Plan Review Details - Permit 19040203
Plan Review Stops For Permit 19040203
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-05-10 Cont ID  
Sent By pleduc Date 2019-05-10 Time   Rev Time 0.00
Received By pleduc Date 2019-05-10 Time 13:39 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-04-16 Cont ID  
Sent By pleduc Date 2019-04-16 Time   Rev Time 0.00
Received By pleduc Date 2019-04-16 Time 14:13 Sent To I
Notes
2019-04-16 14:33:55THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET FP 2 - THERE APPEARS TO BE A SPRINKLER HEAD IN
 THE ELEVATOR MR.
  
 PER NFPA 13
  
 8.15.5.3 AUTOMATIC FIRE SPRINKLERS SHALL NOT BE
 REQUIRED IN ELEVATOR
 MACHINE ROOMS, ELEVATOR MACHINERY SPACES, CONTROL
 SPACES, OR
 HOISTWAYS OF TRACTION ELEVATORS INSTALLED IN ACCORDANCE
 WITH THE
 APPLICABLE PROVISIONS IN NFPA 101, OR THE APPLICABLE
 BUILDING
 CODE, WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE ELEVATOR MACHINE ROOM, MACHINERY SPACE, CONTROL
 ROOM, CONTROL SPACE, OR HOISTWAY OF TRACTION ELEVATOR
 IS
 DEDICATED TO ELEVATOR EQUIPMENT ONLY.
 (2) THE ELEVATOR MACHINE ROOM, MACHINE ROOM, MACHINERY
 SPACE, CONTROL ROOM, CONTROL SPACE, OR HOISTWAY OF
 TRACTION
 ELEVATORS ARE PROTECTED BY SMOKE DETECTORS, OR OTHER
 AUTOMATIC
 FIRE DETECTION, INSTALLED IN ACCORDANCE WITH NFPA72.
 (3) THE ELEVATOR MACHINERY SPACE, CONTROL ROOM, CONTROL
 SPACE,
 OR HOISTWAY OF TRACTION ELEVATORS IS SEPARATED FROM THE
 REMAINDER
 OF THE BUILDING BY WALLS AND FLOOR/CEILING OR ROOF/
 CEILING ASSEMBLIES HAVING A FIRE RESISTANCE RATING OF
 NOT LESS
 THAN THAT SPECIFIED BY THE APPLICABLE BUILDING CODE.
 (4) NO MATERIALS UNRELATED TO ELEVATOR EQUIPMENT ARE
 PERMITTED
 TO BE STORED IN ELEVATOR MACHINE ROOMS, MACHINERY
 SPACES, CONTROL ROOMS, CONTROL SPACES, OR HOISTWAYS OF
 TRACTION
 ELEVATORS.
 (5) THE ELEVATOR MACHINERY IS NOT OF THE HYDRAULIC
 TYPE.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY WITH SPECIFIC
 DETAILS.
  
  
  
  
 2) SHEET FP 6 - THERE APPEARS TO BE A SPRINKLER HEAD AT
 THE TOP OF THE WEST ELEVATOR HOISTWAY
  
 PER NFPA 13
  
 8.15.5.6 THE SPRINKLER REQUIRED AT THE TOP OF THE
 ELEVATOR HOISTWAY
 BY 8.15.5.5 SHALL NOT BE REQUIRED WHERE THE HOISTWAY
 FOR PASSENGER
 ELEVATORS IS NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE AND
 THE CAR ENCLOSURE MATERIALS MEET THE REQUIREMENTS OF
 ASME
 A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY WITH SPECIFIC
 DETAILS.
  
  
  
  
 3) LEVEL 1 CALCULATIONS AND SHEET FP 2 - THE
 CALCULATONS ON PAGE 1 DO NOT MATCH THE CALCULATIONS ON
 FP 2; DIFFERENT DENSITY AND AREA OF SPRINKLER
 OPERATION.
  
 WHICH ONE IS CORRECT?
  
 PLEASE REVIE AND CORRECT OF JUSTIFY.
  
  
  
  
  
 4) SHEET FP 1 - THE IS AN INDICATION UNDER THE NOTES
 SECTION, LAST NOTE, WITH REFERENCE TO PALM BEACH COUNTY
 FIRE RESCUE.
  
 PLEASE CORRECT THAT TO WEST PAM BEACH .
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-10 Cont ID  
Sent By cpuell Date 2019-05-10 Time 15:44 Rev Time 0.00
Received By cpuell Date 2019-05-08 Time 11:07 Sent To  
Notes
2019-05-09 11:07:11RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-16 Cont ID  
Sent By cpuell Date 2019-04-16 Time 15:05 Rev Time 0.00
Received By cpuell Date 2019-04-03 Time 10:31 Sent To  
Notes
2019-04-04 10:31:40ROUTED TO FIRE INBOX