABLANC(S.I.) | | | | | | PENDING -RECEIVE THRESHOLD AGREEMENT FOR REVIEW |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-08-22 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2019-08-22 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2019-08-21 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2019-08-22 11:40:57 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 08.22.2019 | | | PERMIT NO.: 19040464 | | | ________________________________________ | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | ________________________________________ | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. THE SCOPE OF THIS PERMIT REVIEW IS LIMITED TO THE | | | BUILDING ONLY! SEPARATE PERMITS REQUIRED FOR | | | SURROUNDING SITE WORK, HARDSCAPE, FENCING, PARKING, | | | LANDSCAPING, SIGNAGE, ETC. | | | | | | 2. THE PROJECT IS SUBJECT TO ALL DEVELOPMENT ORDER | | | CONDITIONS, AS OUTLINED IN RESOLUTION NO. 227-18, AS | | | APPROVED BY THE CITY COMMISSION ON SEPTEMBER 24, 2018, | | | AND AS MAY BE AMENDED. | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2019-07-18 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2019-07-18 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2019-07-18 15:05:07 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 07.17.2019 | | | PERMIT NO.: 19040463, 19040464, 19040465 | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. ALL LANDSCAPE PLANS SHALL BE REMOVED FROM THE | | | BUILDING PERMIT. | | | | | | 2. THE BIKE PARKING SOUTH OF BUILDING #1 NEEDS TO BE | | | CONFIGURED SUCH THAT THERE ARE THREE (3) BIKE RACKS, | | | WITH SUFFICIENT SPACE TO ACCOMMODATE A SKY BIKE (BIKE | | | SHARE) STATION WITH AT LEAST FOUR (4) BIKES. | | | | | | 3. VARIOUS PLANS (SITE, UTILITY, HARDSCAPE, LANDSCAPE, | | | ELEVATIONS, ETC.) DO NOT MATCH THE LATEST SUBMITTAL | | | (05.10.2019) FOR THE REVISED SITE PLAN APPROVAL. THE | | | LATEST PLANS NEED TO BE SUBMITTED FOR THE SITE PLAN | | | AMENDMENT, AND ONCE APPROVED, ALL PERMITS WILL NEED TO | | | MATCH THE APPROVED AMENDMENT. | | | | | | PURSUANT TO THE REQUIREMENTS OF RESOLUTION NO. 227-18, | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY: | | | | | | A. THE DEVELOPER SHALL IMPROVE HAMPTON ROAD BETWEEN | | | SOUTH DIXIE HIGHWAY AND THE FEC RAILROAD, AS SPECIFIED | | | IN RESOLUTION NO. 227-18. | | | | | | B. THE PROPERTY SHALL BE RE-PLATTED IN ACCORDANCE WITH | | | ALL APPLICABLE STATUTES, REGULATIONS, AND THE CITY?S | | | POLICIES AND PROCEDURES. | | | | | | C. THE APPLICANT SHALL EXECUTE AND RECORD, IN A FORM | | | ACCEPTABLE TO THE CITY AND TO THE APPLICANT, A MUTUAL | | | AND RECIPROCAL CROSS ACCESS EASEMENT AT THE NORTH | | | PROPERTY LINE FOR THE BENEFIT OF BOTH THE SUBJECT | | | PROPERTY AND THE ADJACENT PROPERTY TO THE NORTH. | | | | | | D. A MAINTENANCE AGREEMENT WITH THE CITY SHALL BE | | | EXECUTED FOR THE MAINTENANCE OF THE ROAD RIGHT OF WAY | | | LANDSCAPING, TREE GRATES AND IRRIGATION ADJACENT TO THE | | | PROPERTY. THE DEVELOPER, ITS SUCCESSORS AND ASSIGNS | | | SHALL BE RESPONSIBLE FOR MAINTENANCE OF ALL SUCH | | | IMPROVEMENTS. | | | | | | E. ALL UTILITY ELEMENTS (I.E. BACKFLOW PREVENTERS, | | | ETC.) SHALL BE SCREENED WITH LANDSCAPING TO THE MAXIMUM | | | EXTENT ALLOWED BY THE CONTROLLING UTILITY AGENCY. | | | | | | IMPORTANT INFORMATION TO BE AWARE OF: | | | | | | I. ANY DAMAGE TO EXISTING UTILITIES RESULTING FROM THE | | | DEVELOPER?S CONSTRUCTION ACTIVITIES SHALL BE REPAIRED, | | | AT THE DEVELOPER?S EXPENSE. | | | | | | II. ANY REQUIRED EASEMENTS (I.E. DRAINAGE, UTILITIES, | | | PUBLIC ACCESS, ETC.) SHALL BE PROVIDED VIA PLAT OR | | | SEPARATE LEGAL INSTRUMENT. | | | | | | III. THE DEVELOPER, ITS SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES, TREE GRATES, AND RIGHT OF WAY LANDSCAPING | | | AND IRRIGATION ASSOCIATED WITH THE APPROVED SITE PLAN. | | | ALL PERMITS SHALL BE OBTAINED PRIOR TO COMMENCEMENT OF | | | CONSTRUCTION OF SUCH IMPROVEMENTS. | | | | | | IV. THE DEVELOPER, ITS SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE REMOVAL AND/OR RELOCATION OF ALL | | | STREET LIGHTS/POLES NECESSITATED BY THE PROPOSED | | | DEVELOPMENT. ALL NEW STREET LIGHTING SHALL CONFORM TO | | | THE MINIMUM REQUIREMENTS AND SHALL BE REVIEWED AND | | | PERMITTED BY ALL APPLICABLE GOVERNING AGENCIES, | | | INCLUDING THE CITY?S ENGINEERING SERVICES DEPARTMENT. | | | | | | V. FINAL APPROVAL OF THE ENGINEERING DESIGN SHALL BE | | | BASED UPON SUBMITTAL OF A SEPARATE PERMIT APPLICATION | | | TO, AND REVIEW BY, THE CITY?S PUBLIC WORKS AND | | | ENGINEERING DEPARTMENTS. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2019-05-15 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2019-05-15 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2019-05-15 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2019-05-15 10:15:07 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 05.14.2019 | | | PERMIT NO.: 19040464 | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. WHAT PERMIT IS SITE WORK BEING PERFORMED UNDER? | | | | | | 2. WHAT PERMIT IS SITE LIGHTING BEING PERFORMED UNDER? | | | A PHOTOMETRIC PLAN SHALL BE PROVIDED SHOWING THAT | | | PHOTOMETRIC LEVELS DO NOT EXCEED 1.0 FOOTCANDLES WHEN | | | MEASURED AT THE PROPERTY LINE. | | | | | | 3. ALL WORK WITHIN THE SOUTH DIXIE HIGHWAY RIGHT-OF-WAY | | | SHALL BE SUBJECT TO THE REVIEW AND PERMITTING BY THE | | | FLORIDA DEPARTMENT OF TRANSPORTATION (FDOT). PLEASE | | | PROVIDE A COPY OF SUCH PERMIT. | | | | | | 4. ALL WORK WITHIN THE HAMPTON ROAD RIGHT-OF-WAY SHALL | | | BE PERMITTED THROUGH THE CITY?S ENGINEERING SERVICES | | | DEPARTMENT. | | | | | | 5. SEPARATE LANDSCAPE PERMIT REQUIRED. ALL LANDSCAPE | | | PLANS SHALL BE REMOVED FROM THE BUILDING PERMIT | | | SUBMITTAL AND SUBMITTED UNDER A SEPARATE LANDSCAPE | | | PERMIT APPLICATION. ALL LANDSCAPE PLANS SHALL MATCH | | | THAT WHICH WAS SUBMITTED FOR THE REVISED SITE PLAN | | | APPROVAL. | | | | | | 6. THE SITE PLAN SHALL MATCH THAT WHICH WAS SUBMITTED | | | FOR THE REVISED SITE PLAN APPROVAL. | | | | | | 7. BIKE PARKING DETAIL SHALL SPECIFY THE DIMENSIONS | | | BETWEEN RACKS, BETWEEN THE RACK AND THE EDGE OF | | | PAVEMENT, ETC. DIMENSIONS SHALL MEET THE CITY?S MINIMUM | | | SPACING REQUIREMENTS. | | | | | | 8. THE LOCATIONS OF VARIOUS UTILITIES DO NOT MATCH THAT | | | WHICH WAS PROVIDED AS PART OF THE SITE PLAN AMENDMENT | | | APPLICATION. THE UTILITY LOCATIONS APPEAR TO CONFLICT | | | WITH VARIOUS LANDSCAPE ELEMENTS. | | | | | | 9. THE BIKE PARKING SOUTH OF BUILDING #1 NEEDS TO BE | | | CONFIGURED SUCH THAT THERE ARE THREE (3) BIKE RACKS, | | | WITH SUFFICIENT SPACE TO ACCOMMODATE A SKY BIKE (BIKE | | | SHARE) STATION WITH AT LEAST FOUR (4) BIKES. | | | | | | 10. VARIOUS PLANS (HARDSCAPE, LANDSCAPE, ETC.) DO NOT | | | MATCH THAT WHICH WAS SUBMITTED FOR THE REVISED SITE | | | PLAN APPROVAL; SPECIFICALLY, THE CONFIGURATION ALONG | | | THE WEST FA?ADE OF BUILDINGS #1, #2 AND #3. ENSURE THAT | | | ALL PLANS MATCH THAT WHICH WAS SUBMITTED FOR THE SITE | | | PLAN AMENDMENT. | | | | | | 11. SPECIFICATIONS FOR THE ARTIFICIAL TURF SHALL BE | | | PROVIDED SHOWING COMPLIANCE WITH SEC. 94-451(E) OF THE | | | CITY?S ZLDRS. | | | | | | 12. LOCATION OF THE FENCING SHOWN IN THE NORTHEAST | | | CORNER OF THE PROPERTY DOES NOT MATCH THAT WHICH WAS | | | SUBMITTED FOR THE REVISED SITE PLAN APPROVAL. | | | | | | 13. WHY WERE HARDSCAPE PLANS NOT PROVIDED FOR THE | | | NORTHWEST QUADRANT OF THE SITE? | | | | | | 14. IN BUILDING 3, THE MAINTENANCE ROOM WAS REMOVED AND | | | BECAME THE ?WE WORK SPACE??WITH THE FORMER WWS BEING | | | CONVERTED INTO ADDITIONAL RETAIL. IMPACT ON PARKING | | | CALCULATIONS? IMPACT ON TRAFFIC CONCURRENCY? | | | | | | 15. ELECTRIC VEHICLE CHARGING STATION IS SHOWN IN THE | | | MIDDLE OF THE SIDEWALK. | | | | | | 16. LOCATION OF FENCING IN THE NORTHEAST CORNER OF THE | | | PROPERTY DOES NOT MATCH BETWEEN THE SITE PLAN, | | | HARDSCAPE PLAN, AND LANDSCAPE PLAN. | | | | | | 17. NOT ALL FIRE HYDRANTS SHOWN ON THE LANDSCAPE PLAN | | | ARE REFLECTED ON THE SITE PLAN. | | | | | | 18. BUILDING ELEVATIONS DO NOT MATCH THAT WHICH WAS | | | SUBMITTED FOR THE REVISED SITE PLAN APPROVAL. ALL PLANS | | | NEED TO BE CONSISTENT. | | | | | | PURSUANT TO THE REQUIREMENTS OF RESOLUTION NO. 227-18, | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY: | | | | | | A. THE DEVELOPER SHALL IMPROVE HAMPTON ROAD BETWEEN | | | SOUTH DIXIE HIGHWAY AND THE FEC RAILROAD, AS SPECIFIED | | | IN RESOLUTION NO. 227-18. | | | | | | B. THE PROPERTY SHALL BE RE-PLATTED IN ACCORDANCE WITH | | | ALL APPLICABLE STATUTES, REGULATIONS, AND THE CITY?S | | | POLICIES AND PROCEDURES. | | | | | | C. THE APPLICANT SHALL EXECUTE AND RECORD, IN A FORM | | | ACCEPTABLE TO THE CITY AND TO THE APPLICANT, A MUTUAL | | | AND RECIPROCAL CROSS ACCESS EASEMENT AT THE NORTH | | | PROPERTY LINE FOR THE BENEFIT OF BOTH THE SUBJECT | | | PROPERTY AND THE ADJACENT PROPERTY TO THE NORTH. | | | | | | D. A MAINTENANCE AGREEMENT WITH THE CITY SHALL BE | | | EXECUTED FOR THE MAINTENANCE OF THE ROAD RIGHT OF WAY | | | LANDSCAPING, TREE GRATES AND IRRIGATION ADJACENT TO THE | | | PROPERTY. THE DEVELOPER, ITS SUCCESSORS AND ASSIGNS | | | SHALL BE RESPONSIBLE FOR MAINTENANCE OF ALL SUCH | | | IMPROVEMENTS. | | | | | | E. ALL UTILITY ELEMENTS (I.E. BACKFLOW PREVENTERS, | | | ETC.) SHALL BE SCREENED WITH LANDSCAPING TO THE MAXIMUM | | | EXTENT ALLOWED BY THE CONTROLLING UTILITY AGENCY. | | | | | | IMPORTANT INFORMATION TO BE AWARE OF: | | | | | | I. ANY DAMAGE TO EXISTING UTILITIES RESULTING FROM THE | | | DEVELOPER?S CONSTRUCTION ACTIVITIES SHALL BE REPAIRED, | | | AT THE DEVELOPER?S EXPENSE. | | | | | | II. ANY REQUIRED EASEMENTS (I.E. DRAINAGE, UTILITIES, | | | PUBLIC ACCESS, ETC.) SHALL BE PROVIDED VIA PLAT OR | | | SEPARATE LEGAL INSTRUMENT. | | | | | | III. THE DEVELOPER, ITS SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE | | | STREET TREES, TREE GRATES, AND RIGHT OF WAY LANDSCAPING | | | AND IRRIGATION ASSOCIATED WITH THE APPROVED SITE PLAN. | | | ALL PERMITS SHALL BE OBTAINED PRIOR TO COMMENCEMENT OF | | | CONSTRUCTION OF SUCH IMPROVEMENTS. | | | | | | IV. THE DEVELOPER, ITS SUCCESSORS AND ASSIGNS SHALL BE | | | RESPONSIBLE FOR THE REMOVAL AND/OR RELOCATION OF ALL | | | STREET LIGHTS/POLES NECESSITATED BY THE PROPOSED | | | DEVELOPMENT. ALL NEW STREET LIGHTING SHALL CONFORM TO | | | THE MINIMUM REQUIREMENTS AND SHALL BE REVIEWED AND | | | PERMITTED BY ALL APPLICABLE GOVERNING AGENCIES, | | | INCLUDING THE CITY?S ENGINEERING SERVICES DEPARTMENT. | | | | | | V. FINAL APPROVAL OF THE ENGINEERING DESIGN SHALL BE | | | BASED UPON SUBMITTAL OF A SEPARATE PERMIT APPLICATION | | | TO, AND REVIEW BY, THE CITY?S ENGINEERING DEPARTMENT. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
|