Plan Review Details - Permit 19040167
Plan Review Stops For Permit 19040167
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-04-25 Cont ID  
Sent By thunt Date 2019-04-25 Time 14:54 Rev Time 0.00
Received By thunt Date 2019-04-25 Time 14:54 Sent To  
Notes
2019-04-25 14:56:06GAS PROVISO: A REVISON FOR THE MASTER PERMIT SHALL BE
 REQUIRED BEFORE FINAL GAS ALONG WITH A GENERATOR PERMIT
 BEING ISSUED FOR THE GENERATOR. ALL MANUFACTURE
 INSTALLATION MANUAL INCLUDING THE PRESSURE REGS SHALL
 BE ONSITE**TLH

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-04-18 Cont ID  
Sent By thunt Date 2019-04-18 Time 12:59 Rev Time 0.00
Received By thunt Date 2019-04-18 Time 12:59 Sent To  
Notes
2019-04-18 13:02:50GAS 2ND REVIEW**DENIED**CALLED CONTRACTOR REVIEW LIST
 OF ITEMS STILL MISSING EMAIL PARTS BUT STILL MISSING
 REQUIRED SUBMITTALS
  
 1) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3
  
 2) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD.
  
 3) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 4) )SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-05 Cont ID  
Sent By thunt Date 2019-04-05 Time 09:34 Rev Time 0.00
Received By thunt Date 2019-04-05 Time 09:34 Sent To I
Notes
2019-04-05 09:41:58GAS 1ST REVIEW**DENIED**I HAVE INCLUDED THE GAS
 REQUIREMENTS SHEET IN THIS PACKET FOR YOUR REVIEW.
 PLEASE FEEL FREE TO CONTACT ME AND REVIEW THE COMMENTS
 AND REQUIREMENTS
  
  
 1) VALUE SEEMS LOW. IT MUST INCLUDE THE COST OF ALL
 EQUIPMENT EVEN IF OWNER SUPPLIED. YOU VALUE LISTED IS
 STILL LESS THEN YOUR CONTRACT AMOUNT. PROVIDE A SIGNED
 BONA FIDE CONTRACT. WPB AMEND FBC 109.3
  
 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
  
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
  
 5) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1
  
 6) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF NOT, SUBMIT A
 COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF
 PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET,
 THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM,
 THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM.
 THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM
  
 7) SUBMIT TWO COPIES OF A LEGIBLE HOUSE PLAN SHOWING
 THE LOCATION OF THE TANKLESS WATER HEATER AND THE
 LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS
 IN RELATION TO THE WATER HEATER. THE LOCATION OF THE
 WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 8) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT
 REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT
 BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE
 ON THE APPLICATION IN THE DESCRIPTION OF WORK. PLUMBING
 PERMIT SHOW STORAGE TYPE IN GARAGE. FBC 107.3.5
  
 9) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 10) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
 11) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 12) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-04-25 Cont ID  
Sent By thunt Date 2019-04-25 Time 14:56 Rev Time 0.00
Received By thunt Date 2019-04-24 Time 13:53 Sent To  
Notes
2019-04-25 13:53:58RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2019-04-18 Cont ID  
Sent By thunt Date 2019-04-18 Time 13:03 Rev Time 0.00
Received By thunt Date 2019-04-16 Time 13:41 Sent To  
Notes
2019-04-17 13:41:18RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-05 Cont ID  
Sent By thunt Date 2019-04-05 Time 09:42 Rev Time 0.00
Received By thunt Date 2019-04-03 Time 10:17 Sent To  
Notes
2019-04-04 10:17:44PLUMB<5K