Plan Review Details - Permit 19040111
Plan Review Stops For Permit 19040111
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-22 Cont ID  
Sent By jwitmer Date 2019-07-22 Time 07:01 Rev Time 0.00
Received By jwitmer Date 2019-07-22 Time 06:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-07 Cont ID  
Sent By jwitmer Date 2019-05-07 Time 10:20 Rev Time 0.00
Received By jwitmer Date 2019-05-06 Time 11:38 Sent To  
Notes
2019-05-07 10:20:422017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19040111
 ADD: 901 S. FLAGLER DR. / 1ST & 2ND FLOOR REMODEL/
 LEVEL I
 CONT: GREENVIEW CONSTRUCTION
 TEL: 561-727-5013
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 07/ 2019
 ACTION: DENIED
  
 1) SHEETS A-301 1ST FLOOR & SHEET A-302 THE 2ND FLOOR
 INTERIOR FINISHES INDICATE A MERCANTILE OCCUPANCY AND
 UNSPRINKLERED. PLEASE UPDATE PLANS, THIS IS A BUSINESS
 OCCUPANCY AND FIRE SPRINKLERED BUILDING. SEE 2017 FBC-B
 TABLE 803.11.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-23 Cont ID  
Sent By jpearson Date 2019-07-23 Time 08:58 Rev Time 0.00
Received By jpearson Date 2019-07-22 Time 15:36 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By jpearson Date 2019-05-14 Time 10:57 Rev Time 0.00
Received By jpearson Date 2019-05-14 Time 10:45 Sent To I
Notes
2019-05-14 10:57:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULES INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4
 2. PROVIDE LIGHTING PLAN WITH DESCRIPTION OF NEW OR
 RELOCATED LIGHTING, AND THE METHODS OF CONTROLLING THE
 LIGHTING. WPB FBC 107.2.1
 3. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
 4. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-25 Cont ID  
Sent By pleduc Date 2019-06-25 Time   Rev Time 0.00
Received By pleduc Date 2019-06-25 Time 15:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-04-11 Cont ID  
Sent By pleduc Date 2019-04-11 Time   Rev Time 0.00
Received By pleduc Date 2019-04-11 Time 14:47 Sent To  
Notes
2019-04-11 15:00:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 301 - WITHIN THE INTERIOR FINSIHES BOX THERE
 ARE INCORRECT REFERNECES TO MERCANTILE &
 NON-SPRINKLERED
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 DETAILS.
  
  
  
 2) SHEET A 301 & 302 - THERE ARE NO INDICATIONS OF FIRE
 SPRINKLER WORK DUE TO RECONSTRUCTION.
  
 ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS BY CERTIFIED
 FIRE SPRINKLER CONTRACTORS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 3) ELECTRICAL SHEETS - THERE ARE NO INDICATIONS OF FIRE
 ALARM EQUIPMENT OR RELOCATION DUE TO CONSTRUCTION.
  
 ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS BY CERTIFIED FIRE
 ALARM CONTRACTORS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 4) ELECTRICAL SHEETS - THERE ARE NO INDICATIONS OF EXIT
 SIGN LOCATIONS/INSTALLATIONS THAT COINCIDE WITH THE
 LIFE SAFETY SHEETS.
  
 PLEASE REVIEW AND CORRECT AND/OR NOTE WHETHER EXXISTING
 OR NEW.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-07-23 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-21 Time 14:46 Sent To  
Notes
2019-07-12 10:25:02THIS IS IN C12.
  
  
2019-06-24 14:46:14C11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-05-14 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-02 Time 15:47 Sent To  
Notes
2019-04-03 15:47:19C11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-05-07 Cont ID  
Sent By jwitmer Date 2019-05-07 Time 10:20 Rev Time 0.00
Received By jwitmer Date 2019-05-06 Time 11:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-07-24 Cont ID  
Sent By hmoser Date 2019-07-24 Time 08:22 Rev Time 0.00
Received By hmoser Date 2019-07-24 Time 08:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-07-17 Cont ID  
Sent By ccole Date 2019-07-17 Time 14:53 Rev Time 0.00
Received By ccole Date 2019-07-17 Time 14:53 Sent To  
Notes
2019-07-17 15:00:351ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040111
 7/17/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET E-102: SUBMIT AN AC CHANGE OUT FORM, AND AN
 AHRI CERTIICATE FOR THE NEW MINI SPLIT SYSTEM. THE FORM
 MUST BE SIGNED BY THE MECHANICAL CONTRACTOR OF RECORD-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-03 Cont ID  
Sent By ccole Date 2019-05-03 Time 12:37 Rev Time 0.00
Received By ccole Date 2019-05-03 Time 12:34 Sent To  
Notes
2019-05-03 12:39:561ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040111
 5/3/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS WERE INCLUDED IN THE SETS.
 PROVIDE PLANS OR INDICATE "NO MECHANICAL WORK" ON THE
 PLANS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  