Plan Review Details - Permit 19040111
| Plan Review Stops For Permit 19040111 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-07-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-07-22 |
Time |
07:01 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-07-22 |
Time |
06:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2019-05-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-05-07 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-05-06 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2019-05-07 10:20:42 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 19040111 | | | ADD: 901 S. FLAGLER DR. / 1ST & 2ND FLOOR REMODEL/ | | | LEVEL I | | | CONT: GREENVIEW CONSTRUCTION | | | TEL: 561-727-5013 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: TUES. MAY 07/ 2019 | | | ACTION: DENIED | | | | | | 1) SHEETS A-301 1ST FLOOR & SHEET A-302 THE 2ND FLOOR | | | INTERIOR FINISHES INDICATE A MERCANTILE OCCUPANCY AND | | | UNSPRINKLERED. PLEASE UPDATE PLANS, THIS IS A BUSINESS | | | OCCUPANCY AND FIRE SPRINKLERED BUILDING. SEE 2017 FBC-B | | | TABLE 803.11. | | | | | | 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-07-23 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-07-23 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-07-22 |
Time |
15:36 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-05-14 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-05-14 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-05-14 |
Time |
10:45 |
Sent To |
I |
|
| Notes |
| 2019-05-14 10:57:08 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE PANEL SCHEDULES INDICATING ANY NEW OR | | | ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE | | | CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE | | | TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, | | | 215.5, 408.4 | | | 2. PROVIDE LIGHTING PLAN WITH DESCRIPTION OF NEW OR | | | RELOCATED LIGHTING, AND THE METHODS OF CONTROLLING THE | | | LIGHTING. WPB FBC 107.2.1 | | | 3. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR | | | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE | | | EQUIPMENT PER CODE. NEC 210.63 | | | 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND | | | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN | | | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE | | | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN | | | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC | | | 105.1, 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-06-25 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-06-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-06-25 |
Time |
15:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2019-04-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-04-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-04-11 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2019-04-11 15:00:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET A 301 - WITHIN THE INTERIOR FINSIHES BOX THERE | | | ARE INCORRECT REFERNECES TO MERCANTILE & | | | NON-SPRINKLERED | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC | | | DETAILS. | | | | | | | | | | | | 2) SHEET A 301 & 302 - THERE ARE NO INDICATIONS OF FIRE | | | SPRINKLER WORK DUE TO RECONSTRUCTION. | | | | | | ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE | | | UNDER SEPARATE PERMIT AND SHOP DRAWINGS BY CERTIFIED | | | FIRE SPRINKLER CONTRACTORS. | | | | | | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF | | | ACKNOWLEDGEMENT. | | | | | | | | | | | | 3) ELECTRICAL SHEETS - THERE ARE NO INDICATIONS OF FIRE | | | ALARM EQUIPMENT OR RELOCATION DUE TO CONSTRUCTION. | | | | | | ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE UNDER | | | SEPARATE PERMIT AND SHOP DRAWINGS BY CERTIFIED FIRE | | | ALARM CONTRACTORS. | | | | | | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF | | | ACKNOWLEDGEMENT. | | | | | | | | | | | | 4) ELECTRICAL SHEETS - THERE ARE NO INDICATIONS OF EXIT | | | SIGN LOCATIONS/INSTALLATIONS THAT COINCIDE WITH THE | | | LIFE SAFETY SHEETS. | | | | | | PLEASE REVIEW AND CORRECT AND/OR NOTE WHETHER EXXISTING | | | OR NEW. | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-07-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-06-21 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2019-07-12 10:25:02 | THIS IS IN C12. | | | | | | | | 2019-06-24 14:46:14 | C11 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-05-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-04-02 |
Time |
15:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2019-05-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2019-05-07 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2019-05-06 |
Time |
11:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2019-07-24 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2019-07-24 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2019-07-24 |
Time |
08:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-07-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-07-17 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-07-17 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2019-07-17 15:00:35 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19040111 | | | 7/17/2019 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET E-102: SUBMIT AN AC CHANGE OUT FORM, AND AN | | | AHRI CERTIICATE FOR THE NEW MINI SPLIT SYSTEM. THE FORM | | | MUST BE SIGNED BY THE MECHANICAL CONTRACTOR OF RECORD- | | | SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2019-05-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-05-03 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-05-03 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2019-05-03 12:39:56 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19040111 | | | 5/3/2019 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) NO MECHANICAL PLANS WERE INCLUDED IN THE SETS. | | | PROVIDE PLANS OR INDICATE "NO MECHANICAL WORK" ON THE | | | PLANS- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
|