| 2019-04-10 16:18:52 | 1ST REVIEW FBC-2017 MECHANICAL |
| | REVISION #19040349 |
| | MASTER #19021148 |
| | 4/10/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) DRESSING ROOMS FOR RETAILL STORES (NOT ASSOCIATED |
| | WITH LOCKER ROOMS) REQUIRE EXHAUST VENTILATION AT A |
| | RATE OF 0.25 CFMS PER SF- SEE TABLE 403.3.1.1 FBC M. |
| | THERE IS NO EXCEPTION SHOWN IN THE TABLE FOR DRESSING |
| | ROOMS WITHOUT CEILINGS OR DOORS. PLEASE PROVIDE THE |
| | EXHAUST FANS THAT WERE SHOWN ON THE ORIGINAL APPROVED |
| | PLAN, AND SHOW THE EXHAUST DUCT RUNS AND TERMINATION |
| | LOCATIONS. |
| | |
| | 2) PLEASE PROVIDE THE TYPE AND SIZE OF DIFFUSERS FOR |
| | THE NEW 8" DUCT DROPS- SECTION 603 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |