| 2019-04-15 10:05:58 | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | |
| | 1) PROVIDE DOCUMENTATION SHOWING THE TUB IS LISTED AND |
| | LABELED IN ACCORDANCE WITH UL1795. FBC-P 421.1 |
| | |
| | 2) PROVIDE DOCUMENTATION SHOWING TH HYDROGUARD |
| | TEMPERING VALVE IS LEAD FREE AND ASSE 1070 APPROVED |
| | DEVICE. FBC-R P2713.3 |
| | |
| | 3) HYDROGUARD SUPPORTING DOCUMENTATION SUPPLIED ADVISED |
| | VALVE SHALL NOT BE SET ABOVE 105F. FBC 607.1 REQUIRES |
| | MIN HOT WATER FOR BATHING. DEFINITIONS OF HOT WATER |
| | (FBC-P) IS WATER GREATER THAN OR EQUAL TO 110F. |
| | |
| | 4) PROVIDE DISTANCE THAT EXISTING SHOWER DRAIN WILL BE |
| | RELOCATED TO NEW TUB DRAIN LOCATION. FBC-R P3201.6 |
| | |
| | 5) VALUE SEEMS LOW. PROVIDE SIGNED BONA FIDE CONTRACT. |
| | WPB AMEND TO THE FBC 109.3 BUILDING PERMIT VALUATIONS. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT |
| | SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW |
| | DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| | CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE |
| | APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. |
| | |
| | 6) PROVIDE SANITARY ISOMETRIC DRAWING FOR RELOCATION OF |
| | DRAIN. FBC 107.3.5 |
| | |
| | 7) BUILDING PLAN AND PERMIT MAY BE REQUIRED IF ANY SLAB |
| | REPAIR OR WALL REPAIR WILL BE COMPLETED. FBC 105.1 |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |