Plan Review Details - Permit 19040162
Plan Review Stops For Permit 19040162
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-24 Cont ID  
Sent By jgomez Date 2019-05-24 Time 18:37 Rev Time 0.00
Received By jgomez Date 2019-05-24 Time 18:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-24 Cont ID  
Sent By jgomez Date 2019-05-24 Time 08:55 Rev Time 0.00
Received By jgomez Date 2019-05-24 Time 08:28 Sent To  
Notes
2019-05-24 08:33:52NEW SINGLE FAMILY RESIDENCE R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- ENERGY CALCULATIONS SUBMITTED:
  
 ORIGINAL COMMENT:
 A) THE BUILDING'S OWNER, THE OWNERS ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE PRIOR TO RECEIVING THE PERMIT AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 NOT ADDRESSED.
  
 B) OK.
  
 C) OK.
  
 ORIGINAL COMMENT:
 D) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 NOT ADDRESSED.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By jgomez Date 2019-05-16 Time 09:37 Rev Time 0.00
Received By jgomez Date 2019-05-15 Time 14:14 Sent To  
Notes
2019-05-16 09:38:06NEW SINGLE FAMILY RESIDENCE R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) THE BUILDING'S OWNER, THE OWNER'S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE PRIOR TO RECEIVING THE PERMIT AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 5. THE
 RATIO IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL.
 OR, PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE
 COMPLETE DOCUMENTATION SHOWING COMPLIANCE WITH THE
 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2.
  
 C)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER'S NAME, PERMIT OFFICE, SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $192,863. THE
 PERMIT FEE BALANCE IS $3869.41
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-04-29 Cont ID  
Sent By jpearson Date 2019-04-29 Time 13:08 Rev Time 0.00
Received By jpearson Date 2019-04-29 Time 07:12 Sent To  
Notes
2019-04-29 13:08:46PASSED WITH PROVISO ON PLAN.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-24 Cont ID  
Sent By jgomez Date 2019-05-24 Time 18:37 Rev Time 0.00
Received By jgomez Date 2019-05-24 Time 18:18 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-24 Cont ID  
Sent By jgomez Date 2019-05-24 Time 09:40 Rev Time 0.00
Received By jgomez Date 2019-05-21 Time 14:55 Sent To I
Notes
2019-05-22 14:55:23RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-16 Cont ID  
Sent By jgomez Date 2019-05-16 Time 10:14 Rev Time 0.00
Received By jgomez Date 2019-04-03 Time 10:00 Sent To I
Notes
2019-04-04 10:01:37R12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-05-24 Cont ID  
Sent By jgomez Date 2019-05-24 Time 08:37 Rev Time 0.00
Received By jgomez Date 2019-05-24 Time 08:37 Sent To  
Notes
2019-05-24 08:38:35$9,766.49 PAID. MU-2019-015618.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By jgomez Date 2019-05-16 Time 10:11 Rev Time 0.00
Received By jgomez Date 2019-05-16 Time 10:11 Sent To  
Notes
2019-05-16 10:12:02IMPACT FEES - PAPER SUBMITTALS
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-05-24 Cont ID  
Sent By jgomez Date 2019-05-24 Time 18:37 Rev Time 0.00
Received By jgomez Date 2019-05-24 Time 18:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-05-24 Cont ID  
Sent By jgomez Date 2019-05-24 Time 09:40 Rev Time 0.00
Received By jgomez Date 2019-05-24 Time 09:00 Sent To  
Notes
2019-05-24 09:40:24 
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
  
  
  
 NEW SINGLE FAMILY RESIDENCE R3) SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 NOTE:
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
  
 1- OK.
  
 ORIGINAL COMMENT:
 2- MASTER BEDROOM RETURN AIR DUCT DOESN'T COMPLY WITH
 SEC. M1602.3 FBC-RESIDENTIAL. NOTE: SEE EXCEPTION #3.
 REVISE SIZE OF DUCT AS REQUIRED.
  
 RESPONSE:
 SIZE OF DUCT WAS REDUCED FROM 10" TO 8". SIZE OF DUCT
 NEEDS TO BE INCREASED NOT DECREASED. REVISE AS
 REQUIRED.
  
 3-OK.
  
 4- OK.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 NOTE:
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By jgomez Date 2019-05-16 Time 10:09 Rev Time 0.00
Received By jgomez Date 2019-05-16 Time 09:41 Sent To  
Notes
2019-05-16 10:09:31NEW SINGLE FAMILY RESIDENCE R3) MECHANICAL REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED
 ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF
 THE BUILDING. AND, THE MANUFACTURER'S AND MODEL NUMBER
 SHALL BE SUBMITTED ALSO, ALONG WITH THE SENSIBLE AND
 TOTAL COOLING CAPACITIES AS REQUIRED BY SEC. R403.7.1
 FBC-ENERGY CONSERVATION.
  
 2- MASTER BEDROOM RETURN AIR DUCT DOESN'T COMPLY WITH
 SEC. M1602.3 FBC-RESIDENTIAL. NOTE: SEE EXCEPTION #3.
 REVISE SIZE OF DUCT AS REQUIRED.
  
 3- COOLING AND HEATING CAPACITY SHOWN ON EQUIPMENT
 LISTED ON SHEET M.1 DOESN'T MATCH COOLING AND HEATING
 INFORMATION SHOWN ON THE ENERGY CALCULATIONS. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- NUMBER OF CFM'S SHOWN ON THE FLOOR PLAN ON SHEET M.1
 DON'T MATCH CFM'S SHOWN ON THE EQUIPMENT LISTED ON SAME
 SHEET. REVISE AS REQUITED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-04-16 Cont ID  
Sent By thunt Date 2019-04-16 Time 16:10 Rev Time 0.00
Received By thunt Date 2019-04-16 Time 16:10 Sent To  
Notes
2019-04-16 16:11:33RED LINE ISOMETRIC TO CODE APPROVED WET VENTING

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2019-05-16 Cont ID  
Sent By jgomez Date 2019-05-16 Time 10:12 Rev Time 0.00
Received By jgomez Date 2019-05-16 Time 10:12 Sent To  
Notes
2019-05-16 10:14:00APPROVED ROOF SHINGLES FL10124-R20.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-05-09 Cont ID  
Sent By awooten Date 2019-05-09 Time   Rev Time 0.00
Received By awooten Date 2019-05-09 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-04-26 Cont ID  
Sent By awooten Date 2019-04-26 Time   Rev Time  
Received By awooten Date 2019-04-26 Time   Sent To  
Notes
2019-04-26 09:43:02***************************ZONING REVIEW
 FAILED************************
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 GROSS LOT SQUARE FOOTAGE MINUS
 BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
 ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 THE PROPOSED DRIVEWAY, POOL, MECHANICAL EQUIPMENT AND
 FENCE REQUIRE A SEPARATE PERMIT.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]