Plan Review Details - Permit 19040235
Plan Review Stops For Permit 19040235
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-13 Cont ID  
Sent By pvalenti Date 2019-05-13 Time 10:51 Rev Time 0.00
Received By pvalenti Date 2019-05-13 Time 10:32 Sent To  
Notes
2019-05-13 10:54:43 
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW APPROVED AS PER SUBMITTALS; THE
 FLOORING SUBMITTALS ARE FOR TILE WITH PROFLEX 90.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 17:13 Rev Time 0.00
Received By shill Date 2019-04-30 Time 17:13 Sent To  
Notes
2019-04-30 17:15:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE
 PROPOSED? IF THE UNDERLAYMENT PRODUCT PROPOSED IS NOT
 ONE FOR WHICH WE HAVE TEST REPORTS ON FILE, THE
 FOLLOWING REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-13 Cont ID  
Sent By jpearson Date 2019-05-13 Time 15:43 Rev Time 0.00
Received By jpearson Date 2019-05-13 Time 15:43 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-18 Cont ID  
Sent By jpearson Date 2019-04-18 Time 14:34 Rev Time 0.00
Received By jpearson Date 2019-04-18 Time 14:20 Sent To  
Notes
2019-04-18 14:34:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER
 SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS
 CODE IN SOME AREAS. SHOW RECEPTACLE OUTLETS AS NEW OR
 EXISTING AS APPLIES. PROVIDE CORRECTION. NEC
 210.52(C)(1)
 2. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D)
 3. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET ON THE
 KITCHEN PENINSULA. NEC 210.8, 210.52(C)(3)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-05-10 Cont ID  
Sent By pleduc Date 2019-05-10 Time   Rev Time 0.00
Received By pleduc Date 2019-05-10 Time 14:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-04-09 Cont ID  
Sent By scaldero Date 2019-04-09 Time 12:40 Rev Time 0.00
Received By scaldero Date 2019-04-09 Time 12:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-05-13 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-06 Time 13:15 Sent To  
Notes
2019-05-07 13:15:23B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 17:15 Rev Time 0.00
Received By shill Date 2019-04-04 Time 09:01 Sent To  
Notes
2019-04-09 09:01:28B01

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-05-09 Cont ID  
Sent By ccole Date 2019-05-09 Time 11:42 Rev Time 0.00
Received By ccole Date 2019-05-09 Time 10:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-18 Cont ID  
Sent By ccole Date 2019-04-18 Time 10:12 Rev Time 0.00
Received By ccole Date 2019-04-18 Time 10:04 Sent To  
Notes
2019-04-18 10:19:271ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040235
 4/18/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS
 WITH CORRESPONDING DRAWINGS AND DETAILS- SECTION
 107.2.1 WPB.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 RANGE AND EXHAUST HOOD, AND ANY OTHER NEW COOKING
 APPLIANCES- SECTIONS 505.1 AND 917.1 FBC M. PLEASE SEE
 SECTION 505.2 PRINTED BELOW AND SHOW COMPLIANCE.
  
 505.2 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CFM (0.19 M3/S) SHALL BE PROVIDED WITH MAKEUP AIR
 AT A RATE APPROXIMATELY EQUAL TO THE EXHAUST AIR RATE.
 SUCH MAKEUP AIR SYSTEMS SHALL BE EQUIPPED WITH A MEANS
 OF CLOSURE AND SHALL BE AUTOMATICALLY CONTROLLED TO
 START AND OPERATE SIMULTANEOUSLY WITH THE EXHAUST
 SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-05-09 Cont ID  
Sent By gjohnson Date 2019-05-09 Time 15:33 Rev Time 0.00
Received By gjohnson Date 2019-05-09 Time 14:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-04-12 Cont ID  
Sent By gjohnson Date 2019-04-12 Time 12:48 Rev Time 0.00
Received By gjohnson Date 2019-04-12 Time 11:02 Sent To  
Notes
***NONE***