Plan Review Details - Permit 19040101
Plan Review Stops For Permit 19040101
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-09 Cont ID  
Sent By jleahy Date 2019-05-09 Time 09:18 Rev Time 0.00
Received By jleahy Date 2019-05-09 Time 09:18 Sent To  
Notes
2019-05-09 09:24:29FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR THE WORK SHOWN IS LOW
  
 PLEASE SUBMIT A SIGNED CONTRACT WITH OWNERS SIGNATURE
 FOR REVIEW
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) POWER UNIT USES 120 VOLTS YOU NEED AN ELECTRICAL
 PERMIT FOR THIS WORK. NOT IN THE SCOPE OF AN EF.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2019-05-09 Cont ID  
Sent By jleahy Date 2019-05-09 Time 09:25 Rev Time 0.00
Received By jleahy Date 2019-05-09 Time 09:25 Sent To  
Notes
2019-05-09 09:26:26COULD NOT VERIFY SIGNATURE JLEAHY