Plan Review Details - Permit 19040317
Plan Review Stops For Permit 19040317
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-07-22 Cont ID  
Sent By jwitmer Date 2019-07-22 Time 09:13 Rev Time 0.00
Received By jwitmer Date 2019-07-22 Time 06:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-16 Cont ID  
Sent By shill Date 2019-05-16 Time 11:07 Rev Time 0.00
Received By shill Date 2019-05-16 Time 11:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-30 Cont ID  
Sent By jwitmer Date 2019-04-30 Time 07:25 Rev Time 0.00
Received By jwitmer Date 2019-04-29 Time 15:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-07-24 Cont ID  
Sent By jpearson Date 2019-07-24 Time 15:26 Rev Time 0.00
Received By jpearson Date 2019-07-24 Time 15:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-06-24 Cont ID  
Sent By jpearson Date 2019-06-24 Time 08:46 Rev Time 0.00
Received By jpearson Date 2019-06-24 Time 08:46 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-16 Cont ID  
Sent By jpearson Date 2019-05-16 Time 11:03 Rev Time 0.00
Received By jpearson Date 2019-05-16 Time 11:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-04-29 Cont ID  
Sent By jpearson Date 2019-04-29 Time 13:58 Rev Time 0.00
Received By jpearson Date 2019-04-29 Time 13:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-07-10 Cont ID  
Sent By pleduc Date 2019-07-10 Time   Rev Time 0.00
Received By pleduc Date 2019-07-10 Time 10:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-05-10 Cont ID  
Sent By pleduc Date 2019-05-10 Time   Rev Time 0.00
Received By pleduc Date 2019-05-10 Time 14:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-04-09 Cont ID  
Sent By scaldero Date 2019-04-09 Time 12:43 Rev Time 0.00
Received By scaldero Date 2019-04-09 Time 12:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-07-30 Cont ID  
Sent By pvalenti Date 2019-07-30 Time 13:30 Rev Time 0.00
Received By pvalenti Date 2019-07-03 Time 15:02 Sent To  
Notes
2019-07-03 15:02:37B20

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-06-24 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-03 Time 15:22 Sent To  
Notes
2019-06-04 15:23:09B24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-16 Cont ID  
Sent By shill Date 2019-05-16 Time 11:07 Rev Time 0.00
Received By shill Date 2019-05-02 Time 16:01 Sent To  
Notes
2019-05-02 16:01:47B02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-04-30 Time   Rev Time 0.00
Received By cpuell Date 2019-04-05 Time 15:58 Sent To  
Notes
2019-04-09 09:08:29B03
2019-04-08 15:58:35B01

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-07-30 Cont ID  
Sent By pvalenti Date 2019-07-30 Time 13:21 Rev Time 0.00
Received By pvalenti Date 2019-07-30 Time 13:21 Sent To  
Notes
2019-07-30 13:29:28PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
  
  
 THE PLANS NOW SHOW HARD CEILINGS WITH INSULATION AS PER
 PRIOR REVIEW NOTES.
  
 APPROVED WITH PROVISO:
  
 THE AIR HANDLER LOCATED ABOVE THE CEILING IS REQUIRED
 TO HAVE A CEILING ACCESS OPENING LARGE ENOUGH TO REMOVE
 THE LARGEST APPLIANCE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-06-13 Cont ID  
Sent By ccole Date 2019-06-13 Time 11:06 Rev Time 0.00
Received By ccole Date 2019-06-13 Time 10:53 Sent To  
Notes
2019-06-13 11:21:273RD REVIEW FBC-2017 MECHANICAL
 PERMIT #19040317
 5/13/19
  
 APPLICABLE CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) INSULATION INSTALLED ON A SUSPENDED CEILING WITH
 REMOVABLE CEILING TILES SHALL NOT BE CONSIDERED PART OF
 THE MINIMUM THERMAL RESISTANCE OF THE ROOF INSULATION-
 SECTION C402.2.2 FBC EC. THE SUBMITTED INPUT DATA
 REPORT ATTACHED TO THE ENERGYGAUGE COMPLIANCE REPORT
 SHOWS R-11 IN THE MTL BLDG ROOF WHICH DOES NOT
 REPRESENT THE ACTUAL FIELD CONDITIONS. IN ADDITION,
 PLEASE REVIEW THE 2015 IECC COMMENTARY REGARDING
 INSULATION ON THE UPPERSIDE OF THE CEILING TILES: "THE
 CODE PROHIBITS CONDIDERING TH INSULATION ON THE UPPER
 SIDE OF REMOVABLE CEILING TILES AS A PORTION OF THE
 REQUIRED INSULATION. THEREFORE, ON SUSPENDED CEILING
 SYSTEMS WITH REMOVABLE TILES, ANY INSULATION INSTALLED
 AT THIS LOCATION IS NOT CONSIDERED AS CONTRIBUTING TO
 THE MINIMUM REQUIRED BUILDING THERMAL ENVELOPE
 PROVISIONS."
 IN ORDER TO ADDRESS THIS SITUATION, IT APPEARS
 INSULATION WOULD BE CREDITIED IF IS INSTALLED ABOVE A
 HARD CEILING, OR IF THE WALLS AND THERMAL BARRIERS
 EXTENDED UP TO THE ROOF DECK AND THE ROOF WAS INSULATED
 TO MINIMUM R-10.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-05-13 Cont ID  
Sent By ccole Date 2019-05-13 Time 08:45 Rev Time 0.00
Received By ccole Date 2019-05-10 Time 17:12 Sent To  
Notes
2019-05-13 08:56:372ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19040317
 5/13/19
  
 APPLICABLE CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION C407.2.1 FBC EC : "THE ROOF OR
 CEILING THAT FUNCTIONS AS THE BUILDING'S THERMAL
 ENVELOPE SHALL BE INSULATED TO AN R-VALUE OF AT LEAST
 R-10. MULTIPLE-FAMILY RESIDENTIAL ROOFS/CEILINGS SHALL
 BE INSULATED TO AN R-VALUE OF AT LEAST R-19, SPACE
 PERMITTING. WHERE CAVITIES BENEATH A ROOF DECK ARE
 VENTILATED, THE CEILING SHALL BE CONSIDERED THE
 ENVELOPE COMPONENT UTILIZED IN THE COMMISSION APPROVED
 COMPLIANCE SOFTWARE TOOLS." THE REVISED PLANS AND
 SUBMITTED ENERGYGAUGE REPORT ARE NOT IN COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-24 Cont ID  
Sent By ccole Date 2019-04-24 Time 17:11 Rev Time 0.00
Received By ccole Date 2019-04-24 Time 17:11 Sent To  
Notes
2019-04-24 17:24:081ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040317
 4/24/19
  
 APPLICABLE CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS WERE SUBMITTED. PLEASE PROVIDE
 MECHANICAL PLANS AND SPECIFICATIONS INCLUDING:
 A) AC PLAN SHOWING THE LOCATIONS OF THE AIR HANDLER AND
 CONDENSER, AND DUCT LAYOUT- SECTION 107.2.1 WPB.
 B) AC EQUIPMENT SCHEDULE- SECTION 107.2.1 WPB
 C) AC COOLING AND HEATING SYSTEM SIZING CALCULATIONS-
 SECTION C403.2.1 FBC EC
 D) ENERGY CALCULATIONS FOR THE NEW CONDITIONED OFFICE
 SPACE- SECTION C503.2 FBC EC.
 E) VENTILATION CALULATIONS INDICATING THE REQUIRED AND
 PROVIDED OUTDOOR AIR CFMS- TABLE 403.3.1.1 FBC M.
 F) CONDENSATE DISPOSAL PLAN- SECTION 307.2.1 FBC M.
 G) CONDENSER INSTALLATION DETAILS- SECTION 301.15 FBC
 M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-07-19 Cont ID  
Sent By gjohnson Date 2019-07-19 Time 10:17 Rev Time 0.00
Received By gjohnson Date 2019-07-18 Time 09:53 Sent To  
Notes
2019-07-19 10:18:43PLUMBING PROVISO:
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL.
 2. ALL PLUMBING WORK SHALL COMPLY WITH FBC PLUMBING 6TH
 EDITION 2017
 4. THE CENTER OF THE TOILET SHALL BE 16" MIN 18 MAX OFF
 THE SIDE WALL. PER FBC ACC 604.2
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-06-18 Cont ID  
Sent By thunt Date 2019-06-18 Time 08:26 Rev Time 0.00
Received By thunt Date 2019-06-18 Time 07:11 Sent To  
Notes
2019-06-18 08:26:51PLUMBING PROVISO:
  
 1) PROVIDE TANKLESS WATER HEATER INSTALLATION MANUAL @
 TIME OF INSPECTION. TANKLESS SHALL BE SIZED SO THAT IT
 CAN PRODUCE HOT/TEMPERED WATER TO ALL REQUIRED FIXTURES
 AT FULL DEMAND.
  
 2) A THERMOSTAT CONTROL FOR A WATER HEATER SHALL NOT
 SERVE AS THE TEMPERING LIMITING DEVICE. FBC P607.1.1
  
 3) TEMPERED WATER SHALL BE SUPPLIED BY MEANS OF AN
 APPROVED ASSE 1070 DEVICE LIMITED TO 110F TO ALL HAND
 WASH SINKS. FBC P607.1.2
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-05-06 Cont ID  
Sent By thunt Date 2019-05-06 Time 10:30 Rev Time 0.00
Received By thunt Date 2019-05-06 Time 10:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-19 Cont ID  
Sent By gjohnson Date 2019-04-19 Time 10:31 Rev Time 0.00
Received By gjohnson Date 2019-04-19 Time 10:25 Sent To  
Notes
2019-04-19 10:43:441ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WATER FOUNTAIN AND UTILITY SINK SHALL CONNECT TO
 BUILDING DRAIN DOWNSREAM OF THE BATHROOM GROUP. PER FBC
 PL 912.1
  
 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  