Plan Review Details - Permit 19040231
Plan Review Stops For Permit 19040231
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-06-24 Cont ID  
Sent By cthroop Date 2019-06-24 Time 12:21 Rev Time 0.00
Received By cthroop Date 2019-06-24 Time 10:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-22 Cont ID  
Sent By jduprey Date 2019-05-22 Time 11:00 Rev Time 0.00
Received By jduprey Date 2019-05-22 Time 10:37 Sent To  
Notes
2019-05-22 11:00:03BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ***REPEAT COMMENTS***
  
 1. VALUE APPEARS LOW FOR SCOPE OF WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE. CITY OF WPB CHPT. 1 VALUE 109.3
  
 2. PROVIDE SECOND SET OF PRODUCT APPROVALS.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 3. REF. PLAN PAGE A-1, NOTE 9,LEVEL OF ALTERATION
 SHOULD STATE LEVEL 3.
 505.1 SCOPE.
 LEVEL 3 ALTERATIONS APPLY WHERE THE WORK AREA EXCEEDS
 50 PERCENT OF THE BUILDING AREA.
  
 505.2 APPLICATION.
 LEVEL 3 ALTERATIONS SHALL COMPLY WITH THE PROVISIONS OF
 CHAPTERS 7 AND 8 FOR LEVEL 1 AND 2 ALTERATIONS,
 RESPECTIVELY, AS WELL AS THE PROVISIONS OF CHAPTER 9.
  
 4. OK
  
 5. RAMP DETAIL IS NOT LEGIBLE FBC 107, RAMP SHALL
 COMPLY WITH FBC R311.8. IDENTIFY LOCATION OF RAMP ON
 SITE PLAN. IDENTIFY SLOPE OF RAMP ON DETAIL. SLOPE
 SHALL BE BASED ON LOCATION. I.E. EGRESS DOOR - 1/12.
 NON-EGRESS DOOR 1/8.
  
 R311.8.1MAXIMUM SLOPE.
 RAMPS SERVING THE EGRESS DOOR REQUIRED BY SECTION
 R311.2 SHALL HAVE A SLOPE OF NOT MORE THAN 1 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (8.3-PERCENT SLOPE).
 ALL OTHER RAMPS SHALL HAVE A MAXIMUM SLOPE OF 1 UNIT
 VERTICAL IN 8 UNITS HORIZONTAL (12.5 PERCENT).
 EXCEPTION: WHERE IT IS TECHNICALLY INFEASIBLE TO COMPLY
 BECAUSE OF SITE CONSTRAINTS, RAMPS SHALL HAVE A SLOPE
 OF NOT MORE THAN 1 UNIT VERTICAL IN 8 UNITS HORIZONTAL
 (12.5 PERCENT).
  
 6. ROOFING PERMIT REQUIRED.
  
 7. PROVIDE NORTH CARDINAL ARROW.
 PROVIDE A NORTH CARDINAL DIRECTIONAL ARROW ON THE PLANS
 THAT INDICATES THE ORIENTATION OF THE STRUCTURE. FBC
 107.2.1 & FBC ENERGY CONSERVATION R405.4.2.1
  
 R405.4.2.1 COMPLIANCE REPORT FOR PERMIT APPLICATION.
 A COMPLIANCE REPORT SUBMITTED WITH THE APPLICATION FOR
 BUILDING PERMIT SHALL INCLUDE THE FOLLOWING:
 1.BUILDING STREET ADDRESS, OR OTHER BUILDING SITE
 IDENTIFICATION.
 2.A STATEMENT INDICATING THAT THE PROPOSED DESIGN
 COMPLIES WITH SECTION R405.3.
 3.AN INSPECTION CHECKLIST DOCUMENTING THE BUILDING
 COMPONENT CHARACTERISTICS OF THE PROPOSED DESIGN AS
 INDICATED IN TABLE R405.5.2(1). THE INSPECTION
 CHECKLIST SHALL SHOW RESULTS FOR THE PROPOSED DESIGN
 WITH USER INPUTS TO THE COMPLIANCE SOFTWARE TO GENERATE
 THE RESULTS.
 4.A SITE-SPECIFIC ENERGY ANALYSIS REPORT THAT IS IN
 COMPLIANCE WITH SECTION R405.3.
 5.THE NAME OF THE INDIVIDUAL PERFORMING THE ANALYSIS
 AND GENERATING THE REPORT.
 6.THE NAME AND VERSION OF THE COMPLIANCE SOFTWARE TOOL.
  
 EXCEPTION: MULTIPLE ORIENTATIONS. WHEN AN OTHERWISE
 IDENTICAL BUILDING MODEL IS OFFERED IN MULTIPLE
 ORIENTATIONS, COMPLIANCE FOR ANY ORIENTATION SHALL BE
 PERMITTED BY DOCUMENTING THAT THE BUILDING MEETS THE
 PERFORMANCE REQUIREMENTS IN EACH OF THE FOUR CARDINAL
 (NORTH, EAST, SOUTH AND WEST) ORIENTATIONS, OR THE
 ?WORST? ORIENTATION. COMPLIANCE SOFTWARE TOOLS MAY
 CALCULATE THE ?WORST CASE? ORIENTATION BY ROTATING THE
 BUILDING THROUGH THE 4 OR 8 CARDINAL ORIENTATIONS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By cthroop Date 2019-04-30 Time 07:43 Rev Time 0.00
Received By cthroop Date 2019-04-29 Time 14:39 Sent To  
Notes
2019-04-30 08:02:01BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE APPEARS LOW FOR SCOPE OF WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2. PROVIDE SECOND SET OF PRODUCT APPROVALS.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 3. REF. PLAN PAGE A-1, NOTE 9,LEVEL OF ALTERATION
 SHOULD STATE LEVEL 3.
 505.1 SCOPE.
 LEVEL 3 ALTERATIONS APPLY WHERE THE WORK AREA EXCEEDS
 50 PERCENT OF THE BUILDING AREA.
  
 505.2 APPLICATION.
 LEVEL 3 ALTERATIONS SHALL COMPLY WITH THE PROVISIONS OF
 CHAPTERS 7 AND 8 FOR LEVEL 1 AND 2 ALTERATIONS,
 RESPECTIVELY, AS WELL AS THE PROVISIONS OF CHAPTER 9.
  
 4. IDENTIFY ROOF SLOPE. STATE NUMBER OF LAYERS OF
 UNDERLAYMENT REQUIRED.
  
 RAS 115. R905.2.2 SLOPE.
 ASPHALT SHINGLES SHALL BE USED ONLY ON ROOF SLOPES OF
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) OR
 GREATER. FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12
 UNITS HORIZONTAL (2:12) AND LESS THAN FOUR UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (4:12), DOUBLE
 UNDERLAYMENT APPLICATION IS REQUIRED IN ACCORDANCE WITH
 SECTION R905.2.7.
  
 5. RAMP SHALL COMPLY WITH FBC R311.8. IDENTIFY LOCATION
 OF RAMP ON SITE PLAN. IDENTIFY SLOPE OF RAMP ON DETAIL.
 SLOPE SHALL BE BASED ON LOCATION. I.E. EGRESS DOOR -
 1/12. NON-EGRESS DOOR 1/8.
  
 R311.8.1MAXIMUM SLOPE.
 RAMPS SERVING THE EGRESS DOOR REQUIRED BY SECTION
 R311.2 SHALL HAVE A SLOPE OF NOT MORE THAN 1 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (8.3-PERCENT SLOPE).
 ALL OTHER RAMPS SHALL HAVE A MAXIMUM SLOPE OF 1 UNIT
 VERTICAL IN 8 UNITS HORIZONTAL (12.5 PERCENT).
 EXCEPTION: WHERE IT IS TECHNICALLY INFEASIBLE TO COMPLY
 BECAUSE OF SITE CONSTRAINTS, RAMPS SHALL HAVE A SLOPE
 OF NOT MORE THAN 1 UNIT VERTICAL IN 8 UNITS HORIZONTAL
 (12.5 PERCENT).
  
 6. ROOFING PERMIT REQUIRED.
  
 7. PROVIDE NORTH CARDINAL ARROW.
 PROVIDE A NORTH CARDINAL DIRECTIONAL ARROW ON THE PLANS
 THAT INDICATES THE ORIENTATION OF THE STRUCTURE. FBC
 107.2.1 & FBC ENERGY CONSERVATION R405.4.2.1
  
 R405.4.2.1 COMPLIANCE REPORT FOR PERMIT APPLICATION.
 A COMPLIANCE REPORT SUBMITTED WITH THE APPLICATION FOR
 BUILDING PERMIT SHALL INCLUDE THE FOLLOWING:
 1.BUILDING STREET ADDRESS, OR OTHER BUILDING SITE
 IDENTIFICATION.
 2.A STATEMENT INDICATING THAT THE PROPOSED DESIGN
 COMPLIES WITH SECTION R405.3.
 3.AN INSPECTION CHECKLIST DOCUMENTING THE BUILDING
 COMPONENT CHARACTERISTICS OF THE PROPOSED DESIGN AS
 INDICATED IN TABLE R405.5.2(1). THE INSPECTION
 CHECKLIST SHALL SHOW RESULTS FOR THE PROPOSED DESIGN
 WITH USER INPUTS TO THE COMPLIANCE SOFTWARE TO GENERATE
 THE RESULTS.
 4.A SITE-SPECIFIC ENERGY ANALYSIS REPORT THAT IS IN
 COMPLIANCE WITH SECTION R405.3.
 5.THE NAME OF THE INDIVIDUAL PERFORMING THE ANALYSIS
 AND GENERATING THE REPORT.
 6.THE NAME AND VERSION OF THE COMPLIANCE SOFTWARE TOOL.
  
 EXCEPTION: MULTIPLE ORIENTATIONS. WHEN AN OTHERWISE
 IDENTICAL BUILDING MODEL IS OFFERED IN MULTIPLE
 ORIENTATIONS, COMPLIANCE FOR ANY ORIENTATION SHALL BE
 PERMITTED BY DOCUMENTING THAT THE BUILDING MEETS THE
 PERFORMANCE REQUIREMENTS IN EACH OF THE FOUR CARDINAL
 (NORTH, EAST, SOUTH AND WEST) ORIENTATIONS, OR THE
 ?WORST? ORIENTATION. COMPLIANCE SOFTWARE TOOLS MAY
 CALCULATE THE ?WORST CASE? ORIENTATION BY ROTATING THE
 BUILDING THROUGH THE 4 OR 8 CARDINAL ORIENTATIONS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-06-24 Cont ID  
Sent By cthroop Date 2019-06-24 Time 12:21 Rev Time 0.00
Received By cthroop Date 2019-06-24 Time 11:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-24 Cont ID  
Sent By jpearson Date 2019-05-24 Time 13:57 Rev Time 0.00
Received By jpearson Date 2019-05-24 Time 09:50 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-19 Cont ID  
Sent By fgiaquin Date 2019-04-19 Time 16:19 Rev Time 0.00
Received By fgiaquin Date 2019-04-19 Time 15:48 Sent To  
Notes
2019-04-19 16:17:42ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. TANKLESS WATER HEATER LOCATION IS NOT SHOWN ON
 ELECTRICAL PLAN, PROVIDE LOCATION. FBC 107.2.1
  
 2. PROVIDE CUT SHEETS FOR TANKLESS WATER HEATER FOR
 PRODUCT APPROVAL. MUST BE LISTED UL OR ANOTHER (NRTL).
 FBC 107.2.1 NEC 90.7, 110.2, 110.3B
  
 3. SERVICE DISCONNECT NOT SHOWN ON PLAN. PROVIDE
 LOCATION. FBC 107.2.1
  
 4. AHU OVERCURRENT PROTECTION IS SHOWN AS 20 AMPS. HEAT
 STRIP IN AHU IS SHOWN AS 7.5KW. PROVIDE CORRECT PANEL
 SCHEDULE WITH PROPER OVERCURRENT PROTECTION AND WIRE
 SIZE. FBC 107.2.1
  
 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-07-30 Cont ID  
Sent By tklarge Date 2019-07-30 Time 07:01 Rev Time 0.00
Received By tklarge Date 2019-07-15 Time 14:31 Sent To  
Notes
2019-07-16 14:31:11RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-24 Cont ID  
Sent By cthroop Date 2019-06-24 Time 12:21 Rev Time 0.00
Received By cthroop Date 2019-06-03 Time 15:56 Sent To  
Notes
2019-06-04 15:57:01R12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-25 Cont ID  
Sent By cmontell Date 2019-05-25 Time 07:47 Rev Time 0.00
Received By cmontell Date 2019-05-25 Time 07:47 Sent To  
Notes
2019-05-09 15:46:35R31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-30 Cont ID  
Sent By cthroop Date 2019-04-30 Time 08:14 Rev Time 0.00
Received By cthroop Date 2019-04-04 Time 14:53 Sent To  
Notes
2019-04-04 14:53:11R03

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2019-06-24 Cont ID  
Sent By cthroop Date 2019-06-24 Time 12:20 Rev Time 0.00
Received By cthroop Date 2019-06-24 Time 12:20 Sent To  
Notes
2019-06-24 12:21:03MECHANICAL BY SEPERATE PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-05-25 Cont ID  
Sent By cmontell Date 2019-05-25 Time 07:46 Rev Time 0.00
Received By cmontell Date 2019-05-25 Time 07:45 Sent To I
Notes
2019-05-25 07:46:35MECHANICAL PLAN REVIEW FAIL
  
  
 1. PROVIDE MECHANICAL PLAN.
 FBC CHPT 1 SECTION 105.
  
 2. PROVIDE ENERGY SUBMITTAL.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 3. PROVIDE EPL CARD.
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 CHRIS MONTELLO
 805-6733
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By cthroop Date 2019-04-30 Time 08:08 Rev Time 0.00
Received By cthroop Date 2019-04-29 Time 14:39 Sent To  
Notes
2019-04-30 08:14:22MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE MECHANICAL PLAN.
 FBC CHPT 1 SECTION 105.
  
 2. PROVIDE ENERGY SUBMITTAL.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 3. PROVIDE EPL CARD.
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-07-30 Cont ID  
Sent By tklarge Date 2019-07-30 Time 07:00 Rev Time 0.00
Received By tklarge Date 2019-07-29 Time 11:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-06-17 Cont ID  
Sent By thunt Date 2019-06-17 Time 11:13 Rev Time 0.00
Received By thunt Date 2019-06-17 Time 06:43 Sent To  
Notes
2019-06-17 11:12:58PLUMBING 3RD REVIEW**DENIED**ERIC FROM BUILD PRO WAS
 CONTACTED AND ADVISED OF ISSUES AND ACKNOWLEDGE OF LAST
 PLAN REVIEWERS COMMENTS REQUESTING A MEETING BUT DUE TO
 DESIGN PROFESSIONALS SCHEDULE SHE WAS NOT ABLE TO COME
 IN.BOTH ERIC AND DESIGN PROFESSIONAL ARE NOW ADVISING
 THIS PROJECT WILL MEET THE 2017 FLORIDA ACCESSIBILITY
 CODE IN FULL
  
  
 1) PROVIDE A CODE COMPLYING SANITARY ISOMETRIC DRAWING.
 THE WASHING MACHINE SHALL CONNECT TO A MIN 3" BRANCH/
 STACK. FBC-P 709.1, 406.2
  
 2) TANKLESS WATER HEATER LOCATION HAS BEEN MOVED TO
 UNDER THE KITCHEN SINK. THE INSTALLATION MANUAL DOES
 NOT PERMIT THE INSTALLATION OF THIS UNIT IN AREA'S THAT
 ARE DIFFICULT TO ACCESS, MAINTAIN, SERVICE, REPAIR, OR
 REPLACE OF THE UNIT SHOULD IT BE REQUIRED.. FBC-P 502.1
  
 3) PER ERIC (GC) IT IS YOUR INTENTION TO 100% COMPLY
 WITH 2017 FLORIDA ACCESSIBILITY. IT SO PLEASE ADDRESS
 THE FOLLOWING COMMENTS OTHERWISE REMOVE ALL ADA ITEMS
 FROM PLAN AS I WILL NOT PUT MY SIGNATURE ON A PLAN THAT
 DOES NOT SHOW CODE COMPLIANT ACCESSIBILITY.
 1. SHOW ON ALL SHEETS THE MIN SIZE PERMITTED FOR THE
 SHOWER ALT ROLL IN AS 36" X 60". SEE FBC-ACC 608.2.3
 2. GRAB BARS SHALL BE 33"-36" TO THE TOP OF THE
 GRIPPING SURFACE AND NOT THE CENTER OF THE BAR. FBC-ACC
 608.4
 3. SHOW WASHING MACHINE AS COMPLYING WITH FBC-ACC 611.
 CLEAR FLOOR SPACE, OPERABLE PARTS HEIGHT, ETC
 4. PROVIDE CLEAR FLOOR SPACE FOR THE ALT ROLL IN
 SHOWER. FBC-ACC 608.2.2.1
 5. PROVIDE KITCHEN DETAIL TO INCLUDE CLEAR FLOOR SPACE,
 COUNTER TOP HEIGHT, AND TUNING SPACE. FBC-ACC 606.2,
 606.3
 6. MIRROR SHALL BE MAX 40?"TO THE BOTTOM OF THE
 REFLECTIVE SURFACE.
 7. LIST 2017 FLORIDA ACCESSIBILITY CODE AS APPLICABLE
 CODE ON SHT. A-1
 8,SHOW DETAIL LOCATION OF ALL GRAB BARS. FBC-ACC
 608.3.3, 604.5.1, 604.5.2
 9 PROVIDE DETAIL OF SHOWER VALVE LOCATION MEETING
 FBC-ACC 608.5.3
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-05-13 Cont ID  
Sent By thunt Date 2019-05-13 Time 11:49 Rev Time 0.00
Received By thunt Date 2019-05-13 Time 11:49 Sent To  
Notes
2019-05-13 11:34:12BASED ON A PHONE CONVERSION WITH THE DESIGN
 PROFESSIONAL OF RECORD (MARTHA MCNICHOLAS, P.E) IT IS
 HER INTENT TO MAKE THE BATHROOM ACCESSIBLE TO FIT HER
 CLIENTS NEEDS BUT IN NO WAY MEET FLORIDA ACCESSIBILITY
 CODE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-09 Cont ID  
Sent By jesmith Date 2019-04-09 Time 13:01 Rev Time 0.00
Received By jesmith Date 2019-04-09 Time 12:50 Sent To  
Notes
2019-04-09 13:01:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. P-1 SANITARY RISER DIAGRAM
 A. PER WPB FBC 107.2.1, REPLACE WATER CLOSET P-TRAP
 WITH A VERTICAL TO HORIZONTAL DISCHARGE PIPE.
 B. PER FBC RES P3108.1, KITCHEN SINK AND CLOTHES WASHER
 SHALL NOT CONNECT TO THE BATHROOM GROUP.
 2. P-1 WATER RISER DIAGRAM
 A. PER FBC RES P2903.5, PROVIDE WATER HAMMER ARRESTORS
 FOR CLOTHES WASHER.
 3. PER WPB FBC 107.2.1, PROVIDE SPECS FOR THE TANKLESS
 WATER HEATER AND SHOW THAT IT WILL PROVIDE ADEQUATE HOT
 WATER TO SUPPLY THE NEEDS OF THE HOUSE.
  
  
 END OF COMMENTS
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, AA TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2019-05-22 Cont ID  
Sent By jduprey Date 2019-05-22 Time 11:00 Rev Time 0.00
Received By jduprey Date 2019-05-22 Time 11:00 Sent To  
Notes
2019-05-22 11:01:41ROOF SEPARATE PERMIT REQUIRED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By cthroop Date 2019-04-30 Time 08:03 Rev Time 0.00
Received By cthroop Date 2019-04-30 Time 08:02 Sent To  
Notes
2019-04-30 08:05:32BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. IDENTIFY ROOF SLOPE. STATE NUMBER OF LAYERS OF
 UNDERLAYMENT REQUIRED.
  
 RAS 115. R905.2.2 SLOPE.
 ASPHALT SHINGLES SHALL BE USED ONLY ON ROOF SLOPES OF
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) OR
 GREATER. FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12
 UNITS HORIZONTAL (2:12) AND LESS THAN FOUR UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (4:12), DOUBLE
 UNDERLAYMENT APPLICATION IS REQUIRED IN ACCORDANCE WITH
 SECTION R905.2.7.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-06-12 Cont ID  
Sent By awooten Date 2019-06-12 Time   Rev Time 0.00
Received By awooten Date 2019-06-12 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2019-05-20 Time   Rev Time 0.00
Received By awooten Date 2019-05-15 Time 15:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-04-26 Cont ID  
Sent By awooten Date 2019-04-26 Time   Rev Time  
Received By awooten Date 2019-04-26 Time   Sent To  
Notes
2019-04-26 14:34:27**********************************ZONING REVIEW
 FAILED******************************
  
 IT APPEARS THAT THE BUILDING FOOTPRINT IS NOT BEING
 EXPANDED.
  
 PLEASE SUBMIT A COPY OF THE SURVEY WITH THE RAMP
 LOCATION AND DIMENSIONS.(IF THE RAMP FALLS INTO THE
 FRONTYARD SETBACK, IT WILL BE INCLUDED IN THE LOT
 COVERAGE.)
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  
  