Plan Review Details - Permit 19040126
| Plan Review Stops For Permit 19040126 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-08-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-08-08 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-08-07 |
Time |
18:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-07-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-07-24 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-07-24 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2019-07-24 09:42:34 | PLAN | | | REVIEW COMMENTS | | | 1500 ELIZABETH AVE. SUITE A | | | LEVEL 3 ALTERATION | | | CHANGE OF OCCUPANCY (S-2 TO B) | | | FLOOD ZONE "AE", BFE 12.1' NAVD | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NOT COMPLIED. THE ELEVATION CERTIFICATE THAT WAS | | | SUBMITTED IS NOT ACCEPTABLE. SUBMIT AN ELECTRONIC | | | ELEVATION CERTIFICATE THAT HAS BEEN DIGITALLY SIGNED BY | | | THE SURVEYOR OR A PAPER ONE WITH THE SURVEYOR'S | | | ORIGINAL HANDWRITTEN SIGNATURE. | | | THE PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA. | | | BASED ON THE PBC PROPERTY APPRAISER'S IMPROVEMENT VALUE | | | ($456,220.00) OF THE BUILDING, THE COST OF THE PROPOSED | | | WORK ($835,735.00) EXCEEDS 50 PERCENT OF THE MARKET | | | VALUE OF THE STRUCTURE AND IS A SUBSTANTIAL | | | IMPROVEMENT. THEREFORE, THE RENOVATED BUILDING IS | | | REQUIRED TO COMPLY WITH THE CURRENT CITY FLOOD | | | ORDINANCE. THE LOWEST FLOOR ELEVATION AND ANY EQUIPMENT | | | SERVICING THE BUILDING IS REQUIRED TO BE AT OR ABOVE | | | 12.1' + 2' FREE BOARD= 14.1" NAVD 88. BECAUSE THIS IS A | | | COMMERCIAL BUILDING, IT CAN BE DRY FLOODPROOFED. SEE | | | FEMA PUBLICATION FEMA P-758. FBC 1612.1 | | | | | | 2) NOT COMPLIED. THE ENERGY CODE COMPLIANCE FORM THAT | | | WAS SUBMITTED IS NOT ACCEPTABLE. SUBMIT AN ENERGY CODE | | | COMPLIANCE FORM THAT HAS BEEN DIGITALLY SIGNED BY THE | | | SURVEYOR OR A PAPER ONE WITH THE ENGINEER'S ORIGINAL | | | HANDWRITTEN SIGNATURE. SUBMIT THE REQUIRED DOCUMENTS TO | | | SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION C401.2. | | | | | | 3) NOT COMPLIED. PROVIDE A SURVEY OF THE PROPERTY TO | | | CLARIFY THE ORIENTATION OF THE STRUCTURE AND VERIFY | | | DISTANCES TO LOT LINES. FBC 107.2 | | | | | | 4) COMPLIED. | | | | | | 5) NOT COMPLIED. THE UPLOADED PLAN SHEETS FOR S-1 AND | | | S-2 ARE INCORRECTLY LABELED IN PROJECT DOX. THE PLANS | | | ARE THE REVERSE OF THEIR PROJECT DOX TITLES. THE | | | FOUNDATION PLAN ON THE ACTUAL PLAN SHEET S-1 IS NOT | | | ORIENTED WITH THE COMPASS ROSE. | | | ON SHEET S-1 THE COMPASS ROSE DOES NOT APPEAR TO BE | | | ACCURATE. THE FRONT OF THE BUILDING FACES WEST AND ON | | | SHEET S-1 IT IS INDICATED AS FACING SOUTH. FBC 107.2.1 | | | | | | 6) NOT COMPLIED. I MADE A MISTAKE AND TYPED IN THE | | | WRONG PLAN SHEET. THE ELEVATIONS THAT NEED CORRECTIONS | | | ARE ON SHEET A-3.0.1 | | | THE ELEVATIONS ON SHEET SP-1.0.0 APPEAR TO BE REVERSED. | | | THE WEST ELEVATION SHOULD BE THE FRONT OF THE BUILDING | | | WHICH FACES TOWARDS ELIZABETH AVE. FBC 107.2.1 | | | | | | 7) COMPLIED. | | | | | | 8) COMPLIED. | | | | | | 9) COMPLIED. | | | | | | 10) COMPLIED. | | | | | | 11) NOT COMPLIED. THE COMMON PATH OF TRAVEL IS SHOWN | | | STARTING IN THE HALL. IT SHOULD START IN STUDIO 21 AT | | | THE SAME PLACE THE TRAVEL DISTANCE STARTS. THIS WILL | | | ADD APPROXIMATELY 17' TO THE 40'-4" THAT IS SHOWN. | | | THE COMMON PATH OF TRAVEL IS NOT SHOWN CORRECTLY ON THE | | | LIFE SAFETY PLAN. FBC 107.2 & CHAPTER 2 DEFINITIONS | | | COMMON PATH OF EGRESS TRAVEL. THAT PORTION OF THE EXIT | | | ACCESS TRAVEL DISTANCE MEASURED FROM THE MOST REMOTE | | | POINT WITHIN A STORY TO THAT POINT WHERE THE OCCUPANTS | | | HAVE SEPARATE AND DISTINCT ACCESS TO TWO EXITS OR EXIT | | | ACCESS DOORWAYS. | | | | | | 12) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | 13) NEW COMMENT. WITHOUT THE SURVEY REQUESTED IN | | | COMMENT NUMBER 3, IT IS NOT POSSIBLE FOR ME TO | | | DETERMINE THAT THE REAR EXIT DISCHARGE PROVIDES A | | | DIRECT AND UNOBSTRUCTED ACCESS TO A PUBLIC WAY AS | | | REQUIRED BY FBC 1028.5. INDICATE HOW COMPLIANCE WILL BE | | | ACHIEVED. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-05-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-05-20 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-05-20 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2019-05-20 14:45:48 | PLAN | | | REVIEW COMMENTS | | | 1500 ELIZABETH AVE. SUITE A | | | LEVEL 3 ALTERATION | | | CHANGE OF OCCUPANCY (S-2 TO B) | | | FLOOD ZONE "AE", BFE 12.1' NAVD | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA. BASED ON THEPBC PROPERTY APPRAISER'S IMPROVEMENT | | | VALUE ($456,220.00) OF THE BUILDING, THE COST OF THE | | | PROPOSED WORK ($835,735.00) EXCEEDS 50 PERCENT OF THE | | | MARKET VALUE OF THE STRUCTURE AND IS A SUBSTANTIAL | | | IMPROVEMENT. THEREFORE, THE RENOVATED BUILDING IS | | | REQUIRED TO COMPLY WITH THE CURRENT CITY FLOOD | | | ORDINANCE. THE LOWEST FLOOR ELEVATION AND ANY EQUIPMENT | | | SERVICING THE BULDING IS REQUIRED TO BE AT OR ABOVE | | | 12.1' + 2' FREE BOARD= 14.1" NAVD 88. BECASE THIS IS A | | | COMMERCIAL BUILDING, IT CAN BE DRY FLOODPROOFED. SEE | | | FEMA PUBLICATION FEMA P-758. FBC 1612.1 | | | | | | 2) SUBMIT THE REQUIRED DOCUMENTS TO SHOW COMPLIANCE | | | WITH FBC ENERGY CONSERVATION C401.2. | | | | | | 3) PROVIDE A SURVEY OF THE PROPERTY TO CLARIFY THE | | | ORIENTATION OF THE STRUCTURE AND VERIFY DISTANCES TO | | | LOT LINES. FBC 107.2 | | | | | | 4) PROVIDE A COMPASS ROSE ON THE FLOOR PLAN A-1.1 TO | | | SHOW THE ORIENTATION OF THE BUILDING. FBC 107.2 | | | | | | 5) ON SHEET S-1 THE COMPASS ROSE DOES NOT APPEAR TO BE | | | ACCURATE. THE FRONT OF THE BUILDING FACES WEST AND ON | | | SHEET S-1 IT IS INDICATED AS FACING SOUTH. FBC 107.2.1 | | | | | | 6) THE ELEVATIONS ON SHEET SP-1.0.0 APPEAR TO BE | | | REVERSED. THE WEST ELEVATION SHOULD BE THE FRONT OF THE | | | BUILDING WHICH FACES TOWARDS ELIZABETH AVE. FBC 107.2.1 | | | | | | 7) PROVIDE THE DIMENSIONS FOR THE ACCESSIBLE RAMP AND | | | LANDING ON THE PLANS. FBC ACCESSIBILITY 405 | | | | | | 8) KEYNOTE 2 ON SHEET A-1.1 SPECIFIES NEW ALUMINUM | | | RAILING AT 36" ABOVE FINISH FLOOR. FBC 1015.3 REQUIRES | | | 42" FOR GUARDS AND FBC 1014.2 REQUIRES 34" TO 36" FOR | | | HANDRAILS. | | | | | | 9) FBC 405.7 REQUIRES THE LANDINGS AT RAMPS TO BE A | | | CLEAR LENGTH OF 60" LONG MINIMUM. | | | | | | 10) SOME OF THESE ITEMS WERE NOT PROVIDED OR WERE SHOWN | | | INCORRECTLY ON THE LIFE SAFETY PLANS. | | | THE LIFE SAFETY PLANS NEED TO SHOW THE FOLLOWING: | | | A) NUMBER OF OCCUPANTS IN EACH AREA FBC 1004.1 | | | B) CUMULATIVE OCCUPANT LOADS FBC 1004.1.1 | | | C) EXIT SEPARATION DISTANCE FBC 1015.2.1 | | | D) COMMON PATH OF EGRESS TRAVEL DISTANCE FBC 1014.3 | | | E) EXIT ACCESS TRAVEL DISTANCE FBC 1016.3 | | | F) CLEAR WIDTH OF THE EXIT OR EXIT ACCESS DOORS FBC | | | 1008.1.1 | | | G) CAPACITY OF EGRESS DOORS, OCCUPANT LOAD SERVED AND | | | MEANS OF EGRESS FACTOR FBC1005.3.2 | | | H) DISTRIBUTION OF EGRESS CAPACITY FBC1005.5 | | | | | | 11) THE COMMON PATH OF TRAVEL IS NOT SHOWN CORRECTLY ON | | | THE LIFE SAFETY PLAN. FBC 107.2 & CHAPTER 2 DEFINITIONS | | | COMMON PATH OF EGRESS TRAVEL. THAT PORTION OF THE EXIT | | | ACCESS TRAVEL DISTANCE MEASURED FROM THE MOST REMOTE | | | POINT WITHIN A STORY TO THAT POINT WHERE THE OCCUPANTS | | | HAVE SEPARATE AND DISTINCT ACCESS TO TWO EXITS OR EXIT | | | ACCESS DOORWAYS. | | | | | | 12) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-08-08 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-08-08 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-08-08 |
Time |
09:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-07-18 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-07-18 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2019-07-18 16:02:49 | NEEDS TO BE SIGNED JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-05-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-05-06 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-05-06 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2019-05-06 11:57:49 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | PG.E1.1 | | | | | | AIC RATING FOR SERVICE SHOW CALCULATION. | | | | | | 110.24 AVAILABLE FAULT CURRENT | | | ( A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN | | | DWELLING | | | UNITS SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE | | | MAXIMUM | | | AVAILABLE FAULT CURRENT. THE FIELD MARKING(S) SHALL | | | INCLUDE THE DATE | | | THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF | | | SUFFICIENT | | | DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. | | | | | | SWITCHGEAR TO CONTAIN ARC FLASH INFORMATION AND LABELS | | | 110.16 ARC-FLASH HAZARD WARNING | | | ELECTRICAL EQUIPMENT, SUCH AS SWITCHBOARDS, SWITCHGEAR, | | | PANELBOARDS, | | | INDUSTRIAL CONTROL PANELS, METER SOCKET ENCLOSURES, | | | AND MOTOR CONTROL CENTERS, THAT ARE IN OTHER THAN | | | DWELLING UNITS, | | | AND ARE LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, | | | SERVICING, OR | | | MAINTENANCE WHILE ENERGIZED, SHALL BE FIELD OR FACTORY | | | MARKED | | | TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC | | | FLASH HAZARDS. | | | THE MARKING SHALL MEET THE REQUIREMENTS IN 110.21(B) | | | AND | | | SHALL BE LOCATED SO AS TO BE CLEARLY VISIBLE TO | | | QUALIFIED PERSONS | | | BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR | | | MAINTENANCE OF | | | THE EQUIPMENT. | | | | | | | | | PG.E1.2 | | | | | | ALL OUTLETS WITHIN 6' OF A SINK TO BE GFCI RPOTECTED. | | | | | | 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION | | | FOR PERSONNEL | | | (B) OTHER THAN DWELLING UNITS. ALL 125-VOLT, | | | SINGLE-PHASE, | | | 15- AND 20-AMPERE RECEPTACLES INSTA LLED IN THE | | | LOCATIONS SPECIFIED | | | IN 210.8(B)(1) THROUGH (8) SHALL HAVE GROUND-FAULT | | | CIRCUITINTERRUPTER | | | PROTECTION FOR PERSONNEL. | | | (5) SINKS ? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 | | | M (6 FT) | | | OF THE OUTSIDE EDGE OF THE SINK. | | | | | | ALL LOW VOLTAGE WORK TO BE PERMITTED SEPARATELY. | | | CCTV | | | | | | | | | PG. E1.4 | | | | | | EACH ROOM HAS A BLACK SQUARE WHAT DOES THIS STAND FOR? | | | SYMBOL | | | | | | PROVIDE INTERIOR LIGHTING CALCULATION SHOWING | | | COMPLIANCE WITH THE FBC ENERGY CODE. FBC CE 405.5 | | | | | | PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED IN | | | THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE | | | OCCUPANCY SENSORS REQUIRED. FBC CE 405.2.2, 405.2.2.2 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2019-08-08 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-08-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-08-08 |
Time |
09:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2019-06-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-06-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-06-19 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2019-06-19 12:56:47 | 2ND REVIEW COMMENTS | | | | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | SOME OF THE PREVIOUS COMMENTS WERE NOT ADDRESSED AND | | | ARE BEING RESTATED BELOW: | | | | | | | | | 1) SHEET ALS 1.1 - THERE IS AN INDICATION THAT THIS | | | PROJECT WILL BE FIRE SPRINKLERED. THERE IS NOT AN | | | INDICATION OF AN EXISTING SYSTEM. | | | | | | HOWEVER, THERE IS A NOTE INDICATING THAT THERE IS A | | | FIRE MAIN STUB IN THE SPACE. THIS IS A NEW SYSTEM | | | INSTALLATION AND REQUIRES 61G DOCUMENTS FOR THE EOR PER | | | F.A.C. | | | | | | NEW COMMENT: FIRE SPRINKLER DOCUMENTS PER THE F.A.C. | | | SHALL BE SUBMITTED WITH THIS MASTER PERMIT. SHOP | | | DRAWINGS SHALL BE SUBMITTED UNDER SEPARATE PERMIT BASED | | | OFF OF THE EOR REQUIREMENTS PER THE F.A.C. WITH THIS | | | MASTER PERMIT. | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING | | | DOCUMENTS. | | | (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF | | | PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR | | | INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING | | | PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER?S | | | RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31, | | | 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING | | | CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE AHJ. THE DOCUMENTS SHALL INCLUDE: | | | (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS | | | REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A | | | RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND | | | EXPERIENCE. | | | (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY | | | STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH | | | THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS | | | ARE INTENDED TO CONFORM TO. | | | (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF | | | RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF | | | THE SYSTEM. | | | (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT | | | SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING | | | DOCUMENTS. | | | (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY | | | FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE | | | ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE | | | STATED PURPOSE OF THESE RESPONSIBILITY RULES. | | | (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND | | | BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING | | | DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR | | | CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE | | | OF SUCH DOCUMENTS. | | | (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN | | | ENGINEERING DOCUMENT ONLY FOR INFORMATION OR | | | CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO | | | ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER | | | SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS | | | RESPONSIBILITY. | | | (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY | | | DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST | | | ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS. | | | (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY | | | ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN | | | FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC | | | AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND | | | INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE | | | REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES | | | WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE | | | AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A | | | PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR | | | AGENCY APPROVAL ACTION ON THE SAME PROJECT. | | | SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW | | | IMPLEMENTED 471.033(1)(G), 471.025(3) FS. HISTORY?NEW | | | 1-26-93, FORMERLY 21H-30.003, AMENDED 11-13-08. | | | | | | 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION | | | SYSTEMS. | | | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT | | | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, | | | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE | | | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE | | | WATER MAINS AND DEDICATED FIRE PROTECTION WATER | | | SOURCES. | | | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION | | | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL | | | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN | | | APPLICABLE: | | | (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER | | | SUPPLY AS DEFINED BY 633.021(18) F.S. | | | (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE | | | CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING | | | STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND | | | CONCLUSIONS. | | | (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA. | | | (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, | | | DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR | | | EACH SEPARATE 42 HAZARD OCCUPANCY. | | | (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS | | | MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR | | | CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE | | | NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM | | | DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY | | | DEMANDING DESIGN AREA. | | | (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE | | | FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO | | | CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, | | | STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH | | | RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND | | | LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF | | | SERVICE. | | | (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE | | | POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF | | | WATER. | | | (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF | | | RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER | | | SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION | | | (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE | | | LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY | | | WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY | | | TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND | | | THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE | | | PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE | | | MEASURES. | | | (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND | | | DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS | | | INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. | | | (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD | | | AND INTERIOR FIRE PROTECTION COMPONENTS. | | | (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE | | | MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL | | | DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING | | | APPROVAL AND DOCUMENTATION. | | | (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE | | | INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE | | | OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL | | | ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE | | | CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. | | | SPECIFIC AUTHORITY 471.008, 471.033(2), FS | | | LAW IMPLEMENTED 471.005(7), 471.033(2), FS | | | HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED | | | 4-2-2000, 6-26-01, 7-12-05 | | | | | | PLEASE REVIEW AND PROVIDE THE REQUIRED DOCUMENTS WITH | | | THIS MASTER PERMIT. | | | | | | NEW COMMENT: THE EOR FIRE SPRINKLER DOCUMENTS MAY BE | | | SUBMITTED IN NARRATIVE OR PLAN DRAWINGS AND SHALL MEET | | | THE REQUIRMENTS NOTED ABOVE PER F.A.C. AND MUST BE | | | SUBMITTED AS PART OF THIS MASTER PERMIT. | | | | | | | | | | | | 2) SHEET A1 3.1 - THE DOOR SCHEDULE HAS SYMBOLS THAT DO | | | NOT CORRESPOND TO ANY DOOR INDICATORS. | | | | | | ADDITIONALLY, I WAS UNABLE TO INDENTIFY ANY DOOR | | | INDICATORS ON ANY SHEET. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | NEW COMMENT: THIS COMMENT HAS NOT BEEN ADDRESSED. THE | | | ALPHABETICAL SYMBOLS FOR EACH DOOR IN THE DOOR SCHEDULE | | | DO NOT CORRESPOND TO ANY DOOR ON ANY FLOOR PLAN ON ANY | | | SHEET. | | | | | | PLEASE CORRECT. | | | | | | 3) SHEET A 1.1 & 3.1 - THERE ARE TWO DOORS INDICATED IN | | | THE HALL THAT ARE WITHIN THE EXIT ACCESS. THESE DOORS | | | DO NOT HAVE INDICATORS TO CONFIRM THE HARDWARE/LOCKS | | | THAT MEET THE REQUIREMENTS OF NFPA 101, CH 7, MEANS OF | | | EGRESS. | | | | | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED | | | READILY FROM | | | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. | | | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY | | | TO DOOR | | | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO | | | ELEVATED | | | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON | | | LABORATORY | | | FIRE TEST PROCEDURES. | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | | OF A KEY, A | | | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM | | | THE EGRESS | | | SIDE. | | | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 | | | SHALL NOT | | | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH | | | 23. | | | | | | NEW COMMENT: THIS COMMENT HAS NOT BEEN ADDRESSED AND | | | REMAINS BECAUSE #2 ABOVE HAS NOT BEEN CORRECTED. HOW DO | | | I KNOW WHAT HARDWARE GOES WITH WHAT DOOR IF THEY ARE | | | NOT CORRECTLY IDENTIFIED AND LABLED TO MATCH THE DOOR | | | SCHEDULE. | | | | | | PLEASE CORRECT | | | | | | 4) CORRECTED; NO NEW COMMENT. | | | | | | | | | | | | 5) ELECTIRCAL SHEETS - THERE ARE NO INDICATIONS OF A | | | FIRE SPRINKLER ALARM. A FIRE SPRINKLER SYSTEM IS | | | REQUIRED TO BE MONITORED. | | | | | | 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. | | | 9.6.1* GENERAL. | | | 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY | | | WHERE | | | SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS CODE | | | OR WHERE | | | SUPERVISION OF A NEW FIRE SPRINKLER SYSTEM OR NEW FIRE | | | ALARM | | | SYSTEM IS REQUIRED BY THE FLORIDA BUILDING CODE. | | | | | | THE SYSTEM SHALL BE INSTALLED UNDER SEPARARTE PERMIT | | | AND SHOP DRAWINGS. | | | | | | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF | | | ACKNOWLEDGEMENT. | | | | | | NEW COMMENT: COMMENT NOT ADDRESSED, PLEASE PROVIDE AN | | | APPLICABLE COMMENT. | | | | | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | COMMENT REMAINS. | | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | COMMENT REMAINS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-04-09 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-04-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-04-08 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2019-04-09 13:10:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET ALS 1.1 - THERE IS AN INDICATION THAT THIS | | | PROJECT WILL BE FIRE SPRINKLERED. THERE IS NOT AN | | | INDICATION OF AN EXISTING SYSTEM. | | | | | | HOWEVER, THERE IS A NOTE INDICATING THAT THERE IS A | | | FIRE MAIN STUB IN THE SPACE. THIS IS A NEW SYSTEM | | | INSTALLATION AND REQUIRES 61G DOCUMENTS FOR THE EOR PER | | | F.A.C. | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING | | | DOCUMENTS. | | | (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF | | | PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR | | | INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING | | | PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER?S | | | RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31, | | | 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING | | | CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE AHJ. THE DOCUMENTS SHALL INCLUDE: | | | (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS | | | REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A | | | RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND | | | EXPERIENCE. | | | (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY | | | STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH | | | THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS | | | ARE INTENDED TO CONFORM TO. | | | (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF | | | RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF | | | THE SYSTEM. | | | (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT | | | SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING | | | DOCUMENTS. | | | (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY | | | FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE | | | ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE | | | STATED PURPOSE OF THESE RESPONSIBILITY RULES. | | | (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND | | | BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING | | | DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR | | | CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE | | | OF SUCH DOCUMENTS. | | | (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN | | | ENGINEERING DOCUMENT ONLY FOR INFORMATION OR | | | CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO | | | ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER | | | SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS | | | RESPONSIBILITY. | | | (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY | | | DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST | | | ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS. | | | (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY | | | ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN | | | FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC | | | AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND | | | INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE | | | REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES | | | WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE | | | AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A | | | PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR | | | AGENCY APPROVAL ACTION ON THE SAME PROJECT. | | | SPECIFIC AUTHORITY 471.033(2), 471.008 FS. LAW | | | IMPLEMENTED 471.033(1)(G), 471.025(3) FS. HISTORY?NEW | | | 1-26-93, FORMERLY 21H-30.003, AMENDED 11-13-08. | | | | | | 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION | | | SYSTEMS. | | | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT | | | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, | | | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE | | | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE | | | WATER MAINS AND DEDICATED FIRE PROTECTION WATER | | | SOURCES. | | | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION | | | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL | | | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN | | | APPLICABLE: | | | (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER | | | SUPPLY AS DEFINED BY 633.021(18) F.S. | | | (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE | | | CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING | | | STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND | | | CONCLUSIONS. | | | (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA. | | | (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, | | | DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR | | | EACH SEPARATE 42 HAZARD OCCUPANCY. | | | (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS | | | MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR | | | CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE | | | NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM | | | DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY | | | DEMANDING DESIGN AREA. | | | (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE | | | FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO | | | CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, | | | STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH | | | RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND | | | LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF | | | SERVICE. | | | (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE | | | POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF | | | WATER. | | | (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF | | | RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER | | | SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION | | | (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE | | | LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY | | | WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY | | | TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND | | | THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE | | | PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE | | | MEASURES. | | | (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND | | | DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS | | | INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. | | | (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD | | | AND INTERIOR FIRE PROTECTION COMPONENTS. | | | (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE | | | MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL | | | DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING | | | APPROVAL AND DOCUMENTATION. | | | (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE | | | INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE | | | OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL | | | ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE | | | CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. | | | SPECIFIC AUTHORITY 471.008, 471.033(2), FS | | | LAW IMPLEMENTED 471.005(7), 471.033(2), FS | | | HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED | | | 4-2-2000, 6-26-01, 7-12-05 | | | | | | PLEASE REVIEW AND PROVIDE THE REQUIRED DOCUMENTS WITH | | | THIS MASTER PERMIT. | | | | | | | | | | | | 2) SHEET A1 3.1 - THE DOOR SCHEDULE HAS SYMBOLS THAT DO | | | NOT CORRESPOND TO ANY DOOR INDICATORS. | | | | | | ADDITIONALLY, I WAS UNABLE TO INDENTIFY ANY DOOR | | | INDICATORS ON ANY SHEET. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | 3) SHEET A 1.1 & 3.1 - THERE ARE TWO DOORS INDICATED IN | | | THE HALL THAT ARE WITHIN THE EXIT ACCESS. THESE DOORS | | | DO NOT HAVE INDICATORS TO CONFIRM THE HARDWARE/LOCKS | | | THAT MEET THE REQUIREMENTS OF NFPA 101, CH 7, MEANS OF | | | EGRESS. | | | | | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED | | | READILY FROM | | | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. | | | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY | | | TO DOOR | | | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO | | | ELEVATED | | | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON | | | LABORATORY | | | FIRE TEST PROCEDURES. | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | | OF A KEY, A | | | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM | | | THE EGRESS | | | SIDE. | | | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 | | | SHALL NOT | | | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH | | | 23. | | | | | | | | | | | | 4) SHEET E 1.4 - THERE ARE NO INDICATIONS OF EXIT SIGNS | | | WITHIN THE HALL THAT HAS DOORS AT EACH END. | | | | | | PER NFPA 101 CH 7 | | | | | | 7.10 MARKING OF MEANS OF EGRESS. | | | 7.10.1 GENERAL. | | | 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE | | | MARKED IN | | | ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS | | | 11 | | | THROUGH 43. | | | 7.10.1.2 EXITS. | | | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS | | | THAT OBVIOUSLY | | | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED | | | BY AN APPROVED | | | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT | | | ACCESS. | | | | | | 7.10.1.5 EXIT ACCESS. | | | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, | | | READILY | | | VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO | | | REACH THE EXIT IS | | | NOT READILY APPARENT TO THE OCCUPANTS. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | 5) ELECTIRCAL SHEETS - THERE ARE NO INDICATIONS OF A | | | FIRE SPRINKLER ALARM. A FIRE SPRINKLER SYSTEM IS | | | REQUIRED TO BE MONITORED. | | | | | | 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. | | | 9.6.1* GENERAL. | | | 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY | | | WHERE | | | SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS CODE | | | OR WHERE | | | SUPERVISION OF A NEW FIRE SPRINKLER SYSTEM OR NEW FIRE | | | ALARM | | | SYSTEM IS REQUIRED BY THE FLORIDA BUILDING CODE. | | | | | | THE SYSTEM SHALL BE INSTALLED UNDER SEPARARTE PERMIT | | | AND SHOP DRAWINGS. | | | | | | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF | | | ACKNOWLEDGEMENT. | | | | | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2019-08-08 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-08-08 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-08-08 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2019-08-08 11:20:00 | GAS COMMENTS: APPROVED | | | | | | REFER TO FG-01 AND FG-02 FLUE VENT DETAIL AND | | | CONCENTRIC PIPE KIT IN DOCUMENTS FOR THROUGH THE ROOF | | | VENTING | | | | | | FUEL GAS PROVISO | | | PROVIDE DETAIL UNDER DEFERRED SUBMITTAL FOR | | | MANUFACTURER?S RECOMMENDATION TO CONNECT CONCENTRIC | | | VENT KIT TO WATER HEATER(S) PRIOR TO 1ST INSPECTION | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2019-07-11 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-07-11 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-07-11 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2019-07-11 12:55:25 | 2ND REVIEW: 19031394 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | GAS COMMENTS: | | | | | | | | | | | | 6. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF | | | VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE | | | THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER | | | 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES. | | | SEC.G2426 THROUGH G2439. SHT. P1.1 SHOWS A SINGLE TYPE | | | B DOUBLE WALL VENT SHT P1.4 SHOWS SCHEDULE 40 PVC | | | INTAKE AND EXHAUST PLEASE CLARIFY | | | | | | 7. SUBMIT TWO COPIES OF THE MANUFACTURER?S | | | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS | | | EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE | | | SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED. THE | | | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT | | | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC | | | SEC.305.1, FBC-RES. SEC.G2408.1 | | | SHT. P1.4 SHOWS SPEC FOR VENTS AND MOUNTING RACK BUT | | | NOT WATER HEATERS PLEASE PROVIDE SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR WATER HEATERS. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2019-05-01 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-05-01 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-05-01 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2019-05-01 14:02:40 | | | | 1ST REVIEW: 19031394 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | GAS COMMENTS: | | | | | | 1. SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE | | | PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 | | | FBC-R SEC. G2413.4.1, G2413.4.2. | | | | | | 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE | | | CORRUGATED STAINLESS STEEL TUBING | | | | | | (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO | | | FBC SEC.107.2.1. | | | 3. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS | | | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) | | | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES | | | G2413.4 (1 ) THROUGH G2413.4 (21). | | | | | | 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS | | | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 | | | FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. | | | SEC. G 2413.4.1, G2413.4.2. | | | | | | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 | | | FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR | | | 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES | | | DRYERS). | | | | | | 6. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF | | | VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE | | | THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER | | | 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES. | | | SEC.G2426 THROUGH G2439. | | | | | | 7. SUBMIT TWO COPIES OF THE MANUFACTURER?S | | | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS | | | EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE | | | SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED. THE | | | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT | | | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC | | | SEC.305.1, FBC-RES. SEC.G2408.1 | | | | | | | | | 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE | | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL | | | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) | | | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, | | | G2413.1, G2413.2, & G2413.3. | | | | | | 9) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | | AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS | | | SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. | | | | | | | | | | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-08-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-08-09 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-08-07 |
Time |
15:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-07-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-07-24 |
Time |
17:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-06-17 |
Time |
10:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2019-05-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-05-20 |
Time |
18:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-04-03 |
Time |
16:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2019-08-22 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2019-08-22 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-08-09 |
Time |
07:51 |
Sent To |
|
|
| Notes |
| 2019-08-22 14:40:46 | SEE ATTACHED EMAIL FROM WSWOOPE AT IMPACT FEES - PER | | | WSWOOPE CUSTOMER IS ASKING FOR REDUCTION AND HE HAS | | | AGREED TO ALLOW FOR ISSUANCE WITHOUT PAYMENT. LEM | | 2019-08-09 07:51:40 | 8/9/19 SENT EMAIL TO IMPACT FEE OFFICE. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2019-05-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-05-20 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-05-20 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2019-05-20 11:19:41 | CHANGE OF OCCUPANCY, IMPACT FEE REVIEW IS REQIRED. | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2019-08-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-08-08 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-08-08 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2019-08-08 14:32:32 | REVIEWED BY C.COLE REMOTELY | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-07-18 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-07-18 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2019-07-18 13:18:25 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #19040126 | | | 7/18/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | THE FOLLOWING REVIEW COMMENTS ARE BASED ON REVIEW OF | | | THE RESUBMITTED PLANS AND THE SUBMITTED NARRATIVE BY | | | THE EOR DON PENN IN RESPONSE TO THE 1ST REVIEW | | | COMMENTS. | | | | | | 1) M1.1: RECIRCULATION OF AIR FROM THE SALONS TO THE | | | COMMON AREAS- ENTRY HALL, CORRIDORS, AND BREAKROOM IS | | | PROHIBITED PER TABLE 403.3.1.1 FOOTNOTE B FBC M. | | | | | | 2) M1.3: PROVIDE THE SIZES OF THE MAIN EXHAUST DUCTS | | | FROM THE SALONS TO THE ROOF FANS EF-3 & EF-4. | | | | | | 3) M1.3: PROVIDE THE SEQUENCES OF OPERATION FOR THE | | | EF-3 & EF-4. IT APPEARS BY THE DESIGN THAT THE FANS | | | WILL HAVE TO RUN CONTINOUSLY WHEN THE SALON IS OPEN. | | | WILL THE FANS BE INTERLOCKED WITH THE AC OR LIGHTING | | | SYSTEMS- SEE SECTION 501.4 FBC M. | | | | | | 4) M1.1: BASED ON THE SUBMITTED SPECIFICATIONS FOR THE | | | DRYERS, MAKEUP AIR FOR EXHAUST IS REQUIRED. THE PLAN | | | SHOWS AN EQUAL AMOUNT OF SUPPLY AND RETURN AIR IN THE | | | ROOM. PLEASE NOTE THAT CFMS SHOWN IN THE AIR BALANCE | | | SCHEDULE ON SHEET M1.3 DO NOT MATCH THE CFMS ON THE | | | M1.1 PLAN. | | | | | | 5) M1.1 & M1.2: IN REFERENCE TO COMMENT #4 FROM THE 1ST | | | REVIEW, PLEASE PROVIDE MANUFACTURER'S DATA SHEETS TO | | | VERIFY THE 5-TON AC SYSTEMS CANNOT PRODUCE MORE 2000 | | | CFMS OF SUPPLY AIR, OR PROVIDE THE DS DETECTORS. | | | | | | 6) M1.1: THE EXHAUST DETAIL APPEARS TO SHOW FLEX DUCTS | | | BEING USED FOR TOILET EXHAUST, HOWEVER METAL DUCTWORK | | | IS REQUIRED PER SMACNA HVAC CONSTRUCTION STANDARDS. | | | | | | 7) IN REFERENCE TO COMMENT #8 FROM THE 1ST REVIEW, THE | | | REQUESTED AC CALCULATIONS WERE NOT PROVIDED, HOWEVER | | | ENERGY CALCULATIONS WERE PROVIDED. | | | | | | 8) M1.2: IN REFERENCE TO COMMENT #9 FROM THE 1ST REVIEW | | | THE REQUESTED WIND LOAD ENGINEERING HAS NOT BEEN | | | COMPLETELY PROVIDED. A) NOTE #5 DOES NOT INDICATE THE | | | TYPE AND SIZE OF SCREWS FOR ATTACHING THE RTU'S TO THE | | | CURBS. B) STRUCTURAL DETAILS FOR ATTACHING THE CURBS TO | | | THE ROOF STRUCTURE NOT PROVIDED. C) WIND DESIGN | | | CRITERIA NOT PROVIDED. D) STRUCTURAL DETAILS AND/OR | | | NOA'S FOR THE ROOFTOP PLANS NOT PROVIDED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-05-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-05-03 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-05-03 |
Time |
12:43 |
Sent To |
|
|
| Notes |
| 2019-05-03 15:23:52 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19040126 | | | 5/3/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS M1.1 & M1.2: AN EXHAUST VENTILATION SYSTEM AT | | | A RATE OF 0.6 CFMS PER SQUARE FOOT IS REQUIRED FOR THE | | | BEAUTY SALON PER TABLE 403.3.1.1 FBC M. PLEASE REVISE | | | THE PLANS TO SHOW THE REQUIRED SYSTEM, AND PROVIDE | | | CALCULATIONS, SPECIFICATIONS AND EQUIPMENT SCHEDULES. | | | | | | 2) M1.1 & M1.2: PROVIDE OUTDOOR AIR CALCULATIONS FOR | | | ALL OCCUPIED ROOMS AND SPACES OF THE SALON PER TABLE | | | 403.3.1.1. FBC M. DUE TO THE AMOUNT OF EXHAUST REQUIRED | | | FOR THE SALON, ALONG WITH THE LAUNDRY EXHAUST PLEASE | | | PROVIDE AIR BALANCE CALCULATIONS. | | | | | | 3) M1.1 & M1.2: PROVIDE AUTOMATICALLY CONTROLLED | | | SHUTOFF DAMPERS FOR THE O/A INTAKES- SECTION C403.2.4.3 | | | FBC-17 ENERGY CONSERVATION. | | | | | | 4) M1.1 & M1.2: DUCT SMOKE DETECTORS ARE REQUIRED IN | | | THE SUPPLY AIR SYSTEMS OF EACH 5-TON AC SYSTEM PER | | | SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION | | | CAN BE APPLIED IF THE MANUFACTURER'S SPECIFICATIONS | | | INDICATE SYSTEMS ARE NOT CAPABLE OF PRODUCING OVER 2000 | | | CFMS OF SUPPLY AIR. | | | | | | 5) M1.1 & M1.2: THE PLAN APPEARS TO INDICATE AN ABOVE | | | CEILING PLENUM. PLEASE PLACE A NOTE ON THE PLAN TO | | | CLARIFY, AND ALSO NOTE THAT THE CORRIDORS SHALL NOT BE | | | USED AS A MEANS OF RETURN AIR VIA TRANSFER DUCTS OR | | | JUMPERS FORM THE ROOMS. | | | | | | 6) M1.1 & M1.2: SUBMIT MANUFACTURER?S SPECIFICATIONS | | | FOR THE DRYESR, AND PROVIDE A DRYER EXHAUST DIAGRAM | | | SHOWING THE TOTAL RUN LENGTH OF THE DUCTS FROM THE | | | DRYER OUTLEST TO THE TERMINATION LOCATION- SECTIONS | | | 504.1 AND 504.8.4 FBC M. PLEASE NOTE THAT MAKEUP AIR IS | | | REQUIRED FOR DRYERS EXHAUSTING MORE THAN 200 CFMS- | | | SECTION 504.6 FBC M. | | | | | | 7) M1.1 & M1.2: PLEASE VERIFY THE INSTALLATION | | | LOCATIONS OF THE GAS-FRIED WATER HEATERS ARE NOT IN A | | | RETURN AIR PLENUM SPACE- SECTION 602.1 FBC M. A) | | | INDICATE HOW COMBUSTION AIR WILL BE PROVIDED FOR THE | | | WATER HEATERS AND PROVIDE CALCU;LATIONS- SECTION 304 | | | FBC FG. B) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | WATER HEATERS AND FLUE VENT- SECTION 624.1 FBC FG. | | | | | | 8) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. | | | | | | 9) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF | | | THE RTU'S- SECTION 310.15 FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
P |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-07-18 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-07-18 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2019-07-18 13:54:25 | BUILDING PROVISO | | | | | | AFTER THE CONSTRUCTION IS COMPLETE, A FINAL ELEVATION | | | CERTIFICATE BASED ON FINISHED CONSTRUCTION IS REQUIRED | | | TO BE SUBMITTED AND APPROVED PRIOR TO THE ISSUANCE OF A | | | CERTIFICATE OF OCCUPANCY. | | | | | | | | | | | | THE ELEVATION CERTIFICATE THAT WAS SUBMITTED PRIOR TO | | | THE REMODEL/CHANGE OF OCCUPANCY CONSTRUCTION SHOWS THAT | | | THE BUILDING AND THE LOWEST ADJACENT GRADE IS ABOVE THE | | | REQUIRED BFE OF 12.1 FT. |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2019-05-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-05-15 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-05-15 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2019-05-15 09:18:54 | THIS BUILDING IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA. THE FLOOD ZONE IS AE AND THE BFE IS 12.1' NAVD | | | 88. THE CITY OF WEST PALM BEACH FLOOD ORDINANCE | | | REQUIRES A TWO (2) FOOT FREE BOARD. ALL NEW | | | CONSTRUCTION OR SUBSTANTIALLY IMPROVEMENTED EXISTING | | | BUILDINGS ARE REQUIRED TO COMPLY WITH THE CITY'S FLOOD | | | ORDINANCE AND EITHER BE RAISED TO OR ABOVE THE BFE PLUS | | | TWO FEET OR COMMERCIAL BUILDINGS CAN BE DRY FLOOD | | | PROOFED. THE PROPOSED IMPROVEMENT ($835,735.00) APPEARS | | | TO BE A SUBSTANTIAL IMPROVEMENT BASED ON PROPERTY | | | APPRAISER VALUATION FOR THE STRUCTURE ($456,220.00). IF | | | THIS IS A SUBSTANTIAL IMPROVEMENT, THE STRUCTURE IS TO | | | BE BROUGHT INTO COMPLIANCE (BFE 12.1' + 2'=14.1' NAVD88 | | | FOR FINISHED FLOOR, ALL MECHANICAL EQUIPMENT). | | | APPLICANT MAY PROVIDE DOCUMENTATION FOR VALUATION OTHER | | | THAN PROPERTY APPRAISER; PLEASE SEE FEMA TECHNICAL | | | BULLETIN 758, SECTION 4.5: | | | | | | HTTPS://WWW.FEMA.GOV/MEDIA-LIBRARY-DATA/20130726-1734-2 | | | 5045-2915/P_758_COMPLETE_R3.PDF | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-08-08 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-08-08 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-08-08 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2019-08-08 14:35:51 | PLUMBING COMMEMTS: APPROVED WITH PROVISO | | | PER FBC RES 606.3, SINK SHALL BE INSTALLED WITH THE | | | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 | | | INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR | | | GROUND.SEE REDLINED COMMENT ON A1.7/DETAIL 2A. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-07-11 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-07-11 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-07-11 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2019-07-11 12:32:18 | 2ND REVIEW: 19040126 | | | | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS | | | | | | 1. A MIN OF 1 SINKS IN THE STUDIO ROOMS AND THE BREAK | | | ROOM SINK SHALL COMPLY WITH FBC ACC 212.2/3 AND 606.2/3 | | | SHT. A1.7 SHOWS DETAIL #2A AS COMPLIANT PLEASE INDICATE | | | ON FLOOR PLAN WHICH STUDIO HAS COMPLIANT SINK WITH | | | CLEAR FLOOR SPACE CLEAR OF SHAMPOO STATION. | | | | | | | | | 5. SHT. P1.2 DETAIL FOR WASHING MACHINE BOX AIR HAMMER | | | ARRESTORS REQUIRED AND REPLACE NOTE ON DETAIL CONFORMS | | | TO FBC PL 2017 6TH EDITION NOT 2015 IPC | | | PLEASE NOTE ON WATER ISOMETRIC AIR HAMMER ARRESTOR | | | REQUIRED AT WASHING MACHINE AND QUICK CLOSING VALVES. | | | | | | 6.SHT. P1.3 SPLIT THE WATER AND SANITARY ISOMETRIC | | | DRAWING AND ENLARGE IN ORDER TO DETERMINE CODE | | | COMPLIANCE. PER WPB AMEND TO FBC 107.2.1 | | | LABEL HOT AND COLD AND SHOW DIRECTION OF FLOW ON WATER | | | ISOMETRIC DRAWING. | | | | | | | | | 9. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | | CONFORMS TO ASSE 1070 OR CSA B125.3. PLACE NOT ON WATER | | | ISOMETRIC. PER FBC PL 416.5 | | | VALVE SHOWN ON SHT P1.1 PLUMBING EQUIPMENT SCHEDULE | | | WATTS USG-B-M1 IS NOT LEAD FREE IT SHALL BE LFUSG-B-M1 | | | OR EQUIVALENT | | | | | | NEW COMMENT: | | | | | | 1. LENT TRAP REQUIRED ON WASHING MACHINE DRAIN. PER FBC | | | PL 1003.6 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-05-01 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-05-01 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-04-30 |
Time |
18:06 |
Sent To |
|
|
| Notes |
| 2019-05-01 14:00:09 | 1ST REVIEW: 19040126 | | | | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. A MIN OF 1 SINKS IN THE STUDIO ROOMS AND THE BREAK | | | ROOM SINK SHALL COMPLY WITH FBC ACC 212.2/3 AND 606.2/3 | | | | | | 2. SHT. A1.7 SHOW THE CLEAR FLOOR SPACES WITH | | | DIMENSIONS FOR THE TOILET AND LAVATORY, PER FBC PL | | | 604.3.1 AND 606.2 | | | | | | 3. PLEASE SHOW COMPLIANCE FOR WATER FOUNTAIN PER FBC | | | ACC 602 | | | | | | 4. SHT. A2.0 PLACE NOTE ON PLANS ALL VENT AND EXHAUST | | | SHALL BE A MIN. OF 10' FROM ANY AIR INTAKES. FBC PL | | | 903.5 FBC M 501.3.1 | | | | | | 5. SHT. P1.2 DETAIL FOR WASHING MACHINE BOX AIR HAMMER | | | ARRESTORS REQUIRED AND REPLACE NOTE ON DETAIL CONFORMS | | | TO FBC PL 2017 6TH EDITION NOT 2015 IPC | | | | | | 6.SHT. P1.3 SPLIT THE WATER AND SANITARY ISOMETRIC | | | DRAWING AND ENLARGE IN ORDER TO DETERMINE CODE | | | COMPLIANCE. PER WPB AMEND TO FBC 107.2.1 | | | | | | 7. SHT. P1.3 THE FLOOR DRAINS IN THE BATHROOMS AND IN | | | FRONT OF WASHING MACHINES ARE NOT VENTED PROPERLY THE | | | BUILDING DRAIN IS NOT A VENTED LINE THEY SHOULD CONECT | | | TO WET VENT SYSTEM, BE VENTED SEPARATELY OR VENTED BY A | | | SINK BRANCH THEY CANNOT BE VENTED BY WASHING MACHINE | | | EITHER. PER FBC PL 901.2.1 | | | | | | 8. SHT. P1.3 PLEAS SHOW THE SHUT OFF VALVES ON THE | | | DROPS AS REQUIRED. PER FBC PL 606.1(5) | | | | | | 9. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | | CONFORMS TO ASSE 1070 OR CSA B125.3. PLACE NOT ON WATER | | | ISOMETRIC. PER FBC PL 416.5 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2019-08-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-08-09 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-08-09 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2019-08-09 15:17:49 | DIGITALLY SIGNED DOCUMENTS ADDED TO SIGNATURE FOLDER | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2019-08-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-08-08 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-08-08 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2019-08-08 12:19:07 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THE MEP PAGES ARE NOT DIGITALLY SIGNED. AFTER ALL | | | REVIEWS HAVE PASSED, SUBMIT ONE PAPER ORIGINAL TO THE | | | BUILDING DIVISION, FS471. ALTERNATIVELY, DIGITALLY | | | SIGNED PDFS CAN BE SENT VIA EMAIL. A REVIEW OF THE | | | SUBMITTAL IS REQUIRED PRIOR TO PERMIT ISSUANCE. | | | | | | 2. THE ELEVATION CERTIFICATE AND SURVEY ARE NOT | | | DIGITALLY SIGNED. SUBMIT A PAPER ORIGINAL TO THE | | | BUILDING DIVISION AS SOON AS POSSIBLE. | | | | | | 3. ARCH PAGES AND SUPPORTING DOCUMENTS OK. | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2019-07-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-07-18 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-07-18 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2019-07-18 14:44:42 | NEW ARCH SHEETS DIGITALLY SIGNED ADDED TO SIGNATURE | | | FOLDER 7/18 SH | | | | | | MEP SHEETS NOT DIGITALLY SIGNED - WHEN RESUBMITTING, | | | UPLOAD DIGITALLY SIGNED PLANS. IF DESIGN PROFESSIONAL | | | DOES NOT HAVE A DIGITAL SIGNATURE, ONE PAPER ORIGINAL | | | IS TO BE SUBMITTED TO THE BUILDING DIVISION AFTER ALL | | | REVIEWS HAVE PASSED. A "PLAN REVIEW REQUEST FORM" AND | | | REVIEW OF THE DOCUMENT WILL BE REQUIRED. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2019-05-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-05-20 |
Time |
18:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-05-20 |
Time |
18:08 |
Sent To |
|
|
| Notes |
| 2019-05-20 18:26:12 | MEPS DO NOT HAVE DIGITAL SIGNATURES. | | | BUILDING AND STRUCTURAL AR OKAY. NEW PLANS WILL NEED TO | | | BE CHECKED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-08-08 |
|
|
Cont ID |
|
| Sent By |
hmtribou |
Date |
2019-08-08 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
hmtribou |
Date |
2019-08-08 |
Time |
12:49 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-07-02 |
|
|
Cont ID |
|
| Sent By |
hmtribou |
Date |
2019-07-02 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
hmtribou |
Date |
2019-07-02 |
Time |
09:29 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2019-04-11 |
|
|
Cont ID |
|
| Sent By |
hdanfort |
Date |
2019-04-11 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
hmtribou |
Date |
2019-04-11 |
Time |
16:02 |
Sent To |
I |
|
| Notes |
|
|
|