Plan Review Details - Permit 19040169
Plan Review Stops For Permit 19040169
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-16 Cont ID  
Sent By jduprey Date 2019-04-16 Time 14:52 Rev Time 0.00
Received By jduprey Date 2019-04-16 Time 14:43 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-22 Cont ID  
Sent By fgiaquin Date 2019-07-22 Time 06:40 Rev Time 0.00
Received By fgiaquin Date 2019-07-22 Time 06:08 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-23 Cont ID  
Sent By fgiaquin Date 2019-04-23 Time 17:42 Rev Time 0.00
Received By fgiaquin Date 2019-04-23 Time 17:37 Sent To I
Notes
2019-04-23 17:40:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 NO ELECTRICAL PLAN PROVIDED. A FEW RECEPTACLES ARE
 SHOWN ON THE LANDSCAPE/ARCHITECTURAL DRAWINGS BUT NO
 CONDUIT SIZE, WIRE SIZE, OVERCURRENT PROTECTION, FEEDER
 LOCATION, PANEL ITS BEING FED FROM, OR LOAD
 CALCULATIONS PROVIDED.
  
 2. PROVIDE UL OR OTHER NRTL LISTING FOR ALL LIGHTING
 FIXTURES AND POLES. FBC 107.2.1 NEC 90.7, 110.2, 110.3B
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-22 Cont ID  
Sent By fgiaquin Date 2019-07-22 Time 06:40 Rev Time 0.00
Received By fgiaquin Date 2019-07-10 Time 14:31 Sent To  
Notes
2019-07-11 14:31:24RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-23 Cont ID  
Sent By fgiaquin Date 2019-04-23 Time 17:43 Rev Time 0.00
Received By fgiaquin Date 2019-04-03 Time 11:20 Sent To  
Notes
2019-04-04 11:20:47ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2019-04-15 Time   Rev Time 0.00
Received By pgreilic Date 2019-04-15 Time 11:08 Sent To B
Notes
2019-04-15 11:08:26LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved