Plan Review Details - Permit 19040463
Plan Review Stops For Permit 19040463
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2019-08-20 Cont ID  
Sent By rmcdouga Date 2019-08-20 Time 11:34 Rev Time 0.00
Received By rmcdouga Date 2019-08-20 Time 11:34 Sent To  
Notes
2019-08-20 11:37:43BUILDING 1 HAS BEEN ASSIGNED THE ADDRESS OF 3151 S.
 DIXIE HWY.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2019-07-17 Cont ID  
Sent By rmcdouga Date 2019-07-17 Time 16:24 Rev Time 0.00
Received By rmcdouga Date 2019-07-15 Time 07:47 Sent To  
Notes
2019-07-17 16:24:41THE PERMIT CAN NOT BE ISSUED UNTIL AN ADDRESS HAS BEEN
 ASSIGNED TO THE PROPERTY.
 FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2019-05-23 Cont ID  
Sent By rmcdouga Date 2019-05-23 Time 17:05 Rev Time 0.00
Received By rmcdouga Date 2019-05-23 Time 17:05 Sent To  
Notes
2019-05-23 17:05:35THE PERMIT CAN NOT BE ISSUED UNTIL AN ADDRESS HAS BEEN
 ASSIGNED TO THE PROPERTY.
 FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-22 Cont ID  
Sent By rmcdouga Date 2019-08-22 Time 07:34 Rev Time 0.00
Received By rmcdouga Date 2019-08-22 Time 07:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-17 Cont ID  
Sent By rmcdouga Date 2019-07-17 Time 18:30 Rev Time 0.00
Received By rmcdouga Date 2019-07-16 Time 10:04 Sent To  
Notes
2019-07-17 16:52:32PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 3 STORY MIXED USE ( R-2, M & S-2 )
 TYPE III-B, SPRINKLERED
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) WILL COMPLY.
  
 2) PURSUANT TO FBC 109.3, THE VALUATION HAS BEEN
 ADJUSTED TO $4,471,531.00, WHICH IS THE CALCULATED
 VALUE FOR THIS MIXED USE BUILDING.
 IN ORDER TO AVOID BEING CHARGED FOR DUPLICATE PERMIT
 FEES, PLEASE PROVIDE A LIST OF THE ITEMS THAT REQUIRE A
 SEPARATE PERMIT AND THE COST FOR EACH OF THEM. THIS
 WILL ALLOW ME TO REMOVE THEIR COSTS FROM THE BUILDING
 VALUATION FOR THIS PERMIT. ALL OTHER PERMITS FIRE
 SPRINKLER, FIRE ALARM, RACK STORAGE, EXHAUST HOODS,
 ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & FREEZERS,
 ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL TANKS, GAS
 PERMIT, POOL, JACUZZI AND ASSOCIATED SUB-PERMITS,
 AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, LANDSCAPE,
 IRRIGATION, AUGER CAST PILE AND OR FOUNDATION OR
 STRUCTURE ONLY PERMIT WILL BE SEPARATE REVIEWS AND
 ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL EFFECTIVELY BE THE VALUE OF THE
 BUILDING THAT THE PERMIT FEES WILL BE BASED ON FOR THIS
 PERMIT. THE BUILDING DEPARTMENT DOES NOT WANT TO
 COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT
 COVERED UNDER THE PRIME OR MASTER PERMIT.
  
 3) COMPLIED.
  
 4) PRODUCT APPROVALS WILL BE DEFERRED.
  
 5) THE TESTING REPORTS FOR THE SOUND INSULATION FOR THE
 FLOORING FOR SOUND, FLAME SPREAD AND SMOKE DEVELOPED
 WILL BE DEFERRED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) NOT COMPLIED. NOTE IS STILL ON SOME OF THE PLAN
 SHEETS. THE NOTE THAT STATES 95% PERMIT SET NEEDS TO BE
 REMOVED FROM THE PLANS. PLANS SUBMITTED FOR PERMIT ARE
 REQUIRED TO BE 100% COMPLETE. FBC 107.2.1
  
 9) SHOP DRAWINGS FOR THE BALCONY AND STAIR GUARDS WILL
 BE DEFERRED.
  
 10) ROOF TRUSS DRAWINGS AND LAYOUT PLANS WILL BE
 DEFERRED.
  
 11) COMPLIED.
  
 12) DEFERRED. WILL COMPLY.
  
 13) DEFERRED. WILL COMPLY.
  
 14) COMPLIED.
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 17) COMPLIED.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) COMPLIED.
  
 21) COMPLIED.
  
 22) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 23) NEW COMMENT: SHEET S-1.1 HAS A THRESHOLD INSPECTION
 PLAN. THIS BUILDING IS NOT A "THRESHOLD BUILDING", IT
 WILL BE YOUR DECISION TO REMOVE THIS SHEET OR LEAVE IT
 IN THE PLANS.
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-03 Cont ID  
Sent By rmcdouga Date 2019-06-03 Time 19:17 Rev Time 0.00
Received By rmcdouga Date 2019-05-23 Time 16:58 Sent To  
Notes
2019-05-23 17:18:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 3 STORY MIXED USE ( R-2, M & S-2 )
 TYPE III-B, SPRINKLERED
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR AT
 822-1515 OR E-MAIL: [email protected]
  
 2) THE OF $3,912,215.00 IS LOW BASED ON THE LATEST ICC
 VALUATION DATA. THE CALCULATED VALUE FOR THIS MIXED USE
 BUILDING IS $4,471,531.00
 FBC 109.3 BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY ARE FREE
 OF CHARGE. IF THE M- THE QUALIFIER OF EACH COMPANY,
 THEIR INSURANCES AND LICENSURE UP TO DATE, THE M-E-P
 AND ROOFING PERMITS E-P & ROOFING PERMITS COME IN LATER
 THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR EACH
 PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL EFFECTIVELY BE THE VALUE OF THE
 BUILDING THAT THE PERMIT FEES WILL BE BASED ON FOR THIS
 PERMIT. THE BUILDING DEPARTMENT DOES NOT WANT TO
 COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT
 COVERED UNDER THE PRIME OR MASTER PERMIT.
  
 3) SUBMIT A SIGNED AND SEALED GEOTECHNICAL REPORT TO
 DETERMINE THE BEARING CAPACITY OF THE SOIL. FBC 1803.6
  
 4) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.. 2017 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
 NOTE: DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 5) SUBMIT THE TESTING REPORTS FOR THE SOUND INSULATION
 FOR THE FLOORING FOR SOUND, FLAME SPREAD AND SMOKE
 DEVELOPED. TYPE III-TYPE V CONSTRUCTION: FBC-B-2014
 720.2 CONCEALED INSTALLATION. INSULATING MATERIALS,
 WHERE CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE
 OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
  
 6) THE ENERGY FORMS THAT WERE SUBMITTED ARE NOT SIGNED
 BY A REGISTERED DESIGN PROFESSIONAL AS REQUIRED BY FBC
 ENERGY CONSERVATION C103.1.1.1.2
  
 7) BLOWER DOOR TESTING IS REQUIRED FOR THE RESIDENTIAL
 UNITS IN THIS BUILDING PER FS 553.908. PLEASE NOTE THIS
 ON THE PLANS.
  
 8) THE NOTE THAT STATES 95% PERMIT SET NEEDS TO BE
 REMOVED FROM THE PLANS. PLANS SUBMITTED FOR PERMIT ARE
 REQUIRED TO BE 100% COMPLETE. FBC 107.2.1
  
 9) SUBMIT SHOP DRAWINGS FOR THE BALCONY AND STAIR
 GUARDS. DELEGATED ENGINEERING. FAC 61G15-30.003
 ENGINEERING DOCUMENT CLASSIFICATION. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 10) SUBMIT ROOF TRUSS DRAWINGS AND LAYOUT PLANS. FBC
 107.3.5
  
 11) FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES
 OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS
 THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT
 THE TIME OF THE APPLICATION AND THAT ARE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED
 PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE
 PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 12) DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 13) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT. FBC 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 14) SPECIFY THE LOCATION OF THE ELEVATOR EQUIPMENT ON
 THE PLANS. FBC 107.2.1
  
 15) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 ELEVATOR. FBC 107.2.1
  
 16) ON SHEET LS-0.1.1 THE TRAVEL DISTANCE FOR THE C3
 UNITS ON THE 2ND FLOOR SHOULD BE TAKEN FROM THE
 BALCONIES AS THEY ARE THE MOST REMOTE POINT IN THE
 UNIT. FBC 1017.3
  
 17) THE BILCO ROOF ACCESS HATCH SPECIFIED AS 30" X 36"
 IS TOO SMALL. FBC 1011.12.2 REQUIRES THE OPENING TO BE
 NOT LESS THAN 16 SQUARE FEET AND A MINIMUM DIMENSION OF
 2 FEET.
  
 18) THE ATTIC ACCESS OPENING SIZES ARE NOT PROVIDED ON
 THE PLANS. FBC 1209.2 REQUIRES ATTIC ACCESS OPENINGS TO
 BE NOT LESS THAN 30" X 36".
  
 19) ON SHEET A-7.1.2 THERE IS A DETAIL B THAT HAS A
 BILCO TYPE S HATCH WITH A FIXED LADDER AND SPECIFIED AS
 A FIFTH FLOOR ELEVATION AND THIS IS A THREE STORY
 BUILDING. PLEASE CLARIFY. FBC 107.2.1
  
 20) ON SHEET LS-0.1.1 THE OVERHEAD GARAGE DOOR AT THE
 EXTERIOR OF THE TRASH ROOM IS SPECIFIED AS A 90 MIN.
 FIRE RATED DOOR. HOWEVER, THIS DOOR IS NOT SPECIFIED AS
 A RATED DOOR IN THE DOOR SCHEDULE ON SHEET A5.1.3.
 PLEASE CORRECT. FBC 107.2.1
  
 21) SHEET A8-8.1.2 HAS DETAIL 12 FOR THE JAMB AT TRASH
 CHUTE DOOR. THE PLANS FOR THIS BUILDING DO NOT APPEAR
 TO SHOW A TRASH CHUTE. PLEASE CORRECT. FBC 107.2.1
  
 22) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-23 Cont ID  
Sent By jpearson Date 2019-08-23 Time 09:41 Rev Time 0.00
Received By jpearson Date 2019-08-23 Time 09:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-16 Cont ID  
Sent By jpearson Date 2019-07-16 Time 08:53 Rev Time 0.00
Received By jpearson Date 2019-07-16 Time 08:53 Sent To  
Notes
2019-07-16 08:14:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
  
 NEW COMMENTS:
  
 7. SMOKE ALARMS ARE SHOWN ON DIFFERENT CIRCUITS.
 PROVIDE CORRECTION. FBC RE R314
 8. SEVERAL SHEETS FROM THE FIRST SUBMISSION THAT STATE
 THEY ARE 95% DOCUMENTS HAVE NOT BEEN REPLACED WITH THIS
 SUBMISSION. PROVIDE A FULL SET FOR REVIEW. WPB FBC
 107.2.1
 9. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC
 210.8(D)
 10. AS THIS IS NOT A 100% SUBMITTAL, FURTHER COMMENTS
 NOT ADDRESSED IN THIS REVIEW MAY BE POSSIBLE UPON NEXT
 REVIEW. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-20 Cont ID  
Sent By jpearson Date 2019-05-20 Time 10:04 Rev Time 0.00
Received By jpearson Date 2019-05-20 Time 07:07 Sent To  
Notes
2019-05-20 07:25:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 2. SHEET E-3.1.0 AND E-5.1.0 SHOW A SERVICE FOR PANEL
 S. SITE LIGHTING AND SERVICE SHOULD BE A SEPARATE
 SUBMITTAL. IF THIS IS ATTACHED TO THE BUILDING, THEN
 THE SERVICE SHOULD BE TIED TO THE GROUNDING ELECTRODE
 SYSTEM OF THAT BUILDING. IT SHOULD ALSO BE LABELED AS
 AN ADDITIONAL SERVICE, OR AN ADDITIONAL MAIN. MAINS
 NEED TO BE GROUPED. ADDITIONAL SERVICES NEED TO BE
 LABELED PROPERLY. PROVIDE CLARIFICATIONS AND
 CORRECTIONS AS NEEDED. WPB FBC 107.2.1; NEC 215.5,
 230.2, 230.72, 250.50
 3.PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE COMPLIANCE WITH NEC 240.87.
 5. NOTE FOR AIC CALCULATION NOTED AS A DEFERRED
 SUBMITTAL. PROVIDE WHEN AVAILABLE. NEC 110.9, 110.10
 6. PROVIDE NOTE FOR LABELING OF UNIT PANELS. THE
 CURRENT PLAN SHOWS THE PANELS NAMED AFTER THE TYPE OF
 UNIT. THE IDENTIFICATION SHALL INCLUDE AN APPROVED
 DEGREE OF DETAIL THAT ALLOWS EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. NEC 408.4
  
 AS THIS IS NOT A 100% SUBMITTAL, FURTHER COMMENTS NOT
 ADDRESSED IN THIS REVIEW MAY BE POSSIBLE UPON NEXT
 REVIEW.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2019-08-21 Cont ID  
Sent By rrossano Date 2019-08-21 Time   Rev Time 0.00
Received By rrossano Date 2019-08-21 Time   Sent To  
Notes
2019-08-21 09:52:33REVIEWED UNDER FORMAL ENGINEERING SUBMITTAL E19010020.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2019-07-26 Cont ID  
Sent By shill Date 2019-07-26 Time 15:57 Rev Time 0.00
Received By shill Date 2019-07-26 Time 15:57 Sent To  
Notes
2019-07-26 15:57:45CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 10:21 Rev Time 0.00
Received By shill Date 2019-04-30 Time 10:21 Sent To  
Notes
2019-04-30 10:21:37CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-07-30 Cont ID  
Sent By pleduc Date 2019-07-30 Time   Rev Time 0.00
Received By pleduc Date 2019-07-30 Time 15:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-13 Cont ID  
Sent By pleduc Date 2019-06-13 Time   Rev Time 0.00
Received By pleduc Date 2019-06-13 Time 15:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-04-29 Cont ID  
Sent By pleduc Date 2019-04-29 Time   Rev Time 0.00
Received By pleduc Date 2019-04-29 Time 10:58 Sent To  
Notes
2019-04-29 11:35:47THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 0.1 - THERE IS NO INDCATION OF INFORMATION
 UNDER SECTION, FIRE ALARM. THERE ARE, HOWEVER,
 INDICATIONS OF FIRE ALARM ON OTHER PLAN SHEETS.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 1A) SHEET LS 0.01 - UNDER THE PROJECT NARRATIVE THERE
 ARE INDICATIONS OF "ENCLOSED PARKING GARAGE AND
 "HIGHEST OCCUPIED FLOOR LEVEL ABOVE FIRE DEPARTMENT
 ACCESS 317'-6", AS WELL AS, OTHER HIGH RISE REFERENCES.
  
 PLEASE REVIEW AND CLARIFY/CORRECT.
  
  
  
  
 2) SHEET C 6.00 - THEREARE INDICATION OF FIRE MAINS AND
 UNDERGROUND FIRE LINES.
  
 ALL UNDERGROUND FIRE LINE AND FIRE MAINS SHALL BE
 INSTALLED AND INSPECTED PER NFPA 24.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS
 PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
  
  
 2A) SHEET C 6.00 - WATER SUPPLY SHALL BE INSTALLED AND
 MAINTAINED PRIOR TO ANY WORK ON A STRUCTURE.
  
 PER NFPA 241, SAFEGUARDING CONSTRUCTION, ALTERATION,
 AND DEMOLITION OPERATIONS
  
 8.7.2 WATER SUPPLY.
 8.7.2.1* AWATER SUPPLY FOR FIRE PROTECTION, EITHER
 TEMPORARY OR
 PERMANENT, SHALL BE MADE AVAILABLE AS SOON AS
 COMBUSTIBLE
 MATERIAL ACCUMULATES.
 8.7.2.2 THERE SHALL BE NO DELAY IN THE INSTALLATION OF
 FIRE PROTECTION
 EQUIPMENT. (SEE A.8.2.5.)
 8.7.2.3* WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE
 TO
 BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND IN
 SERVICE
 PRIOR TO COMMENCING CONSTRUCTION WORK ON ANY STRUCTURE.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS
 PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
  
  
 3) SHEET LS 0.1.1 - THERE ARE INDICATION OF EYE SENSOR
 RELAEASE AT EACH EXIT AS WELL AS PUSH TO EXIT BUTTONS.
  
 ALL EXITING EQUIPMENT AND DEVICES SHALL COMPLY WITH
 NFPA 101, CH 7 MEANS OF EGRESS AND SHALL BE INSTALLED
 AND INSPECTED UNDER SEPARATE SHOP DRAWINGS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS
 PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
  
  
  
 4) SHEET E 2.1.0 - THERE INDICATIONS OF FIRE ALARM
 DEVICES AND EQUIPMENT.
  
 ALL FIRE ALARM EQUIPMENT AND DEVICES SHALL BE INSTALLED
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS
 PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
  
  
  
 5) SHEET E 2.1.1 - THERE IS AN INDICATION OF A FACP
 WITHIN THE LOBBY; HOWEVER, THERE IN NO INDICATION OF A
 SMOKE DETECTOR OVER IT.
  
 PER NFPA 72
  
 10.4.4* IN AREAS THAT ARE NOT CONTINUOUSLY OCCUPIED,
 AUTOMATIC
 SMOKE DETECTION SHALL BE PROVIDED AT THE LOCATION OF
 EACH FIRE ALARM CONTROL UNIT(S), NOTIFICATION APPLIANCE
 CIRCUIT
 POWER EXTENDERS, AND SUPERVISING STATION TRANSMITTING
 EQUIPMENT
 TO PROVIDE NOTIFICATION OF FIRE AT THAT LOCATION.
 EXCEPTION: WHERE AMBIENT CONDITIONS PROHIBIT
 INSTALLATION OF AUTOMATIC
 SMOKE DETECTION, AUTOMATIC HEAT DETECTION SHALL BE
 PERMITTED.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 6) SHEET A 2.1.1 - THERE IS GATE, G8, INDICATED WITHIN
 AN EXIT PATH/DISCHARGE. THIS GATE MUST PROVIDE FREE
 EXIT.
  
 THERE IS NO EXIT HARDWARE PROVIDED/INDICATED FOR THIS
 GATE. ANY EXIT HARDWARE SHALL COMPLY WITH NFPA 101, CH
 7, MEANS OF EGRESS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS
 PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-26 Cont ID  
Sent By gjohnson Date 2019-08-26 Time 12:55 Rev Time 0.00
Received By gjohnson Date 2019-07-29 Time 10:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-26 Cont ID  
Sent By shill Date 2019-07-26 Time 15:58 Rev Time 0.00
Received By shill Date 2019-06-10 Time 08:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-03 Cont ID  
Sent By rmcdouga Date 2019-06-03 Time 19:17 Rev Time 0.00
Received By rmcdouga Date 2019-04-10 Time 16:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-08-06 Cont ID  
Sent By lmarchan Date 2019-08-06 Time 10:20 Rev Time 0.00
Received By lmarchan Date 2019-06-19 Time 16:33 Sent To  
Notes
2019-08-06 07:51:47RECEIPT - MU-2019-0731-329 - $294,071.99 PAID
2019-06-19 16:33:496/19/19 SENT TO IMPACT FOR REVIEW PER APPLICANT. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-05-23 Cont ID  
Sent By rmcdouga Date 2019-05-23 Time 17:26 Rev Time 0.00
Received By rmcdouga Date 2019-05-23 Time 17:26 Sent To  
Notes
2019-05-23 17:26:08PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-08-15 Cont ID  
Sent By pvalenti Date 2019-08-15 Time 11:28 Rev Time 0.00
Received By ccole Date 2019-08-15 Time 11:28 Sent To  
Notes
2019-08-15 11:29:23MECHANICAL REVIEW
  
 APPROVED PER CHRIS COLE (REMOTELY)

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-07-10 Cont ID  
Sent By ccole Date 2019-07-10 Time 15:09 Rev Time 0.00
Received By ccole Date 2019-07-10 Time 14:09 Sent To  
Notes
2019-07-10 16:11:322ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19040463
 7/10/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGYGAUGE TOTAL BUILDING PERFORMANCE
 COMPLIANCE SUBMITTAL DOES NOT PROVIDE ANY COMPLIANCE
 DATA FOR THE RETAIL PORTIONS OF THE BUILDING SHOWN ON
 THE GROUND FLOOR, INCLUDING THE CONSTRUCTS AND SQUARE
 FOOTAGE OF THOSE PORTIONS- SECTIONS C407.1 & C407.2 FBC
 EC. A) THE REQUESTED MINIMUM VENTILATION FOR THE RETAIL
 SPACES AND CORRIDOR HAVE NOT BEEN PROVIDED IN THE TABLE
 ON SHEET M-5.1.1.
  
 2) SHEETS M-2.1.1 & M-5.1.1: COMMENT #3 FROM THE 1ST
 REVIEW HAS NOT BEEN COMPLETELY ADDRESSED. ON SHEET
 M-2.1.1. PLEASE PLACE A NOTE TO INDICAET THAT THE
 GARAGE EXHAUST OUTLETS ARE A MINIMUM 3' AWAY FROM
 OPERABLE OPENINGS INTO THE BUILDING- SECTION 501.3.1
 (3) FBC M. M-5.1.1: THE GARAGES HAVE BEEN CLASSIFIED AS
 PARKING GARAGES ON SHEET LS-0.1.0 WHICH REQUIRES THE
 EXHAUST SYSTEMS TO EITHER RUN CONTINOUSLY (SECTION
 502.13 FBC M), OR OPERATE INTERMITTENTLY BY MEANS OF
 CARBON MONOXIDE AND NITROGEN DIOXIDE SENSORS- SECTION
 404.1 FBC M. PLEASE NOTE THAT AUTOMATIC OPERATION OF
 THE SYSTEM SHALL NOT REDUCE THE VENTILATION AIRFLOW
 RATE BELOW 0.05 CFM PER SQ. FT.- SECTION 404.2 FBC M.
  
 3) SHEET M-5.1.1: COMMENT #4 FROM THE 1ST REVIEW COPIED
 BELOW STILL EXISTS.
 403.3.2.1 OUTDOOR AIR FOR DWELLING UNITS.
 AN OUTDOOR AIR VENTILATION SYSTEM CONSISTING OF A
 MECHANICAL EXHAUST SYSTEM, SUPPLY SYSTEM OR COMBINATION
 THEREOF SHALL BE INSTALLED FOR EACH DWELLING UNIT.
 LOCAL EXHAUST OR SUPPLY SYSTEMS, INCLUDING OUTDOOR AIR
 DUCTS CONNECTED TO THE RETURN SIDE OF AN AIR HANDLER,
 ARE PERMITTED TO SERVE AS SUCH A SYSTEM. THE OUTDOOR
 AIR VENTILATION SYSTEM SHALL BE DESIGNED TO PROVIDE THE
 REQUIRED RATE OF OUTDOOR AIR CONTINUOUSLY DURING THE
 PERIOD THAT THE BUILDING IS OCCUPIED. THE MINIMUM
 CONTINUOUS OUTDOOR AIRFLOW RATE SHALL BE DETERMINED IN
 ACCORDANCE WITH EQUATION 4-9.
  
 (EQUATION 4-9)
 WHERE:
 QOA = OUTDOOR AIRFLOW RATE, CFM
 AFLOOR = FLOOR AREA, FT2
 NBR = NUMBER OF BEDROOMS; NOT TO BE LESS THAN ONE
 EXCEPTION: THE OUTDOOR AIR VENTILATION SYSTEM IS NOT
 REQUIRED TO OPERATE CONTINUOUSLY WHERE THE SYSTEM HAS
 CONTROLS THAT ENABLE OPERATION
 FOR NOT LESS THAN 1 HOUR OF EACH 4-HOUR PERIOD. THE
 AVERAGE OUTDOOR AIR FLOW RATE OVER THE 4-HOUR PERIOD
 SHALL BE NOT LESS THAN THAT PRESCRIBED BY EQUATION 4-9.
  
 4) M-6.1.2: COMMENT #8 FROM THE 1ST REVIEW HAS NOT
 ADDRESSED. PLEASE INDICATE THE TYPE AND SIZE OF
 CONDENSATE PIPING TO BE INSTALLED IN THE PLENUM RATED
 AC CLOSETS- SECTIONS 307.2.1 & 602.2.1 FBC M.
  
 5) M-4.1.3: THE 16X6 RETURN FROM THE MASTER SUITE IS
 UNDERSIZED PER SECTION 601.6(3) FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-07 Cont ID  
Sent By ccole Date 2019-05-07 Time 16:21 Rev Time 0.00
Received By ccole Date 2019-05-07 Time 14:07 Sent To  
Notes
2019-05-07 17:02:591ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040463
 5/7/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTIONS 202, C101.4.1, C101.5, R101.4.1
 AND R101.5 FBC EC. THE RESIDENTIAL PORTION OF THE
 PROPOSED PROJECT SHALL COMPLY WITH THE FLORIDA ENERGY
 CODE RESIDENTIAL PROVISIONS, AND THE COMMERCIAL PORTION
 SHALL COMPLY WITH THE FLORIDA ENERGY CODE COMMERCIAL
 PROVISIONS. NEITHER THE SUBMITTED ENERGYGAUGE SUMMIT
 FLA/COM REPORT OR THE TRACE 700 HEAT LOAD CALCULATION
 SOFTWARE CAN BE USED TO SHOW COMPLIANCE FOR THE
 RESIDENTIAL PORTION. PLEASE SEE SECTION R101.5.1 FOR
 ACCEPTABLE RESIDENTIAL ENERGY COMPLIANCE SUBMITTAL
 MATERIALS, AND SECTION R403.7.1 WHICH REQUIRES SYSTEM
 SIZINGS TO BE PERFORMED IN ACCORDANCE WITH ACCA MANUAL
 S AND J. PLEASE NOTE THAT ALL CALUCALTIONS PERFORMED BY
 THE ENGINEER SHALL BE ELECTRONICALLY SIGNED AND SEALED-
 SECTION 61G15-23.005 FAC.
  
 2) BASED ON COMMENT #1, THE COMMERCIAL PORTION OF THE
 BUILDING MUST BE SEPARATED FROM THE RESIDENTIAL PORTION
 AND SEPARATE ENERGY COMPLIANCE AND HEAT LOAD
 CALCULCATIONS IN ACCORDANCE WITH THE FLORIDA ENERGY
 CODE COMMERCIAL PROVISONS SHALL BE SUBMITTED.
  
 3) SHEET M2.1.1: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE GARAGES, AND THE SEQUENCE OF
 OPERATION FOR THE FANS- SEE TABLE 403.3.1.1 AND 501.4
 FBC M. A) SHOW THE REQUIRED CLEARANCE DISTANCES FOR THE
 EXHAUST OUTLET TO OPERABLE AND MECHANICAL AIR INTAKES,
 AND FROM GRADE- SECTION 501.3.1 FBC M.
  
 4) M5.1.1: PLEASE CORRECT THE FBC MINIMUM VENTILATION
 CALCULATIONS AND REMOVE OR CORRECT THE NOTES SPECIFYING
 RATES BASED ON THE TABLES IN THE FBC R, THE FBC R CODE
 IS APPLICABLE ONLY FOR SINGLE FAMILY HOMES, DUPLEXES,
 AND TOWNHOUSES. REFER TO SECTION 403.3.2.1 FBC M COPIED
 BELOW, AND INDICATE COMPLIANCE:
  
 403.3.2.1 OUTDOOR AIR FOR DWELLING UNITS.
 AN OUTDOOR AIR VENTILATION SYSTEM CONSISTING OF A
 MECHANICAL EXHAUST SYSTEM, SUPPLY SYSTEM OR COMBINATION
 THEREOF SHALL BE INSTALLED FOR EACH DWELLING UNIT.
 LOCAL EXHAUST OR SUPPLY SYSTEMS, INCLUDING OUTDOOR AIR
 DUCTS CONNECTED TO THE RETURN SIDE OF AN AIR HANDLER,
 ARE PERMITTED TO SERVE AS SUCH A SYSTEM. THE OUTDOOR
 AIR VENTILATION SYSTEM SHALL BE DESIGNED TO PROVIDE THE
 REQUIRED RATE OF OUTDOOR AIR CONTINUOUSLY DURING THE
 PERIOD THAT THE BUILDING IS OCCUPIED. THE MINIMUM
 CONTINUOUS OUTDOOR AIRFLOW RATE SHALL BE DETERMINED IN
 ACCORDANCE WITH EQUATION 4-9.
  
 (EQUATION 4-9)
 WHERE:
  
 QOA = OUTDOOR AIRFLOW RATE, CFM
  
 AFLOOR = FLOOR AREA, FT2
  
 NBR = NUMBER OF BEDROOMS; NOT TO BE LESS THAN ONE
  
 EXCEPTION: THE OUTDOOR AIR VENTILATION SYSTEM IS NOT
 REQUIRED TO OPERATE CONTINUOUSLY WHERE THE SYSTEM HAS
 CONTROLS THAT ENABLE OPERATION
 FOR NOT LESS THAN 1 HOUR OF EACH 4-HOUR PERIOD. THE
 AVERAGE OUTDOOR AIR FLOW RATE OVER THE 4-HOUR PERIOD
 SHALL BE NOT LESS THAN THAT PRESCRIBED BY EQUATION 4-9.
  
 5) SHEETS M4.1.1, 4.1.2, AND 4.1.3: LOCAL EXHAUST
 SYSTEMS ARE REQUIRED FOR THE KITCHENS AT A RATE OF 100
 CFMS INTERMITTENT OR 25 CFMS CONTINUOUS. INDICATE HOW
 COMPLIANCE WILL BE MET.
  
 6) A4.1.5, M4.1.1, 4.1.2, AND 4.1.3: THE CITY OF WPB
 BUILDING DEPARTMENT REQUIRES EITHER THE DESIGN
 PROFESSIONAL OF RECORD OR THE INTUMESCENT PAINT
 MANUFACTURER TO CERTIFY THE APPLICATION OF THE PAINT ON
 THE INTERIOR SIDES OF THE AC CLOSET DOORS- SECTION
 107.2.1 WPB. FINAL MECHANICAL APPROVAL IS CONTINGENT ON
 RECEIPT OF A SIGNED AND SEALED LETTER OR REPORT BY THE
 DESIGN PROFESSIONAL OF RECORD, OR A MANUFACTURER'S
 CERTIFICATION LETTER WITH AN APPROVAL STAMP BY THE
 DESIGN PROFESSIONAL. PLEASE PLACE NOTES ON THE PLANS
 ACCORDINGLY.
  
 7) M4.1.1, 4.1.2, AND 4.1.3: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE CLOTHES DRYERS- SECTION 504.1
 FBC M.
  
 8) M6.1.2- AC CLOSET DETAIL: INDICATE THEY TYPE AND
 SIZE OF CONDENSATE PIPING FOR THE AIR HANDLER- SECTIONS
 307.2.1 AND 602.2.1 FBC M.
  
 9) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S
 ARE REQUIRED FOR THE ROOFTOP CONDENSER STANDS AND
 EXHAUST AND O/A INLET LOUVERS. THESE MAY BE SUBMITTED
 NOW WITH THE ENGINEER OF RECORD'S SHOP DRAWING STAMP OF
 APPROVAL, OR MAY BE DEFERRED SUBMITTALS- SEE SECTION
 107.3.4.1 WPB. PLEASE NOTE THAT THE O/A LOUVERS SHALL
 BE AMCA 550 RATED PER SECTION 401.5 FBC M.
  
 10) CLARIFY IF THERE WILL BE AN ELEVATOR MACHINERY OR
 CONTROL ROOM AND SHOW THE LOCATION IF APPLICABLE-
 SECTION 3005.1. PLEASE NOTE THAT ELEVATOR MACHINE OR
 CONTROL ROOMS REQUIRE INDEPENDENT VENTILATION SYSTEMS-
 SECTION 3005.2. FBC B.
  
 11) CLARIFY IF THE HOISTWAY WILL BE VENTED AND PROVIDE
 DETAILS- LOCATION OF VENT, TYPE AND SIZE OF VENT AND
 DAMPER ETC . PLEASE NOTE THAT PLUMBING AND MECHANICAL
 SYSTEMS SHALL NOT BE LOCATED IN THE HOISTWAY ENCLOSURE-
 SECTION 3002.9 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-08-26 Cont ID  
Sent By gjohnson Date 2019-08-26 Time 12:51 Rev Time 0.00
Received By gjohnson Date 2019-08-23 Time 14:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-07-09 Cont ID  
Sent By gjohnson Date 2019-07-09 Time 18:00 Rev Time 0.00
Received By gjohnson Date 2019-07-02 Time 08:09 Sent To  
Notes
2019-07-09 18:00:272ND REVIEW: 19040464
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH
  
 3) SHT. A-10.4.1, A-10.4.2 AND A-10.4.3 THE LEGEND
 REFERENCED IN THE RESPONSE LETTER DOES NOT SHOW THE
 REQUIRED 56" X48" CLEAR FLOOR SPACE FOR THE TOILET
 PLEASE ADD TO LEGEND PER FHA DESIGN MANUAL REQUIREMENT
 #7
  
 8) PLEASE PROVIDE MANUFACTURE SPECIFICATION FOR SUB
 METER IT SHALL SHOW THAT METER IS RATED FOR AIR PLENUM
 NON COMBUSTIBLE MATERIAL.
  
 NEW COMMENTS;
  
 1. SEPARATE PERMIT REQUIRED FOR ALL BACK FLOWS PLACE
 NOTE ON PLAN.PER WPB UTILITIES DEPARTMENT
  
 2. PROVIDE ROOF DRAIN SIZING CALCULATIONS. PER FBC PL
 1106.2
  
 PLANS MARKED AS 75% COMPLETE PROVIDE 100% COMPLETE
 PLANS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-07 Cont ID  
Sent By gjohnson Date 2019-05-07 Time 17:38 Rev Time 0.00
Received By gjohnson Date 2019-05-07 Time 08:35 Sent To  
Notes
2019-05-07 17:43:55 
 1ST REVIEW: 19040463
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THIS PROJECT SHALL COMPLY WITH FBC ACC 233.3.1 AND
  
 233.3.1.1 RESIDENTIAL DWELLING UNITS WITH MOBILITY
 FEATURES. IN FACILITIES WITH RESIDENTIAL DWELLING
 UNITS, AT LEAST 5 PERCENT, BUT NO FEWER THAN ONE UNIT,
 OF THE TOTAL NUMBER OF RESIDENTIAL DWELLING UNITS SHALL
 PROVIDE MOBILITY FEATURES COMPLYING WITH 809.2 THROUGH
 809.4 AND SHALL BE ON AN ACCESSIBLE ROUTE AS REQUIRED
 BY 206.
  
 233.3.1.2 RESIDENTIAL DWELLING UNITS WITH COMMUNICATION
 FEATURES. IN FACILITIES WITH RESIDENTIAL DWELLING
 UNITS, AT LEAST 2 PERCENT, BUT NO FEWER THAN ONE UNIT,
 OF THE TOTAL NUMBER OF RESIDENTIAL DWELLING UNITS SHALL
 PROVIDE COMMUNICATION FEATURES COMPLYING WITH 809.5.
 PLEASE CLEARLY INDICATE WHICH UNITS COMPLY. PER WPB
 AMEND TO FBC 107.2
  
 2. THE LAVATORY'S IN THE B BATHROOMS SHALL BE MAX 34"
 OFF FINISH FLOOR. PER FHA DESIGN MANUAL REQ.. #7
  
 3. SHT. A-10.4.1, A-10.1.1 AND A-10.1.2 SHOW DIMENSIONS
 ON THE CLEAR FLOOR SPACE FOR THE TOILET, LAVATORY,
 SHOWER AND KITCHEN PER FHA DESIGN MANUAL REQ. #7
  
 4.SHT. P-2.0.0 IN THE MIDDLE OF THE PAGE THERE IS A
 NOTE UNDER SEPARATE PERMIT WHAT IS THIS NOTE FOR PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. A-10.1.1 UNIT A1-B DOES NOT SHOW DESIGN SPEC
 FOR THE BATHROOM PLEASE CLARIFY. PER FHA DESIGN MANUAL
 REQ. #7
  
 6. SHT. P-2.4.6 OVER FLOW DRAIN ARE REQUIRED ON ROOFS
 THE CAN COLLECT WATER IF THE MAIN DRAIN FAILS PLEASE
 SHOW OVERFLOW DRAIN LOCATIONS. PER FBC PL 1108.1
  
 7. PLEASE PROVIDE A PAN DRAIN RISER. PER WPB AMEND TO
 FBC 107.2.1
  
 8. PROVIDE MANUFACTURE SPECIFICATIONS FOR SUB METER.
 PER WPB AMEND TO FBC 107.2.1
  
 9. SHOW SIZE AND MANUFACTURE OF THE GREASE INTERCEPTOR
 AND PIPING DETAIL. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2019-08-26 Cont ID  
Sent By gjohnson Date 2019-08-26 Time 12:37 Rev Time 0.00
Received By gjohnson Date 2019-08-26 Time 12:36 Sent To  
Notes
2019-10-21 11:23:01GREASE INTERCEPTORS IN THE TRASH ROOMS APPROVED PER
 PLAN.
  
 GREASE INTERCEPTORS FOR FUTURE USE LOCATED OUTSIDE THE
 BUILDING SHALL COMPLY WITH PROVISO BEFORE BEING ISSUED.
  
  
  
2019-08-26 12:51:37PROVISO 19040464
  
  
  
 PLUMBING COMMENTS: COMPLY BEFORE PERMIT IS ISSUED
  
 1. PROVIDE SITE PLAN SHOWING ALL GREASE INTERCEPTORS.
 PER WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE PIPING DETAIL FOR THE GREASE INTERCEPTOR.
 PER WPB AMEND TO FBC 107.2
  
 3. TEST PORT REQUIRED ON OUTLET SIDE OF INTERCEPTOR A
 TWOWAY CLEANOUT CAN BE USED OR PREMANUFACTURED CAN BE
 USED. PER WPB UTILITIES.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2019-07-17 Cont ID  
Sent By rmcdouga Date 2019-07-17 Time 18:30 Rev Time 0.00
Received By rmcdouga Date 2019-07-17 Time 18:30 Sent To  
Notes
2019-07-17 18:31:16ROOFING SUBMITTALS HAVE BEEN DEFERRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-06-03 Cont ID  
Sent By rmcdouga Date 2019-06-03 Time 07:02 Rev Time 0.00
Received By rmcdouga Date 2019-06-03 Time 07:02 Sent To  
Notes
2019-06-03 07:03:35NO PRODUCT APPROVALS FOR ROOFING WERE SUBMITTED. PLANS
 SHOW CONCRETE S-TILE ON THE SLOPED ROOF AND TPO ON THE
 FLAT ROOF.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-08-22 Cont ID  
Sent By rmcdouga Date 2019-08-22 Time 07:41 Rev Time 0.00
Received By rmcdouga Date 2019-08-22 Time 07:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-07-26 Cont ID  
Sent By shill Date 2019-07-26 Time 15:58 Rev Time 0.00
Received By shill Date 2019-07-26 Time 15:58 Sent To  
Notes
2019-07-26 15:58:17SEE PREVIOUS SIGNATURE REVIEW
  
2019-07-16 07:10:01ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SELF-CERTIFICATION IS NOT
 ACCEPTABLE FOR ENGINEERS. ADDITIONALLY, THE DIGITAL
 SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED AND
 SEALED" AS PER FAC 61G15-23.004. PROVIDE CORRECTION.
 WPB FBC 107.1; FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 10:20 Rev Time 0.00
Received By shill Date 2019-04-30 Time 10:20 Sent To  
Notes
2019-04-30 10:21:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLANS ARE NOTED AS 95%. 100% DOCUMENTS ARE REQUIRED FOR
 PERMIT ISSUANCE.
  
 1. THE ENERGY CALCS ARE NOT DIGITALLY SIGNED AND
 SEALED, FS471, 481.
  
 2. SURVEY, ARCHITECTURAL PAGES OK (SIGNATURES, TITLE
 BLOCK).
  
 3. CIVIL PAGES LACK THE STATEMENT REQUIRED BY
 FAC61G15-23.004 (REQUIRED FOR DIGITALLY SIGNED
 DOCUMENTS). PLEASE ADDRESS, BUT ONLY RESUBMIT PAGES
 WHICH CHANGE DUE TO CODE RELATED COMMENTS.
  
 4. PLEASE SUBMIT LANDSCAPE PAGES WITH A SEPARATE
 LANDSCAPE PERMIT APPLICATION.
  
 5. STRUCTURAL PAGES PREPARED BY EDUARDO GONZALEZ ARE
 95%. 100% PERMIT DOCUMENTS ARE REQUIRED FOR PERMIT
 ISSUANCE.
  
 THE DIGITAL SIGNATURE (OR PLAN) LACKS THE STATEMENT
 REQUIRED BY FAC61G15-23.004, PLEASE INCLUDE ON ALL
 PAGES.
  
 6. THE FMEP PAGES LACK THE STATEMENT REQUIRED BY
 FAC61G15-23.004, ALSO LACK A COMPLETE TITLE BLOCK (CA
 AND NAME PROVIDED, NO ADDRESS), LACKS A SEAL. EITHER
 THE SIGNATURE IS TO STATE "SIGNED AND SEALED" OR THE
 IMAGE OF A SEAL IS TO BE ON EACH PAGE.
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-08-22 Cont ID  
Sent By jroach Date 2019-08-22 Time 11:41 Rev Time 0.00
Received By jroach Date 2019-08-22 Time 11:41 Sent To  
Notes
2019-08-22 11:42:45ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 08.22.2019
 PERMIT NO.: 19040463
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THE SCOPE OF THIS PERMIT REVIEW IS LIMITED TO THE
 BUILDING ONLY! SEPARATE PERMITS REQUIRED FOR
 SURROUNDING SITE WORK, HARDSCAPE, FENCING, PARKING,
 LANDSCAPING, SIGNAGE, ETC.
  
 2. THE PROJECT IS SUBJECT TO ALL DEVELOPMENT ORDER
 CONDITIONS, AS OUTLINED IN RESOLUTION NO. 227-18, AS
 APPROVED BY THE CITY COMMISSION ON SEPTEMBER 24, 2018,
 AND AS MAY BE AMENDED.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-07-18 Cont ID  
Sent By jroach Date 2019-07-18 Time 15:04 Rev Time 0.00
Received By jroach Date 2019-07-18 Time 15:04 Sent To  
Notes
2019-07-18 15:04:28ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.17.2019
 PERMIT NO.: 19040463, 19040464, 19040465
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ALL LANDSCAPE PLANS SHALL BE REMOVED FROM THE
 BUILDING PERMIT.
  
 2. THE BIKE PARKING SOUTH OF BUILDING #1 NEEDS TO BE
 CONFIGURED SUCH THAT THERE ARE THREE (3) BIKE RACKS,
 WITH SUFFICIENT SPACE TO ACCOMMODATE A SKY BIKE (BIKE
 SHARE) STATION WITH AT LEAST FOUR (4) BIKES.
  
 3. VARIOUS PLANS (SITE, UTILITY, HARDSCAPE, LANDSCAPE,
 ELEVATIONS, ETC.) DO NOT MATCH THE LATEST SUBMITTAL
 (05.10.2019) FOR THE REVISED SITE PLAN APPROVAL. THE
 LATEST PLANS NEED TO BE SUBMITTED FOR THE SITE PLAN
 AMENDMENT, AND ONCE APPROVED, ALL PERMITS WILL NEED TO
 MATCH THE APPROVED AMENDMENT.
  
 PURSUANT TO THE REQUIREMENTS OF RESOLUTION NO. 227-18,
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY:
  
 A. THE DEVELOPER SHALL IMPROVE HAMPTON ROAD BETWEEN
 SOUTH DIXIE HIGHWAY AND THE FEC RAILROAD, AS SPECIFIED
 IN RESOLUTION NO. 227-18.
  
 B. THE PROPERTY SHALL BE RE-PLATTED IN ACCORDANCE WITH
 ALL APPLICABLE STATUTES, REGULATIONS, AND THE CITY?S
 POLICIES AND PROCEDURES.
  
 C. THE APPLICANT SHALL EXECUTE AND RECORD, IN A FORM
 ACCEPTABLE TO THE CITY AND TO THE APPLICANT, A MUTUAL
 AND RECIPROCAL CROSS ACCESS EASEMENT AT THE NORTH
 PROPERTY LINE FOR THE BENEFIT OF BOTH THE SUBJECT
 PROPERTY AND THE ADJACENT PROPERTY TO THE NORTH.
  
 D. A MAINTENANCE AGREEMENT WITH THE CITY SHALL BE
 EXECUTED FOR THE MAINTENANCE OF THE ROAD RIGHT OF WAY
 LANDSCAPING, TREE GRATES AND IRRIGATION ADJACENT TO THE
 PROPERTY. THE DEVELOPER, ITS SUCCESSORS AND ASSIGNS
 SHALL BE RESPONSIBLE FOR MAINTENANCE OF ALL SUCH
 IMPROVEMENTS.
  
 E. ALL UTILITY ELEMENTS (I.E. BACKFLOW PREVENTERS,
 ETC.) SHALL BE SCREENED WITH LANDSCAPING TO THE MAXIMUM
 EXTENT ALLOWED BY THE CONTROLLING UTILITY AGENCY.
  
 IMPORTANT INFORMATION TO BE AWARE OF:
  
 I. ANY DAMAGE TO EXISTING UTILITIES RESULTING FROM THE
 DEVELOPER?S CONSTRUCTION ACTIVITIES SHALL BE REPAIRED,
 AT THE DEVELOPER?S EXPENSE.
  
 II. ANY REQUIRED EASEMENTS (I.E. DRAINAGE, UTILITIES,
 PUBLIC ACCESS, ETC.) SHALL BE PROVIDED VIA PLAT OR
 SEPARATE LEGAL INSTRUMENT.
  
 III. THE DEVELOPER, ITS SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES, TREE GRATES, AND RIGHT OF WAY LANDSCAPING
 AND IRRIGATION ASSOCIATED WITH THE APPROVED SITE PLAN.
 ALL PERMITS SHALL BE OBTAINED PRIOR TO COMMENCEMENT OF
 CONSTRUCTION OF SUCH IMPROVEMENTS.
  
 IV. THE DEVELOPER, ITS SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE REMOVAL AND/OR RELOCATION OF ALL
 STREET LIGHTS/POLES NECESSITATED BY THE PROPOSED
 DEVELOPMENT. ALL NEW STREET LIGHTING SHALL CONFORM TO
 THE MINIMUM REQUIREMENTS AND SHALL BE REVIEWED AND
 PERMITTED BY ALL APPLICABLE GOVERNING AGENCIES,
 INCLUDING THE CITY?S ENGINEERING SERVICES DEPARTMENT.
  
 V. FINAL APPROVAL OF THE ENGINEERING DESIGN SHALL BE
 BASED UPON SUBMITTAL OF A SEPARATE PERMIT APPLICATION
 TO, AND REVIEW BY, THE CITY?S PUBLIC WORKS AND
 ENGINEERING DEPARTMENTS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-05-15 Cont ID  
Sent By jroach Date 2019-05-15 Time 11:42 Rev Time 0.00
Received By jroach Date 2019-05-15 Time 11:42 Sent To  
Notes
2019-05-15 11:42:36ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.14.2019
 PERMIT NO.: 19040463
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. WHAT PERMIT IS SITE WORK BEING PERFORMED UNDER?
  
 2. WHAT PERMIT IS SITE LIGHTING BEING PERFORMED UNDER?
 A PHOTOMETRIC PLAN SHALL BE PROVIDED SHOWING THAT
 PHOTOMETRIC LEVELS DO NOT EXCEED 1.0 FOOTCANDLES WHEN
 MEASURED AT THE PROPERTY LINE.
  
 3. ALL WORK WITHIN THE SOUTH DIXIE HIGHWAY RIGHT-OF-WAY
 SHALL BE SUBJECT TO THE REVIEW AND PERMITTING BY THE
 FLORIDA DEPARTMENT OF TRANSPORTATION (FDOT). PLEASE
 PROVIDE A COPY OF SUCH PERMIT.
  
 4. ALL WORK WITHIN THE HAMPTON ROAD RIGHT-OF-WAY SHALL
 BE PERMITTED THROUGH THE CITY?S ENGINEERING SERVICES
 DEPARTMENT.
  
 5. SEPARATE LANDSCAPE PERMIT REQUIRED. ALL LANDSCAPE
 PLANS SHALL BE REMOVED FROM THE BUILDING PERMIT
 SUBMITTAL AND SUBMITTED UNDER A SEPARATE LANDSCAPE
 PERMIT APPLICATION. ALL LANDSCAPE PLANS SHALL MATCH
 THAT WHICH WAS SUBMITTED FOR THE REVISED SITE PLAN
 APPROVAL.
  
 6. THE SITE PLAN SHALL MATCH THAT WHICH WAS SUBMITTED
 FOR THE REVISED SITE PLAN APPROVAL.
  
 7. BIKE PARKING DETAIL SHALL SPECIFY THE DIMENSIONS
 BETWEEN RACKS, BETWEEN THE RACK AND THE EDGE OF
 PAVEMENT, ETC. DIMENSIONS SHALL MEET THE CITY?S MINIMUM
 SPACING REQUIREMENTS.
  
 8. THE LOCATIONS OF VARIOUS UTILITIES DO NOT MATCH THAT
 WHICH WAS PROVIDED AS PART OF THE SITE PLAN AMENDMENT
 APPLICATION. THE UTILITY LOCATIONS APPEAR TO CONFLICT
 WITH VARIOUS LANDSCAPE ELEMENTS.
  
 9. THE BIKE PARKING SOUTH OF BUILDING #1 NEEDS TO BE
 CONFIGURED SUCH THAT THERE ARE THREE (3) BIKE RACKS,
 WITH SUFFICIENT SPACE TO ACCOMMODATE A SKY BIKE (BIKE
 SHARE) STATION WITH AT LEAST FOUR (4) BIKES.
  
 10. VARIOUS PLANS (HARDSCAPE, LANDSCAPE, ETC.) DO NOT
 MATCH THAT WHICH WAS SUBMITTED FOR THE REVISED SITE
 PLAN APPROVAL; SPECIFICALLY, THE CONFIGURATION ALONG
 THE WEST FA?ADE OF BUILDINGS #1, #2 AND #3. ENSURE THAT
 ALL PLANS MATCH THAT WHICH WAS SUBMITTED FOR THE SITE
 PLAN AMENDMENT.
  
 11. SPECIFICATIONS FOR THE ARTIFICIAL TURF SHALL BE
 PROVIDED SHOWING COMPLIANCE WITH SEC. 94-451(E) OF THE
 CITY?S ZLDRS.
  
 12. LOCATION OF THE FENCING SHOWN IN THE NORTHEAST
 CORNER OF THE PROPERTY DOES NOT MATCH THAT WHICH WAS
 SUBMITTED FOR THE REVISED SITE PLAN APPROVAL.
  
 13. WHY WERE HARDSCAPE PLANS NOT PROVIDED FOR THE
 NORTHWEST QUADRANT OF THE SITE?
  
 14. IN BUILDING 3, THE MAINTENANCE ROOM WAS REMOVED AND
 BECAME THE ?WE WORK SPACE??WITH THE FORMER WWS BEING
 CONVERTED INTO ADDITIONAL RETAIL. IMPACT ON PARKING
 CALCULATIONS? IMPACT ON TRAFFIC CONCURRENCY?
  
 15. ELECTRIC VEHICLE CHARGING STATION IS SHOWN IN THE
 MIDDLE OF THE SIDEWALK.
  
 16. LOCATION OF FENCING IN THE NORTHEAST CORNER OF THE
 PROPERTY DOES NOT MATCH BETWEEN THE SITE PLAN,
 HARDSCAPE PLAN, AND LANDSCAPE PLAN.
  
 17. NOT ALL FIRE HYDRANTS SHOWN ON THE LANDSCAPE PLAN
 ARE REFLECTED ON THE SITE PLAN.
  
 18. BUILDING ELEVATIONS DO NOT MATCH THAT WHICH WAS
 SUBMITTED FOR THE REVISED SITE PLAN APPROVAL. ALL PLANS
 NEED TO BE CONSISTENT.
  
 PURSUANT TO THE REQUIREMENTS OF RESOLUTION NO. 227-18,
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY:
  
 A. THE DEVELOPER SHALL IMPROVE HAMPTON ROAD BETWEEN
 SOUTH DIXIE HIGHWAY AND THE FEC RAILROAD, AS SPECIFIED
 IN RESOLUTION NO. 227-18.
  
 B. THE PROPERTY SHALL BE RE-PLATTED IN ACCORDANCE WITH
 ALL APPLICABLE STATUTES, REGULATIONS, AND THE CITY?S
 POLICIES AND PROCEDURES.
  
 C. THE APPLICANT SHALL EXECUTE AND RECORD, IN A FORM
 ACCEPTABLE TO THE CITY AND TO THE APPLICANT, A MUTUAL
 AND RECIPROCAL CROSS ACCESS EASEMENT AT THE NORTH
 PROPERTY LINE FOR THE BENEFIT OF BOTH THE SUBJECT
 PROPERTY AND THE ADJACENT PROPERTY TO THE NORTH.
  
 D. A MAINTENANCE AGREEMENT WITH THE CITY SHALL BE
 EXECUTED FOR THE MAINTENANCE OF THE ROAD RIGHT OF WAY
 LANDSCAPING, TREE GRATES AND IRRIGATION ADJACENT TO THE
 PROPERTY. THE DEVELOPER, ITS SUCCESSORS AND ASSIGNS
 SHALL BE RESPONSIBLE FOR MAINTENANCE OF ALL SUCH
 IMPROVEMENTS.
  
 E. ALL UTILITY ELEMENTS (I.E. BACKFLOW PREVENTERS,
 ETC.) SHALL BE SCREENED WITH LANDSCAPING TO THE MAXIMUM
 EXTENT ALLOWED BY THE CONTROLLING UTILITY AGENCY.
  
 IMPORTANT INFORMATION TO BE AWARE OF:
  
 I. ANY DAMAGE TO EXISTING UTILITIES RESULTING FROM THE
 DEVELOPER?S CONSTRUCTION ACTIVITIES SHALL BE REPAIRED,
 AT THE DEVELOPER?S EXPENSE.
  
 II. ANY REQUIRED EASEMENTS (I.E. DRAINAGE, UTILITIES,
 PUBLIC ACCESS, ETC.) SHALL BE PROVIDED VIA PLAT OR
 SEPARATE LEGAL INSTRUMENT.
  
 III. THE DEVELOPER, ITS SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES, TREE GRATES, AND RIGHT OF WAY LANDSCAPING
 AND IRRIGATION ASSOCIATED WITH THE APPROVED SITE PLAN.
 ALL PERMITS SHALL BE OBTAINED PRIOR TO COMMENCEMENT OF
 CONSTRUCTION OF SUCH IMPROVEMENTS.
  
 IV. THE DEVELOPER, ITS SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE REMOVAL AND/OR RELOCATION OF ALL
 STREET LIGHTS/POLES NECESSITATED BY THE PROPOSED
 DEVELOPMENT. ALL NEW STREET LIGHTING SHALL CONFORM TO
 THE MINIMUM REQUIREMENTS AND SHALL BE REVIEWED AND
 PERMITTED BY ALL APPLICABLE GOVERNING AGENCIES,
 INCLUDING THE CITY?S ENGINEERING SERVICES DEPARTMENT.
  
 V. FINAL APPROVAL OF THE ENGINEERING DESIGN SHALL BE
 BASED UPON SUBMITTAL OF A SEPARATE PERMIT APPLICATION
 TO, AND REVIEW BY, THE CITY?S PUBLIC WORKS AND
 ENGINEERING DEPARTMENTS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved