Plan Review Details - Permit 19040274
Plan Review Stops For Permit 19040274
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-04-25 Cont ID  
Sent By rgathrig Date 2019-04-25 Time 14:07 Rev Time 0.00
Received By rgathrig Date 2019-04-25 Time 14:07 Sent To  
Notes
2019-04-25 14:08:27BUILDING PROVISO
 1. ANY OR ALL PROVISOS FOR THE BASE BUILDING SHALL
 APPLY TO THIS INTERIOR BUILD OUT
 2. MUST PROVIDE ENERGY CODE DOCUMENTS BY FRAMING
 INSPECTION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-22 Cont ID  
Sent By shill Date 2019-04-22 Time 14:32 Rev Time 0.00
Received By shill Date 2019-04-22 Time 14:32 Sent To  
Notes
2019-04-22 14:35:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE NARRATIVE REFERS TO PLANS FOR BASE BUILDING,
 15111020. SHEET 126.60-12.90-21C - UNIT 21C ENLARGED
 FLOOR PLAN (19040274) IS NOT CONSISTENT WITH SHEET
 113-A2-71B - LEVEL 21 ENLARGED FLOOR PLAN - SOUTH.
 PLEASE ADVISE WHERE THE PLAN CAN BE FOUND (REVISION
 TRACKING # AND PAGE NAME), OR CLOUD THE PLANS TO SHOW
 CHANGES FROM BASE BUILDING, FBC 107.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-04-24 Cont ID  
Sent By jleahy Date 2019-04-24 Time 16:32 Rev Time 0.00
Received By jleahy Date 2019-04-24 Time 16:32 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2019-04-25 Cont ID  
Sent By jleahy Date 2019-04-25 Time 09:40 Rev Time 0.00
Received By jleahy Date 2019-04-25 Time 09:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-04-25 Cont ID  
Sent By pleduc Date 2019-04-09 Time   Rev Time 0.00
Received By pleduc Date 2019-04-09 Time 16:11 Sent To  
Notes
2019-04-09 16:12:30PPREVIOUS COMMENTS ADDRESSED.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2019-04-25 Cont ID  
Sent By rgathrig Date 2019-04-25 Time 14:13 Rev Time 0.00
Received By rgathrig Date 2019-04-25 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-26 Cont ID  
Sent By lmarchan Date 2019-04-26 Time 10:47 Rev Time 0.00
Received By lmarchan Date 2019-04-08 Time 11:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-04-25 Cont ID  
Sent By rgathrig Date 2019-04-25 Time 14:13 Rev Time 0.00
Received By rgathrig Date 2019-04-25 Time 14:12 Sent To  
Notes
2019-04-25 14:13:27PASSED WITH PROVISOS

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-04-25 Cont ID  
Sent By rgathrig Date 2019-04-25 Time 14:08 Rev Time 0.00
Received By rgathrig Date 2019-04-25 Time 14:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-04-25 Cont ID  
Sent By rgathrig Date 2019-04-25 Time 14:14 Rev Time 0.00
Received By rgathrig Date 2019-04-25 Time 14:13 Sent To  
Notes
***NONE***